Q7877 UW SAN Report, 73, 75 & 77 Eumundi Noosa Road & 2C, 2D, 2E Starboard Avenue, Noosaville, QLD 4566 · MCU24/0125
Mailing Address: PO Box 953, Caboolture QLD 4510 e@ Customer Service Centres: 33 King Street, Caboolture QLD 4510 6-10 Maud Street, Maroochydore QLD 4558 Unitywater 1300 0 UNITY (1300 086 489) , aehiing you today, ABN: 89 791 717 472 investing in tomorrow. Our ref: A8567537 PF / SR812961994/2024 Mr Daniel Barwick HTC Group Australia Pty Ltd PO Box 89 Ashgrove Qld 4060 Email: [email protected] 28 November 2024 Dear Mr Barwick Network Pressure and Flow Data — Request for information — Lot 1-2-3-48-49-50 $P298783 situated at 73-75-77 Eumundi Noosa Road and 2C-2D-2E Starboard Avenue Noosaville Queensland. | refer to your application received by Unitywater in which you request pressure and flow data for the above property. Minimum Standard of Service In accordance with Queensland Government Guidelines Unitywater designs, constructs, operates and maintains its water supply network to provide the following minimum standard of service a 2/3 of the calculated maximum hour demand on the peak day: Table 1 — Minimum Standard of Service Flow Available from Unitywater’s Water Main for Fire Fighting Purposes (litres/second) Residual Head in Water Main Servicing the Use (metres) Type of Use Residential including multi — storey residential dwellings of 15 12 less than 3 storey Commercial that is ancillary to . : 15 12 residential use Multi-storey residential greater 30 12 than 3 storey Commercial and or Industrial 30 12 Page 1 of 3 Unitywater is a statutory authority that provides water and £\ FX F&F FR Unitywater has certification to: Unityw . . fost: dest £ & feck OH&S AS/NZS 4801:2001 Reg No 500000079 - sewerage services for the Moreton Bay, Sunshine Coast NATA Lay Ree Ritey A ese Environmental ISO 14001:2015 Reg No 500000079 + SWE and Noosa Council areas. Quality ISO 9001:2015 Reg No 500000079 and Nc Food Safety ISO 22000:2018 Reg No 500000079
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 2 pages
Page 2
e Unitywater Serving you today, investing in tomorrow. Unitywater does not guarantee that firefighting flow will be available at all times on the grounds that components of Unitywater’s water supply infrastructure may be shut down temporarily for planned maintenance or to repair bursts or damage caused by others. The current type of use for this property is Residential including multi-storey residential dwellings of less than 3 storey; according to Council’s Planning scheme. Hence, in accordance with Table 1 above, the Minimum Standard of Service that applies is 15 litres/second at 12 m residual head. Current Dynamic Model Data Unitywater’s current dynamic water supply model indicates the following under a demand condition of 2/3 of the estimated maximum hour demand on the peak day in Year 2026. Table 2 — Estimated Available Flow and Pressure to 2026 Assessment Node Water Main Background Estimated RL at (Location as shown below) | Diameter (mm) | Demand (L/s) | Assessment node(mAHD) Hyd 5015687 100 0 14.0 Flow (I/s) 0 10 15 20 Pressure (m) 44.8 42.5 40.7 38.4 Unitywater reserves the right, at any time, to change the operating pressures3.9 within the water supply network, but not below the Minimum Standard of Service stated in Table 1. Unitywater accepts no liability whatsoever for changes in the operating pressure of this water supply network and the consequent impacts on any fire suppression system within the subject property. It shall be the property owner’s responsibility to ensure that any fire suppression system operating on the property complies with the relevant requirement of the Building Code of Australia and that this system is regularly tested for compliance with the relevant standards. Any upgrade of the fire suppression system required due to changes in the operating pressure of the water supply network will be the property owner’s responsibility. Suggested Approach to Design of Fire Suppression System It is suggested that the owner of the property consult with a qualified and suitably experienced hydraulic designer to consider the risks associated with designing a fire suppression system for the subject property based upon the output from Unitywater’s current dynamic water supply model. Unitywater may alter the operating pressure of the network at any time. Page 2 of 3 Unitywater has certification to: OH&S AS/NZS 4801:2001 Reg No 500000079 Environmental ISO 14001:2015 Reg No 500000079 Quality ISO 9001:2015 Reg No 500000079 Food Safety ISO 22000:2018 Reg No 500000079 Unitywater is a statutory authority that provides water and sewerage services for the Moreton Bay, Sunshine Coast and Noosa Council areas.
Page 3
e Unitywater Serving you today, investing in tomorrow. It is suggested that this risk should be balanced against the cost of designing and installing a fire suppression system that would provide the desired level of performance when supplied with water from Unitywater’s mains at the Minimum Standard of Service stated in Table 1. It may be beneficial to consider providing space and conduits on the subject property that could be utilised for installation of storage tanks and or pumping equipment and associated electrical equipment in the instance that an upgrade of the fire suppression system was necessary in the future. Further Information Please note that the Flow and Pressure details given in this letter is based ona dynamic model run and not from a physical hydrant test Should you require clarification of the foregoing please contact Unitywater on 1300 086 489 during business hours or by email to [email protected] sincerely a Asoka Kiriella Unit Leader Network Planning Node Location map ( Node H2) 95th percentile here Page 3 of 3 Unitywater is a statutory authority that provides water Unitywater has certification to: y tory y Pp A TS fy eS OH&S AS/NZS 4801:2001 Reg No 500000079 and sewerage services for the Moreton Bay, Sunshine NATA Rey RSF ey Environmental ISO 14001:2015 Reg No Coast and Noosa Council areas. 500000079 Quality ISO 9001:2015 Reg No 500000079 Food Safety ISO 22000:2018 Reg No 500000079
Used in these records
Q7877 UW SAN Report, 73, 75 & 77 Eumundi Noosa Road & 2C, 2D, 2E Starboard Avenue, Noosaville, QLD 4566.pdfRelated documentApplication case desk ↗
About this file
- File size
- 591 KB (small file)
- File type
No other editions are linked here.