Report #S7186, Lot 10 (MCH 5387), Tropicana Rise, Castaways Beach QLD 4567
28 August 2013




 6.9       Erosion Control & Landscaping

Prior to construction, an erosion and sediment control plan should be established. This document can be
referenced to the publication, Soil Erosion and Sediment Control (EA 1996).


 6.10      Construction Recommendations

The proposed two storey residence (consisting of concrete slab on ground and suspended timber floors on
steel posts and lightweight cladding) is considered suitable for this allotment.


 6.11      Surface Movement and classification

In accordance with AS2870-2011 – Residential Footings and Slabs, the site must be classified “P” – soft
soils.


 6.12      Factor of Safety

                                                                     th
In accordance with the Maroochy Plan 2000 (dated 8 August 2011), modelling of the slope on Lot 10
against landslip has taken place with respect to current site conditions and the proposed residential
construction. Parameters include: -
           Cohesion of the soils
           Topographic grades
           The revealed soil profile and the depth to rock
           Density of the revealed soils
           Angle of internal friction
           Seepage and groundwater.

This modelling concludes a factor of safety against landslip to range between 1.8 and 2.2. We conclude the
proposed development of Lot 10 as referenced is sustainable, with a factor of safety against landslip to be
greater than 1.5.


 6.13      Plumbing

Penetrations of the footing beams shall be avoided, but where necessary shall be sleeved to allow for
movement. Closed-cell polyethylene lagging a minimum of 20mm thick shall be used around all
stormwater and sewer pipe penetrations through external footings. Further, connections of stormwater
and waste drains shall include flexible connections.




GeoConsulting Pty Ltd
1/8 Denna St, Maroochydore, QLD, 4558. Phone: 5443 6622, Fax: 5479 1899, Email: [email protected]   13 | P a g e

Used in these records

About this file

File size
2.7 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

REFERENCED DOCUMENT - MCU13_0146.pdf · 2.7 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.