Effluent Disposal Report
Job No: 22/388
Date: 11/11/22
Client: QRE Construction
Site Address: 332 Eastern Branch Road, Kin Kin
Proposed Structure: Proposed Glamping Tents & Amenities Blocks
Information Provided by the Client: Site Plan & Site Meeting
Local Authority: Noosa Shire Council
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 8 pages
Page 2
Introduction
The purpose of this report is to evaluate and design a suitable on-site treatment system and disposal
area in accordance with AS 1547 – 2012, the Queensland Plumbing and Wastewater Code, the
Plumbing and Drainage Act, The Environmental Protection Act & Local Authority requirements.
The report relates exclusively to the above site and the proposed and or existing buildings shown on
the plan only. All measurements and levels shown are as accurate as possible with the information
provided these are to be used for locating the onsite effluent disposal system only.
Site Description
Weather Conditions Scattered showers
Slope 18-22%
Slope Stability To be addressed by others
Vegetation Grassed, scattered trees
Fill Nil
Flooding Nil
Watercourses Present >10m
Site exposure Sun & wind
Salinity Nil
Surface condition Nil cracks, seepage or compaction
Boulders & Rock outcrops Nil
Will water from uphill traverse the area Yes, diversion drain to prevent
Water table Nil
Soil Category (AS1547-2012 Table M1)
Borehole 0-0.1m 0.1-0.6m
BH1-BH3 Cat 4 Cat 5
Clay Loams Light Clays
Weakly Structured Moderately Structured
0.12-0.5m/d 0.06-0.12m/d
Recommended Design Irrigation Rate
Test Result 0.07
Recommended Design Irrigation Rate 3mm/day
Adopted Rate 3/mm/day
Calculations
Bedrooms 5 (5 x 1 bedroom glamping tents)
Persons 10
DIR (mm/day) 3
Litres per person per day (Tank supply) 120
Calculations 10x120=1200 /3= 400
Disposal Area Required 400m2 Heavy Droplet Surface Irrigation
Page 3
Risk Assessment
Risk Risk Mitigation
Surface Runoff Diversion Drain
Human Contact Signs to identify area. Apply by setbacks
Overloading of system and LAA Use correct DIR, flow allowances and
maximum occupancy
Performance Solution
• The design has considered site and soil conditions and has also been discussed with the
landowner.
• Irrigation area has been designed using correct DIR.
• The spray from the sprinklers shall not exceed 500mm in height, 2000mm in dia. (1m
throw) and be heavy droplet in nature that prevents misting and drift. Control valves may be
needed to adjust the flow and pressure to achieve this.
• All pipework and materials used are to be new, meet relevant standards and be fit for use.
• Category 4 soils or better will assist in even distribution of treated effluent.
Page 4
Recommendations
Treatment
The amenities blocks are to be serviced by septic tanks, pump wells and an Advanced
Secondary ASTP/Sand filter fitted with a large capacity pump. See plan for location &
layout. (System must be approved by QLD Depart of Housing & Public Works)
• Installer to ensure tank position does not damage to existing or proposed structures and does
not cause audible disturbance to nearby residences once final site plan and earthworks are
known. (Tank position on plan is indicative, final positioning to be nominated by installer)
• The tank must be installed and anchored, if necessary, to prevent flotation.
Installer to confirm sufficient fall is available to the treatment plant prior to installation once
the floor height is known.
• Top of treatment plant shall be at least 150mm above any flood levels that are present.
• A filter must be installed in between treatment plant and irrigation area
• Pump must have sufficient power to pressurise the irrigation area, controls valves may be
necessary on the irrigation lines to restrict flow to prevent sprays misting or drifting outside
the designated land application area.
• Two signs are to be erected stating “Effluent Water, Avoid Contact, Do not drink”
• Flexible joints should be used from the treatment to the proposed/existing structure where
the site is “H1” or higher.
Irrigation Area
A 400sqm fixed surface irrigation area consisting of fixed heavy droplet sprinklers
300mm high and a maximum spray diameter of 2m and height of 0.5m. (see plan)
• All pipework and fittings used must meet relevant Australian Standards be buried, withstand
150% of pump shut-off-head and be fit for use.
• The supply line from the treatment plant to the irrigation area shall be buried 25-32mm
purple line poly within a 200mm layer sand bed to prevent damage.
• The area is to be installed in a way that creates no pooling or runoff.
• The installer is to install non return valves to evenly distribute effluent and prevent back to
the treatment plant.
• A reserve area equal to the above area is available.
Diversion and Vegetation Requirements
• The area is to have a shallow diversion drain or mound uphill of the area to divert surface
water around the area.
• The area is to be mulched & densely planted out with water tolerant shrubs & grasses.
• All Storm water from the residence and uphill slopes is to be diverted away from the area.
Page 5
Setbacks
The below minimum setbacks must be complied with when installing the system. Greater
setbacks may be stipulated on the plan due to site and soil conditions.
(Advanced Secondary)
Surface & Covered Surface Irrigation
10M from a watercourse, dam, table drain, bore etc.
10M from a dwelling or habitable building or recreation area.
2M from a boundary/driveway if it slopes away or is level with that boundary/driveway.
4M from boundary/driveway if it slopes towards that boundary/driveway
6M from an inground water tank
6M from pool edge.
Maintenance, usage, and installation notes
The installer, builder and homeowner should families themselves with the below.
• Scrape all dishes to remove fats, grease, etc. before washing
• Don't use a garbage grinder
• Use biodegradable soaps
• Use a low-phosphorus detergent, don't use powerful bleaches
• Don't put sanitary napkins and other hygiene products into the system
• Spray or irrigation areas should have access restricted
• Divert surface water away from land application area
• No vehicles or stock should be allowed on trenches, beds or irrigation area.
• Deep rooting trees or shrubs should not be grown over absorption trenches or pipes
• Vegetable gardens and/or fruit trees should not be planted within or near area, where there
is a possibility of airborne spray coming into contact with the plant.
• Structures should not be constructed near areas that encourage people to congregate.
• Play areas and equipment should be well away from areas where there is no possibility of
spray coming into contact with humans.
• Treatment plants and septic tanks are to be desludged every 3-5 years.
• If any part of this design is unclear, please call before buying products or installing.
• This report must be approved by the local authority and appropriate permits issued before
any works can be undertaken.
• Installer is to contact local council prior to burying the system for a site inspection and
certification.
• Follow the manufacturer's instructions, relevant codes, standards and guidelines for
installation, servicing, maintaining and cleaning the system and irrigation
area/trenches/beds.
• The Treatment Plant is to be placed on an approved service schedule
Page 6
Limitations of Report & Notes
This report is based on information gathered from the field investigation and information
provided by the client if any. Ground Drill should be notified immediately if ground
conditions are found to differ from this report.
Unless otherwise stated this report does not address the following issues;
• Mining Subsidence.
• Slope Stability (If the site is in a known slip area or is steep, it is recommended that a
Geotechnical Engineer be engaged to conduct a Slope Stability assessment).
• Deep soft or settling soils
• Soil Contamination, hazardous materials and or acid sulphate.
• Any slopes, dimensions, levels, site features or plans in this report are approximate only
show approximate testing locations.
• Flood levels (It is the client’s responsibility to inform us of any flood levels on the
allotment).
• If water is found in the boreholes this depth may vary greatly over time. This report does not
address the influence any natural springs may have on the structure.
• It is the client’s responsibility to inform us of any nearby underground services that have
been or will be installed near the proposed area.
• Earthworks could affect the design.
• If any fill is placed on the allotment post investigation this could change the design.
• Surface water is to be diverted away from the area.
• This investigation undertaken consisted of the occluded boreholes/test pits, given the size of
the site it is possible that a problem could have been missed. eg. Filled dam/gully, soft soils,
fill, springs, boulders, rock etc. We cannot give a definitive assurance that none of these
problems exist on the site unless we did a greater number of boreholes which would be
uneconomical and impractical.
• Ground Drill will not be liable for any Council Inspection, submission or reviewing fees due
to changes in report or plan requested by client or Council.
• No allowance has been made for spa baths
Authorised Signatory
Matthew Bennett
on behalf of Ground Drill Pty Ltd
QBCC Lic # 15034580
Page 7
Soil Profiles
BH 1 Soil Description BH 2 Soil Description BH 3 Soil Description
0 CLAYEY SILT (ML) – Brown, low 0 CLAYEY SILT (ML) – Brown, low 0 CLAYEY SILT (ML) – Brown, low
plasticity fines, moist, firm. plasticity fines, moist, firm. plasticity fines, moist, firm.
100 SILTY CLAY (CH) – High plasticity, 100 SILTY CLAY (CH) – High 100 SILTY CLAY (CH) – High plasticity,
brown, trace fine to medium gravel, plasticity, brown, trace fine to brown, trace fine to medium gravel,
moist, firm. medium gravel, moist, firm. moist, firm.
200 200 200
300 300 300
400 400 400
500 500 500
600 Hand Auger Refusal 600 Hand Auger Refusal 600 Hand Auger Refusal
700 700 700
800 800 800
900 900 900
1000 1000 1000
1100 1100 1100
1200 1200 1200
1300 1300 1300
1400 1400 1400
1500 1500 1500
Site Photo
Page 8
To
Advanced Proposed
Secondary K-Rain
ASTP Valve
10m
40m
Fixed Sprinkler layout Ground Drill Pty Ltd
See site plan for location. Sunshine Coast, QLD.
NTS QBCC # 150 345 80 C:\Users\Ground Drill Desktop\Documents\Advertising\print\logo.jpg
E: [email protected]
W: www.grounddrill.com.au
P: 0407 035 220
Page 9
Notes
Levels shown are
approximate and are sourced
from local council mapping N
or information provided by
the client. These levels are
solely to demonstrate the
functionality of the system.
Actual floor height is to be
confirmed with the builder
prior to installation.
All pipe work from the
structure to the proposed Proposed
system should be covered Amenities Block
and adequately vented and Proposed Advanced (Approx RL 81)
Proposed
be vermin/insect proof. Secondary
0m 4000L
All work carried out should 29 Treatment Plant
Septic
meet relevant (Approx RL 83) Proposed
Tank
codes/standards and be done 4000L
by an appropriately qualified Septic
and licensed person. Tank
Proposed system should be
constructed in a way to Proposed Proposed
maximize evapotranspiration Amenities Block 450L
and minimize potential (Approx RL 84) Pump
pooling and runoff. Well
If plans were not available at
the time of investigation
further reporting and design Proposed
work may be needed prior to 4000L
council submission and Septic 32-40mm Pump Well line
installation. Proposed Tank (Burried in a 200mm sand layer)
Care is to be taken not to Amenities
compact,smear or damage Block
the soil structure during
installation (This can lead to
premature failure).
If structures have been built
since our initial investigation
(Including neighboring
82m
structures) please contact us
to confirm this will not
adversely effect the design.
Final landscaping and BH4
installation should discourage PT2
and limit causal pedestrian
BH5
access.(By way of plantings, 32mm Delivery line
PT3
border, mounds, visual and (Burried in a 200mm sand layer)
or physical deterrents)
The owner should obtain
knowledge on how to use
Slope
and maintain the proposed BH3
16-22%
system. Most of this is PT1
available from your chosen
supplier/installer.
This report must be Reserve Area Proposed Surface
approved by the local council Irrigation Area - 400sqm
prior to any work (10x 40m)
commencing. (Approximate RL 101)
The effluent disposal
report must be
accompanied by a Site
Classification Report. If
the Site Classification is
H1,H2, E or P an
articulation joint will need
to be designed by a
person licensed to do so.
Client- QRE Consruction
Site - 332 Eastern Branch Road, Kin Kin
Ground Drill Pty Ltd
Date - 11/11/22
Abbreviations Sunshine Coast, QLD.
Job# - 22/388
BH : Borehole DCP : Dynamic Cone Penetrometer QBCC # 150 345 80
Scale - 1 : 2000 @ A4 (Site features are approximate-Do not scale)
PT : Percolation Test HD : Heavy Droplet Lilac Sprinkler E: [email protected]
TV : Turf Valve RWT : Rain Water Tank W: www.grounddrill.com.au
P: 0407 035 220