SURFACE WATER MANAGEMENT PLAN J) Cara/no
5. IRRIGATION TANK SIZING
I Historical rainfall data was obtained for Noosa for the period between 1950 and 2002. A
yield analysis was conducted, applying the rainfall to the building roof area (accounting for
a first flush loss of 0.2mm and an initial loss of 1 mm) to estimate the daily inflow to the tank.
The roof area was assumed to be 4600 m2, derived from initial design drawings. In many
instances, the fall of the roof and surrounding ground levels dictate that not all of the
rainwater can be practicably harvested - for this reason a 'half-sized' roof of 2300m2 was
also modelled.
Demands of 2500, 3000 and 3500 litres per day were used. Over a nursery area of
approximately 1000 m2, this equates to an irrigation rate of about 2.5, 3.0 and 3.5 mm per
day.
The model provides an estimate of the demand supplied, expressed as a percentage of the
total volume required. Note that it is not a percentage of total time the demand is supplied
- although this figure will be similar. The results are shown in Table 13 below.
Table 13 Rainwater Tank Performance
Demand supplied (%) for each tank size (kL)
D eman d : roo f area
10 20 30 40 50 60 70 80 90 100 150 200
2500 Lpd:4600m2 64 79 87 91 94 95 96 97 98 99 100 100
74
r
3000 Lpd : 4600m2 59 83 88 91 93 94 96 96 97 99 100
3500 Lpd 4600m2 56 70 79 84 88 91 92 94 95 96 98 99
2500 Lpd:2300m2 60 75 83 87 90 92 94 95 96 97 99 100
3000 Lpd:2300m2 55 70 78 83 86 89 91 92 93 94 97 99
i7 3500 Lpd2300m2 52 65 73 78 82 85 87 89 90 91 95 97
The results are better presented as a graph, as follows:
Rainwater Tank Performance
2500 Lpd, full roof
3000 Lpd, full roof
3500 Lpd, full roof
2500 Lpd, half roof
3000 Lpd. half roof
3500 Lpd, half roof
55
50
0 50 100 150 200
Tank Size (kL)
Bunnings Warehouse Version 1 15 December 2006
J\3501-54\WP\S'WMPdoc Commercial in Confidence Page 14
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
OPW11/0023 Development Application part 2 of 2 Planning Report and Plans 178 Eumundi Noosa Road NoosavilleRelated documentApplication case desk ↗
About this file
- File size
- 70.0 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.