39 Lorilet 05 Bushfire Hazard Overlay Code
Performance outcomes Acceptable outcomes
PO3 AO3.1 Existing firefighting water supply is
Development provides an adequate water supply Premises are connected to the reticulated water supply. established in the area since approximately
for fire fighting purpose which is reliable, safely mid-1980s.
located and freely accessible. Editor's note—For reconfiguring a lot, water supply
needs to provide for a minimum flow and pressure of 10
litres a second at 200kPa at all times for fire fighting
purposes.
OR
AO3.2 Not applicable.
Where there is no available reticulated water supply, the
premises has:
1. an accessible dam, swimming pool or water
tank available for fire fighting purposes
with an onsite water volume of not less
than 5,000 litres; and
2. a water supply outlet pipe 50 millimetres in
diameter fitted with a standard fire brigade
fitting connected to the water supply (other
than where the water supply is in a
swimming pool or dam).
Editor’s Note—Water supply capacity for fire fighting
purposes is in addition to water supply capacity for other
uses and activities on the premises.