Plans 19 The Peninsula Jetty_signed · MCU22/0017

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn
                                                                                                            GENERAL                                                                                                           DIMENSIONS/LEVELS                                                                                                    CONSTRUCTABILITY CONSTRAINTS:
                                                                                                            G1    STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH THE                                                   L1.       CONSTRUCTION SHALL BE SET OUT USING SURVEY BENCHMARKS PROVIDED BY COUNCIL.                                 CC1. CONSTRUCTABILITY CONSTRAINTS:
                                                                                                                  SPECIFICATION, ARCHITECTURAL, AND OTHER CONSULTANTS' DOCUMENTS.
                                                                                                                                                                                                                              L2. ALL LEVELS AND SETOUT POINTS ARE SHALL BE CONFIRMED ON SITE BY REGISTERED                                             A)   PROTECT ALL EXISTING INFRASTRUCTURE (EG CULVERT CROSSING, PAVEMENTS,
                                                                                                            G2    REFER TO THE ARCHITECTURAL DRAWINGS FOR SETOUT. NO DIMENSIONS SHALL BE                                      SURVEYOR PRIOR TO CONSTRUCTION. ADVISE ANY DISCREPANCY BEFORE PROCEEDING.                                                      FENCING & ELECTRICAL POLES/WIRES) FROM ANY DAMAGE.
                                                                                                                  OBTAINED BY SCALING FROM DRAWINGS.
                                                                                                                                                                                                                              L3.       DIMENSION STANDARDS:                                                                                         B)      ALLOW OF LIKELIHOOD OF FLOW WITHIN THE WATERWAY: EXISTING WATERWAY ARE
                                                                                                            G3    UNLESS OTHERWISE NOTED (UNO), ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN                                      - REDUCED LEVELS, CHAINAGES AND COORDINATES ARE ALL IN METRES.                                                       FLOODED MULTIPLE TIMES PER YEAR. PROTECT CONSTRUCTION EQUIPMENT AND
                                                                                                                  MILLIMETRES.                                                                                                          - CIVIL DRAWINGS (SKC SERIES): ALL OTHER DIMENSIONS ARE IN METRES (m).                                               WORKS.
                                                                                                                                                                                                                                        - STRUCTURAL DRAWINGS (SKS SERIES): ALL OTHER DIMENSIONS ARE IN MILLIMETRES (mm).
                                                                                                            G4    THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF THE                                                                                                                                                         CC2. NO WORK TO COMMENCE ON SITE UNTIL:
                                                                                                                  STRUCTURE UNTIL ITS COMPLETION AND SHALL ENSURE THAT NO PART OF THE STRUCTURE                               L4.       ALL LEVELS ARE TO AUSTRALIAN HEIGHT DATUM.                                                                      - OFFICIAL PRE-START MEETING HELD AND PRE-START MEETING MINUTES ISSUED
                                                                                                                  IS OVER-STRESSED BY EXCESSIVE LOADING.                                                                                                                                                                                                - CONTRACTOR'S MANAGEMENT PLANS SUBMITTED (SITE, TRAFFIC, ENVIRONMENT,
                                                                                                                                                                                                                              L5.       DIMENSIONS SHALL NOT BE SCALED FROM DRAWINGS.                                                                   SAFETY) FOR SUPERINTENDENT'S REVIEW.
                                                                                                            G5    ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE CURRENT VERSION
                                                                                                                  OF THE APPLICABLE STANDARD EXCEPT WHERE VARIED BY THE SPECIFICATION AND/OR                                  L6.       DESIGN USES DIGITAL TERRAIN MODEL GENERATED FROM THE SITE SURVEY. SOME                                     DRIVEN PILES:
                                                                                                                  DRAWINGS. APPLICABLE CODES OF PRACTICE INCLUDE BUT ARE NOT LIMITED TO THE                                             ELEMENTS ARE INTERPOLATED AND MAY VARY FROM THE ACTUAL SITE CONDITIONS
                                                                                                                  FOLLOWING:                                                                                                                                                                                                                       P1.       PILES SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS2159.
                                                                                                                  AS 1163        STRUCTURAL STEEL HOLLOW SECTIONS
                                                                                                                  AS 1170        SAA LOADING CODE                                                                             DESIGN CRITERIA
                                                                                                                                                                                                                                                                                                                                                   P2.       CONSTRUCTION CONSTRAINTS: AVOID LOADING EXISTING REVETMENT WALLS.
                                                                                                                  AS 1289        METHODS OF TESTING SOILS FOR ENGINEERING PURPOSES
                                                                                                                  AS 1554        WELDING OF STEEL STRUCTURES                                                                  DC1 THE STRUCTURAL ELEMENTS HAVE BEEN DESIGNED FOR THE FOLLOWING LIVE LOADS
                                                                                                                                                                                                                                                                                                                                                   P3.       DESIGN LOADS: PILES TO ACHIEVE GEOTECHNICAL CAPACITIES (VERTICAL &
                                                                                                                  AS 1664        ALUMINIUM STRUCTURES                                                                             IN ACCORDANCE WITH AS 1170.1: LIVE LOAD REDUCTIONS ARE NOT APPLICABLE.
                                                                                                                                                                                                                                                                                                                                                             HORIZONTAL) SHOWN ON THE DRAWINGS
                                                                                                                  AS 1684        RESIDENTIAL TIMBER-FRAMED CONSTRUCTION                                                           ELEMENT            UDL         CONCENTRATED
                                                                                                                  AS 1720        TIMBER STRUCTURES                                                                                ROOF               0.25 kPa    1.1KN
                                                                                                                                                                                                                                                                                                                                                   P4.       REQUIRED PILE POSITION TOLERANCES:
                                                                                                                  AS 2159        PILING CODE                                                                                      INTERNAL FLOORS    1.5kPa
                                                                                                                  AS 4100        STEEL STRUCTURES                                                                                 DECK               2.0kPa
                                                                                                                                                                                                                                                                                                                                                             PLAN POSITION: +/- 50mm AT UNDERSIDE OF EACH GROUND BEAM.
                                                                                                                  AS 5100        BRIDGE DESIGN                                                                                    THOROUGHFARES      4.0 kPa
                                                                                                                                                                                                                                                                                                                                                             PILE VERTICALITY:
                                                                                                                  BCA            BUILDING CODE OF AUSTRALIA (NATIONAL CONSTRUCTION CODE)                                                                                                                                                                     - WITHIN 4% FOR ALL PILES
                                                                                                                                                                                                                              DC2 WIND LOADS HAVE BEEN DETERMINED IN ACCORDANCE WITH AS 1170.2 BASED ON:
                                                                                                            G6    ANY DISCREPANCY SHALL BE REFERRED TO THE SUPERINTENDENT FOR A DECISION BEFORE                                   IMPORTANCE LEVEL            2
                                                                                                                                                                                                                                                                                                                                                   P5.       PILE TOE LEVELS ON THE DRAWINGS ARE ESTIMATED LEVELS. ACTUAL TOE LEVELS
                                                                                                                  PROCEEDING WITH THE WORK.                                                                                       REGION                      N4
                                                                                                                                                                                                                                                                                                                                                             SHALL BE DETERMINED DURING CONSTRUCTION BY AN RPEQ-CERTIFIED
                                                                                                                                                                                                                                  ULTIMATE WIND SPEED         61 m/s
                                                                                                                                                                                                                                                                                                                                                             GEOTECHNICAL ENGINEER.
                                                                                                            G7  ALL PROPRIETARY PRODUCTS NOT DEEMED TO COMPLY WITH THE BCA SHALL HAVE                                             SERVICEABILITY WIND SPEED   39.0 m/s
                                                                                                                THIRD-PARTY CERTIFICATION WITH RELEVANT TESTING AND SIGN-OFF BY AN RPEQ ENGINEER.                                 TERRAIN CATEGORY            2
                                                                                                                                                                                                                                                                                                                                                   P6.       DO NOT FOUND PILES HIGHER THAN TOE LEVELS ON DRAWINGS, UNLESS APPROVED BY
                                                                                                                PROPRIETARY PRODUCTS INCLUDES PREFABRICATED TRUSSES, LIGHT-GAUGE STEEL                                                                                                                                                                       BOTH THE SUPERINTENDENT AND THE GEOTECHNICAL ENGINEER. THE
                                                                                                                FRAMING, FLOORING PRODUCTS, RECYCLED TIMBER AND PLASTICS, BALUSTRADES, SCREENS, DC3 EARTHQUAKE LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 1170.4 BASED                                                                                SUPERINTENDENT SHALL SEEK ADVICE FROM THE DESIGN ENGINEER AS REQUIRED.
                                                                                                                SHADE FABRICS, JOINERY, PARTITIONS AND OPERABLE WALLS.                                ON:
                                                                                                                                                                                                      ACCELERATION COEFFICIENT     0.06
                                                                                                            G8 REFER TO ARCHITECTS DRAWINGS FOR DETAILS OF ALL GROOVES, FILLETS, HOBS, DRIP           SITE FACTOR                  1
                                                                                                                GROOVES AND THE LIKE.                                                                 IMPORTANCE LEVEL             1
                                                                                                                                                                                                      STRUCTURE TYPE
                                                                                                            G9  GIVE AT LEAST 24 HOURS NOTICE OF AN INSPECTION BEING REQUIRED FOR :                   DESIGN CATEGORY              EDC1
                                                                                                                - PILING
                                                                                                                - JETTY FRAMING (TIMBER)                                                          DC4 FIRE RESISTANCE LEVELS OF STRUCTURAL ELEMENTS HAVE BEEN TAKEN AS FOLLOWS:
                                                                                                                - BRACING AND TIE DOWN                                                                ELEMENT       FRL (mins)
                                                                                                                                                                                                      COLUMNS        -/-/-
                                                                                                            G10 ALL FABRICATION SHOP DRAWINGS SHALL BE PROVIDED TO THE ENGINEER FOR REVIEW AND        BEAMS          -/-/-
                                                                                                                COMMENT IN A3 HARDCOPY OR PDF FORMAT.                                                 WALLS          -/-/-
File: C:\- A Projects\00 - Black & More\7882 - 19 The Peninsula Jetty\ 7882- Notes Sheet.dwg




                                                                                                            G11   ABBREVIATIONS (GENERAL):                                                                                    DC5 DETERMINATION OF DESIGN LOADING FOR NON-STRUCTURAL ELEMENTS SUCH AS
                                                                                                                  NTS      NOT TO SCALE                                                                                           CEILING AND CLADDING SYSTEMS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR
                                                                                                                  UNO      UNLESS NOTED OTHERWISE
                                                                                                                  NSOE     NOT SHOWN ON ELEVATION                                                                             DC6 FLOOD LOADING HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5100 WITH NOMINAL
                                                                                                                  NSOP     NOT SHOWN ON PLAN                                                                                      FLOOD VELOCITY TO BE CONFIRMED BY HYDRAULIC REQUIREMENTS AS FOLLOWS:
                                                                                                                  TYP      TYPICAL                                                                                                -V100 = 1m/s.
                                                                                                                  (O)      OVER
                                                                                                                  (U)      UNDER                                                                                              TEMPORARY WORKS:
                                                                                                                  CRS      CENTRES
                                                                                                                  NOM      NOMINAL
                                                                                                                                                                                                                              T1.       MAINTAIN THE WORKS IN A SAFE CONDITION. ENSURE STRUCTURES ARE NOT
                                                                                                                  CFW      CONTINUOUS FILLET WELD
                                                                                                                                                                                                                                        OVER-STRESSED AT ANY TIME. TEMPORARY ROAD SURFACES SHALL BE TRAFFICABLE
                                                                                                                                                                                                                                        AT ALL TIMES. POTHOLES ETC SHALL BE MONITORED AND REPAIRED.


                                                                                                                                                                                                                              T2.       CONTRACTOR'S RPEQ TO CERTIFY DESIGN AND CONSTRUCTION FOR TEMPORARY
                                                                                                                                                                                                                                        WORKS: STRUTS, PROPPING, FORMWORK STRIPPING AND PROPPING PROCEDURES, TIE
                                                                                                                                                                                                                                        BACKS, EXCAVATION SHORING, PROTECTION WORKS, DE-WATERING SYSTEMS,
                                                                                                                                                                                                                                        FORMWORK, EARLY LOADING OF STRUCTURES AND THE LIKE.
Printed: 08 November 2021, 6:28 AM




                                                                                                                                                                                                                                                                                                                                                                                                                                          FOR CONSTRUCTION
                                                                                                                                                                                    R.P. DATA                       © Black & More                                                                           Client                               Project                                                  Drawing Title
                                                                                                                                                                                    LOT:    267                     This document is and shall remain
                                                                                                                                                                                                                                                                         Black & More
                                                                                                                                                                                                                                                                         ABN 19 609 960 232
                                                                                                                                                                                                                                                                                                                        ANDREW HAY           PROPOSED JETTY
                                                                                                                                                                                    RP:     856191                  the property of Black & More.                                                            Address
                                                                                                                                                                                                                                                                                                                        19 THE PENINSULA NOOSA WATERS                                                       GENERAL NOTES - SHEET 1 OF 2
                                                                                               Revisions




                                                                                                                                                                                                                    This document may only be used                       7 / 28 Sunshine Beach Road,
                                                                                                                                                                                    19 THE PENINSULA NOOSA WATERS                                                        Noosa Heads QLD. 4567
                                                                                                                                                                                                                    for the purposes for which it was
                                                                                                                                                                                                                    commissioned and in accordance                       PO Box 611, Noosa Heads QLD. 4567   Drawn            Drawing        Approved                               Date    12/11/21
                                                                                                                                                                                    Client:                         with the Terms of Engagement for
                                                                                                                                                                                                                                                                         Telephone (07) 5447 4444
                                                                                                                                                                                                                                                                                                                         ST   Check     JB
                                                                                                                                                                                    ANDREW HAY                      the commission. Unauthorised use                                                                                                                                                       Drawing Size Scale (A3 size)     Drg No                Revision
                                                                                                           C1 CONSTRUCTION ISSUE                                                                                                                                                                                                                                                      RPEQ 23058
                                                                                                           No.                         Description       Reviewed Approved   Date
                                                                                                                                                                                                                    of this document in any form
                                                                                                                                                                                                                    whatsoever is prohibited.
                                                                                                                                                                                                                                                                         Email
                                                                                                                                                                                                                                                                         Internet
                                                                                                                                                                                                                                                                                   [email protected]
                                                                                                                                                                                                                                                                                   www.blackm.com
                                                                                                                                                                                                                                                                                                             Designed
                                                                                                                                                                                                                                                                                                                         JB
                                                                                                                                                                                                                                                                                                                              Design
                                                                                                                                                                                                                                                                                                                              Check     SS    Drawing is not to be used for construction unless approved      A3             NOT TO SCALE            7882- S002    C1
                                                                                               External References:    B&M-JETTY-TITLE-A3_e.dwg

Used in these records

About this file

File size
1.2 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Plans 19 The Peninsula Jetty_signed.pdf · 1.2 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.