     BUNNINGS WAREHOUSE, NOOSAVILLE
     SURFACE WATER MANAGEMENT PLAN                                                        (4:^ Car-dna

F1                For the purposes of the modelling, sensible device parameters based on outline quantity
                  calculations were input to the model, as described in the table below. If the layout of the
                  site changes in future these can be amended to suit, providing that the overall effectiveness
                  is maintained. The bio-retention device is modelled as a single large device, for example,
                  where in fact several smaller devices of equal total capacity would be employed in the car
                  park landscaping divides around the site.

                  Table 11        Bioretention Device Parameters

                    Parameter                                                     Value

                    Surface Area (m)                                               860
                    Extended Detention Depth (m)                                   0.1

                    Filter Area (m)                                                860

                    Filter Depth (m)                                               0.5

                    Mean Particle Diameter (mm)                                    0.36

                    Saturated Hydraulic Conductivity (mm/hr)                       180
                    Overflow Weir Width (m)                                         2


                  Rainwater tanks provide some reduction in nitrogen loads, thought to be via biofilm activity
                  within the tank. The reduction in overall runoff through storage and reuse will also minimise
                  loads at the site outlet. To enable a conservative quality assessment, only a nominal
                  rainwater tank size was used, having a volume of 18kL and a surface area of 8m2. A
                  realistic re-use demand of 1250kL per year was applied. This size is conservative given
                  the likely rainwater tank size to be adopted (refer Section 5).

                  4.8            Modelling Results
                  The results of the MUSIC modelling, shown as total annual loads, are presented in the
                  table overleaf. It can be seen from the tables that the treatment train would reduce all of
                  the total loads released from the developed site to such an extent that the target reductions
                  are achieved for all pollutants.

                  Table 12        Total Annual Loads

                                              Total Suspended             Total             Total       Total Gross
                              Situation
                                                   Solids              Phosphorus          Nitrogen      Pollutants

                          Existing Site

t                         (Rural Res)

                          Development
                           Potential
                                                 3,000 kg/yr


                                                 6,880 kg/yr
                                                                          6.27 kg/yr


                                                                          18.5 kg/yr
                                                                                           34.1 kg/yr


                                                                                           106 kg/yr
                                                                                                          196 kg/yr


                                                                                                          683 kg/yr

                      Development with
                                                 1240 kg/yr               5.20 kg/yr       54.8 kg/yr      0 kg/yr
                       treatment train

                     Realised Reduction             82 %                    72 %             48 %          100 %

                     Target      Reduction          80 %                    60 %             45 %           90 %

                  Note that the proposed development, owing to its water sensitive urban design
                  measures, produces lower annual pollutant loads than the existing rural residential
                  case, for most of the modelled pollutants.


I
'    Bunnings Warehouse                                       Version 1                                 15 December 2006
     J \3501 541WP15WMP doc                            Commercial in Confidence                                 Page 13

Used in these records

About this file

File size
70.0 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

OPW11_0023 Development Application part 2 of 2 Planning Report and Plans 178 Eumundi Noosa Road Noosaville.pdf · 70.0 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.