Skip to the record
Accept no imitations.

Council archive · source document

Q7877 UW SAN Report, 73, 75 & 77 Eumundi Noosa Road & 2C, 2D, 2E Starboard Avenue, Noosaville, QLD 4566 · MCU24/0125

of 3

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

e
Unitywater

Serving you today,
investing in tomorrow.

Unitywater does not guarantee that firefighting flow will be available at all times on the grounds
that components of Unitywater’s water supply infrastructure may be shut down temporarily for
planned maintenance or to repair bursts or damage caused by others.

The current type of use for this property is Residential including multi-storey residential
dwellings of less than 3 storey; according to Council’s Planning scheme. Hence, in accordance
with Table 1 above, the Minimum Standard of Service that applies is 15 litres/second at 12 m
residual head.

Current Dynamic Model Data

Unitywater’s current dynamic water supply model indicates the following under a demand
condition of 2/3 of the estimated maximum hour demand on the peak day in Year 2026.

Table 2 — Estimated Available Flow and Pressure to 2026

 

Assessment Node Water Main Background Estimated RL at
(Location as shown below) | Diameter (mm) | Demand (L/s) | Assessment node(mAHD)

 

 

 

 

 

 

 

 

 

Hyd 5015687 100 0 14.0
Flow (I/s) 0 10 15 20
Pressure (m) 44.8 42.5 40.7 38.4

 

 

 

 

Unitywater reserves the right, at any time, to change the operating pressures3.9 within the
water supply network, but not below the Minimum Standard of Service stated in Table 1.

Unitywater accepts no liability whatsoever for changes in the operating pressure of this water
supply network and the consequent impacts on any fire suppression system within the subject
property. It shall be the property owner’s responsibility to ensure that any fire suppression
system operating on the property complies with the relevant requirement of the Building Code
of Australia and that this system is regularly tested for compliance with the relevant standards.
Any upgrade of the fire suppression system required due to changes in the operating pressure
of the water supply network will be the property owner’s responsibility.

Suggested Approach to Design of Fire Suppression System

It is suggested that the owner of the property consult with a qualified and suitably experienced
hydraulic designer to consider the risks associated with designing a fire suppression system
for the subject property based upon the output from Unitywater’s current dynamic water supply
model. Unitywater may alter the operating pressure of the network at any time.

Page 2 of 3
Unitywater has certification to:

OH&S AS/NZS 4801:2001 Reg No 500000079
Environmental ISO 14001:2015 Reg No
500000079

Quality ISO 9001:2015 Reg No 500000079

Food Safety ISO 22000:2018 Reg No 500000079

Unitywater is a statutory authority that provides water
and sewerage services for the Moreton Bay, Sunshine
Coast and Noosa Council areas.

 

 

Used in these records

About this file

File size
591 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Q7877 UW SAN Report, 73, 75 & 77 Eumundi Noosa Road & 2C, 2D, 2E Starboard Avenue, Noosaville, QLD 4566.pdf · 591 KB (small file)