2.2.1.2 Defined Flood Levels and Flood Immunity
An assessment was completed to identify if the proposed buildings associated with the development will achieve the required 0.5m
freeboard. Table 2.5 provides a summary of the floor levels along with associated defined flood level, freeboard provided and if it achieves
the minimum 0.5m freeboard (SC6.7.5 Specific Design and Construction Requirements – Clause (2) (m) (iv)). When reviewing the results,
each building achieves the minimum freeboard required. It is noted that FFL2 achieves its freeboard through the inclusion of a wall (approx.
1m high) to contain flows within the flow path. Figure 2.5 provides an overview of finished floor levels, top of wall levels and defined flood
height (i.e. 1% (2100) AEP).
TABLE 2.5: SUMMARY OF FINISHED FLOOR LEVELS AND FLOOD IMMUNITY.
Section Finished Floor Level Top of Wall (m AHD) DFL (m AHD) Freeboard Achieved Min 0.5m Freeboard
(m AHD) (m) Achieved
FFL1 18.60 - 18.05 0.55 ✓
FFL2 17.75 18.75* 17.80 0.95 ✓
FFL3 18.25 - 17.55 0.70 ✓
FFL4 18.0 - 17.49 0.51 ✓
FFL5 18.0 - 17.22 0.78 ✓
FFL6 19.0 - 17.01 1.99 ✓
Foot Bridge 18.90 - 16.92 1.98 ✓
* The flood immunity to this building is provided by an impervious wall.
DocumentNOOSA
Set ID:CALILE I BBNE01676-0001-REP-001-1
23806878 11
Version: 0, Version Date: 01/01/1900
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.