Referenced Document - MCU13/0146
Report #S7186, Lot 10 (MCH 5387), Tropicana Rise, Castaways Beach QLD 4567
28 August 2013
6.14 Site Maintenance
Long-term stability of the house foundations is the responsibility of the owner/occupier of the dwelling.
Large changes in moisture conditions around the structure's footings (inconsistent watering patterns), will
cause movement, and may lead to damage of the house. Further, trees are to be planted away from the
structure area in order not to adversely affect the foundation performance. You are advised to read the
report, Foundation Maintenance and Footing Performance: A Homeowner’s Guide, (CSIRO 2003), a copy
which can be downloaded from http://www.publish.csiro.au/nid/22/pid/3612.htm.
6.15 Consideration to Tree Planting
A zone of drying influence is associated with single trees or groups of trees under consideration. The site
classification and foundation design for this project has been based on the assumption that the design will
NOT be subject to any zone of drying influence produced by trees. AS2870-2011 Appendix H
(informative) may be referenced as a guide for determining the influence distance of trees. Based on this
appendix, single trees are to be planted a minimum distance of 1.0 times HT (mature height or an estimate
of the height it will attain within the design life of the building) away from the structure. A group of trees
are to be planted a minimum distance of 1.5 times HTg (0.9 times the design height of the tallest tree)
away from the structure. For a group of four or more trees in a row the trees are to be planted a
minimum distance of 2.0 times HTg away from the structure.
7.0 CONCLUSIONS
7.1 Recommendations
Notwithstanding the following conclusions, it is recommended: -
Unretained fill areas are structurally undesirable.
Massive retaining wall structures are structurally undesirable.
Lightweight flexible structures that step down the slope are preferred. The proposed house is
suitable for this allotment.
Minimise cut/fill earthworks. Retaining walls should be designed for both instances for the
proposed residence.
All footings are to bear to the underlying medium dense SAND.
Install and maintain drainage systems to divert water away from the proposed residence.
7.2 Slope Stability Risk
It has been concluded that this geological region has a low risk of slope instability; however with the adoption
of our recommendations, this risk can be managed as “low/very low”. Further, we conclude the proposed
GeoConsulting Pty Ltd
1/8 Denna St, Maroochydore, QLD, 4558. Phone: 5443 6622, Fax: 5479 1899, Email: [email protected] 14 | P a g e
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
REFERENCED DOCUMENT - MCU13/0146Related documentApplication case desk ↗
About this file
- File size
- 2.7 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.