Plans 19 The Peninsula Jetty_signed · MCU22/0017

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn
                                                                                                            TIMBER FRAMING & BRACING:                                                                                                                                                                                                ALUMINIUM:
                                                                                                            T1    ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS 1720, AS 1684                                        MINIMUM SPACING, EDGE & END DISTANCES FOR NAILS AND SCREWS                                       A1.    ALL WORKMANSHIP AND MATERIALS SHALL COMPLY WITH BEST PRACTISE ALUMINIUM
                                                                                                                  AND THE REFERENCED STANDARDS THEREIN.                                                                                                                                                                                     FABRICATION AND THE CURRENT AUSTRALIAN STANDARD AS 1664.
                                                                                                                                                                                                                                                           MINIMUM DISTANCE                                                          A2.    ALUMINIUM SECTIONS SHALL COMPLY WITH AS 1734, AS 1886 OR AS 1867.
                                                                                                            T2    ALL FRAMING, BRACING AND TIE-DOWN INFORMATION FORMS THE BASIS OF THE                                                                                                                                               A3.    ALL WELDING SHALL COMPLY WITH AS 1665.
                                                                                                                  STRUCTURES STABILITY DOWN TO FOUNDATIONS. ALTERNATIVE METHODS SHALL                                                SPACING TYPE          HOLES FOR      HOLES FOR                                                  A4.    ALL WELDING SHALL BE CARRIED OUT USING ARGONGAS SHIELDING. WELD
                                                                                                                  ONLY BE ACCEPTED ON APPROVAL OF THE ENGINEER.                                                                                            NAILS NOT      NAILS PREBORED SCREWS                                             CONSUMABLES SHALL BE COMPATIBLE WITH BOTH PARENT ALLOYS IN ACCORDANCE
                                                                                                                                                                                                                                                           PREBORED       TO 80% DIA.                                                       WITH AS AS 1665. FOR 6063-T6 USE 4043 FILLER WIRE. PLATE-TO-EXTRUSION ALLOYS
                                                                                                            T3    PREFABRICATED TIMBER ROOF TRUSSES, PROPRIETARY FLOOR JOIST SYSTEMS                                                 END DISTANCE            20D               10D        10D                                               SHALL BE WELDED USING APPROPRIATE FILLERS IN ACCORDANCE WITH WTIA
                                                                                                                  AND ALTERNATIVE TIMBER ELEMENTS TO THOSE SHOWN ON THE ENGINEERING                                                  EDGE DISTANCE            5D                5D         5D                                               TECHNICAL NOTES WHERE NOT COVERED BY AS 1665.
                                                                                                                  DRAWINGS ARE TO BE DESIGNED AND CERTIFIED BY THE SUPPLIER'S STRUCTURAL                                             ALONG-GRAIN SPACING     20D               10D        10D                                        A5.    ALL WELDS SHALL BE A MINIMUM 5mm CONTINUOUS FILLET WELD ALL ROUND,
                                                                                                                  ENGINEER. DESIGN AND INSPECTION CERTIFICATES FOR THESE ELEMENTS ARE TO BE                                          CROSS-GRAIN SPACING     10D               3D          3D                                               UNLESS NOTED OTHERWISE.
                                                                                                                  ISSUED TO THE CONTRACTOR FOR LODGEMENT WITH THE LOCAL AUTHORITY.                                                                                                                                                   A6.    ALUMINIUM EXTRUSIONS SHALL BE STRUCTURAL GRADE ALLOY:- EXTRUSIONS 6063-T6
                                                                                                                                                                                                                                                                                                                                            UNLESS NOTED OTHERWISE.
                                                                                                            T4    ALL TIMBER MEMBERS USED ARE TO HAVE A MINIMUM LEVEL OF DURABILITY AS                                                                                                                                               A7.    ALUMINIUM PLATE IS TO BE WROUGHT GRADE ALLOY 5083 H116.
                                                                                                                  SPECIFIED IN AS1684.2 - APPENDIX B.                                                                                                                                                                                A8.    ALL STEEL AND STAINLESS STEEL BOLTS AND ALL OTHER FIXINGS MUST BE ISOLATED
                                                                                                                                                                                                                                                                                                                                            FROM ALUMINIUM USING NYLON OR SIMILAR APPROVED PACKERS/GASKETS, AND
                                                                                                            T5    ALL HWD TIMBER SHALL BE SEASONED UNO.                                                                                                                                                                                     WASHERS WITH SHANK COLLARS.
                                                                                                                                                                                                                                                                                                                                     A9.    SHOP DETAIL DRAWINGS ARE TO BE SUBMITTED TO THE ARCHITECT AND ENGINEER
                                                                                                            T6    ALL TIMBER SHALL BE FREE OF GUM VEINS, KNOTS, SHAKES, CHECKS, WANES AND ANY                                                                                                                                               FOR REVIEW. APPROVAL IS TO BE OBTAINED FROM THE COUNCIL, THE ARCHITECT AND
                                                                                                                  OTHER IMPERFECTIONS WITHIN CONNECTION ZONES.                                                                                                                                                                              THE ENGINEER, PROIR TO COMMENCING FABRICATION.

                                                                                                            T7    ALL TIMBER FRAMING TO BE MINIMUM H6 TREATED UNO.

                                                                                                            T8    EXPOSED FRAMING (TIMBER FRAMING THAT MAY BE SUBJECT TO PERIODIC WETTING):
                                                                                                                      - SHALL BE EITHER H6 PRESSURE TREATED OR DURABILITY CLASS 1
                                                                                                                        SPECIES (MINIMUM) SAWN TIMBER (UNO)

                                                                                                            T9    WASHERS SHALL BE PROVIDED UNDER ALL NUTS AND BOLT HEADS (EXCEPT CUP-HEAD
                                                                                                                  BOLTS) BEARING AGAINST TIMBER AS FOLLOWS:
                                                                                                                      BOLT SIZE       WASHER
                                                                                                                      <=M12           50X50X3.0mm
                                                                                                                         M16          57X57X4.0mm
                                                                                                                         M20          65X65X5.0.mm
                                                                                                                        >M20          75X75X6.0mm

                                                                                                            T10   X….. INDICATES M12DIA ANCHOR ROD/BOLT

                                                                                                            T11   [X]….. INDICATES M16DIA ANCHOR ROD/BOLT

                                                                                                            T12   SB…. INDICATES STRAP BRACE ROOF BRACING FIXED TO TOP OF EACH JOIST WITH 2
                                                                                                                  SCREWS. BEND STRAP BRACING OVER AT ENDS, FIX WITH 2 SCREWS TO TOP OF JOIST
                                                                                                                  AND 4 SCREWS TO SIDE FACE OF SUPPORTING MEMBER. ALL ROOFS TO BE BRACED.

                                                                                                            T13   ALL FASTENERS ARE TO BE GRADE A4-70 STAINLESS STEEL IN ACCORDANCE WITH
                                                                                                                  ISO-3506-1. EXTERNAL ANCHORS WHERE SUBJECT TO SALT AIR SHALL BE STAINLESS
                                                                                                                  STEEL A4-70:
                                                                                                                        -SCREWS TO BE NO.14 TYPE 17 WITH 50MM EMBEDMENT (UNO)
                                                                                                                        -ALL JOIST HANGERS, FRAMING ANCHORS, TRIPLE GRIPS AND THE LIKE, SHALL BE
                                                                                                                        STAINLESS STEEL. TO BE MANUFACTURED BY PRYDA OR APPROVED
File: C:\- A Projects\00 - Black & More\7882 - 19 The Peninsula Jetty\ 7882- Notes Sheet.dwg




                                                                                                                       EQUIVALENT, WITH 5 NO. 2.8mm DIA X 30MM
                                                                                                                        NAILS EACH LEG MINIMUM. INSTALL AS PER MANUFACTURERS SPECIFICATION.

                                                                                                            T14   PROVIDE BLOCKING OVER SUPPORTS AT 1800 MAX CRS IN ACCORDANCE WITH AS 1684
                                                                                                                  FOR TIMBER BEARERS AND JOISTS WITH D/B >= 4.

                                                                                                            T15   FOR JOISTS WITH SPAN >3000 AND BOTTOM OF JOIST UNRESTRAINED BY CEILING
                                                                                                                  DIAPHRAGM:
                                                                                                                       -PROVIDE 1 ROW OF BLOCKING BETWEEN EACH JOIST AT
                                                                                                                            MIDSPAN FOR SPANS < 4200mm
                                                                                                                       -PROVIDE 2 ROWS OF BLOCKING BETWEEN EACH JOIST AT
                                                                                                                            THIRD POINTS FOR SPANS >4200mm

                                                                                                            T16   FIXING LOCATIONS TO BE FIXED ACCORDING TO THE FOLLOWING MINIMUM PACINGS
                                                                                                                  (D = FIXING SHANK DIA. IN mm):
                                                                                                                  BOLTS       4D  EDGE DISTANCE TO BOTH EDGES IN DIRECTION OF SHEAR LOAD
                                                                                                                              5D  PITCH BETWEEN BOLTS
                                                                                                                              5D  EDGE DISTANCE FROM END OF ELEMENT
                                                                                                                              13D MINIMUM OVERALL ELEMENT DEPTH
Printed: 08 November 2021, 6:58 AM




                                                                                                                                                                                                                                                                                                                                                                                                                                             FOR CONSTRUCTION
                                                                                                                                                                                       R.P. DATA                       © Black & More                                                                      Client                                    Project                                                  Drawing Title
                                                                                                                                                                                       LOT:    267                     This document is and shall remain
                                                                                                                                                                                                                                                                       Black & More
                                                                                                                                                                                                                                                                       ABN 19 609 960 232
                                                                                                                                                                                                                                                                                                                      ANDREW HAY           PROPOSED JETTY
                                                                                                                                                                                       RP:     856191                  the property of Black & More.                                                       Address
                                                                                                                                                                                                                                                                                                                      19 THE PENINSULA NOOSA WATERS                                                            GENERAL NOTES - SHEET 2 OF 2
                                                                                               Revisions




                                                                                                                                                                                                                       This document may only be used                  7 / 28 Sunshine Beach Road,
                                                                                                                                                                                       19 THE PENINSULA NOOSA WATERS                                                   Noosa Heads QLD. 4567
                                                                                                                                                                                                                       for the purposes for which it was
                                                                                                                                                                                                                       commissioned and in accordance                  PO Box 611, Noosa Heads QLD. 4567   Drawn            Drawing             Approved                               Date    12/11/21
                                                                                                                                                                                       Client:                         with the Terms of Engagement for
                                                                                                                                                                                                                                                                       Telephone (07) 5447 4444
                                                                                                                                                                                                                                                                                                                       ST   Check          JB
                                                                                                                                                                                       ANDREW HAY                      the commission. Unauthorised use                                                                                                                                                       Drawing Size Scale (A3 size)     Drg No                Revision
                                                                                                           C1 CONSTRUCTION ISSUE                                                                                                                                                                                                                                                         RPEQ 23058
                                                                                                           No.                         Description          Reviewed Approved   Date
                                                                                                                                                                                                                       of this document in any form
                                                                                                                                                                                                                       whatsoever is prohibited.
                                                                                                                                                                                                                                                                       Email
                                                                                                                                                                                                                                                                       Internet
                                                                                                                                                                                                                                                                                 [email protected]
                                                                                                                                                                                                                                                                                 www.blackm.com
                                                                                                                                                                                                                                                                                                           Designed
                                                                                                                                                                                                                                                                                                                       JB
                                                                                                                                                                                                                                                                                                                            Design
                                                                                                                                                                                                                                                                                                                            Check          SS    Drawing is not to be used for construction unless approved      A3             NOT TO SCALE            7882- S003    C1
                                                                                               External References:    B&M-JETTY-TITLE-A3_e.dwg

Used in these records

About this file

File size
1.2 MB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Plans 19 The Peninsula Jetty_signed.pdf · 1.2 MB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.