Original source · versioned page text
QC100259_Pomona Exchange_DD_Rev01-220630
Attached to the e-mail Operational Works Application OP"W22/0174 - DA Form 1 & 2 - Plans - 25 Railway Pde, Pomona.
1 2 3 4 5 6
A A
BACK PLATE TO SUPPORT
METER PANEL, DISTRIBUTION
BOARD AND FIBRE BOX,
SHALL BE MINIMUM
1500mm WIDE x 800mm HEIGHT
2
UNISTRUT STIFFENER TO BE
INSTALLED FROM AN OFF CUT
B FROM THE CABLE UNISTRUTS B
H-FRAME INSTALLED IN
ACCORDANCE WITH
MANUFACTURER SPECIFICATIONS
1
625
725
1 MIN 100 THICK COMPOUND FINISH
C C
FINISHED GRADE
3
PREPARE GROUND BELOW PLATFORM
FEET IN ACCORDANCE WITH SHEET T2
NOTES G3, G4 & G5.
GROUND PREPARATION SHALL BE
D EQUIPMENT PLATFORM - H-FRAME DETAIL COMPLETED BELOW PLATFORM FEET TO
ACHIEVE 150kPa ALLOWABLE VERTICAL H-FRAME FOUNDATION D
NTS SCALE: 1:20
BEARING CAPACITY
CLIENT EQUIPMENT KEYED NOTES:
1 FIBRE INTERFACE PANEL
E E
2 OAN CABINET W/ EXTERNAL AC UNIT
3 EQUIPMENT GROUND BAR
FOR CONSTRUCTION
THIS SHEET TO BE READ IN CONJUNCTION WITH SHEET T2.
ELECTRICAL SITE EQUIPMENT KEYED NOTES: ORDER DRAWN CHKD AMENDMENT EXAM APPD DATE ISS
183929 JM MF FOR CONSTRUCTION - SP30092467WO015DOWN - SATELLITE RC PG 17.06.22 0.1
1 100A DISTRIBUTION BOARD WITH INTERNAL SURGE
PROTECTION DEVICE SATELLITE ACCESS NODE SITE 183929
COMPLIANCE BOX POMONA EXCHANGE
COMPLETED AS PER DESIGN
F EQUIPMENT PLATFORM - H-FRAME DETAIL F
ALTERATIONS IN RED 25 RAILWAY PARADE, POMONA, QLD 4568
NAME (PRINT)
DWG SHT T2-1
SIGNATURE DATE
C Telstra Corporation Limited ABN 33 051 775 556 All rights reserved. NO. QC100259 NO. .
1 2 3 4 5 Cad file: QC100259.dwg A3
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
Large file: the download may take up to a minute.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.