aqua

It can be seen from Table 3 that the Design Storm Method results in marginally larger trench sizes and thus
these sizes are recommended for use on this site. The hydraulic services design has nominated two location for
the infiltration systems with one being located near the northern and southern boundaries at the rear of the
house. A flow split has also been nominated with 60% of the flow going to the northern system and 40% going
to the southern system. The following is infiltration system is recommended for the southern and norther
system:

e Southern System — 10 x Atlantis Flo-Tanks (double) (w) x 0.90m (d) x 3.4m (I)

e Northern System — 15 x Atlantis Flo-Tanks (double) (0.82m (w) x 0.90m (d) x 5.5m (I)

It is noted that there is a 3m Unity Water sewer easement in the property. It is understood that Unity water
may in some circumstances allow the infiltration trench within the easement however Unity Water would need
to be consulted.

CONCLUSION

Based on the methodology contained within the “The WSUD Technical Design Guidelines for South East
Queensland” and the geotechnical information available for the site it is recommended that a minimum
infiltration area and volume as provided in Tables 3 be installed within the development to prevent water
leaving the site. This volume and area could be accommodated by a total of 25 x Atlantis Flo-Tank (Double).

| trust this assessment of stormwater management requirements for your development meets your needs. Feel
free to contact me should you wish to discuss any of the content in this letter.

Yours faithfully,

Kelly McKendry ,

Water Resources Engineer / Director (RPEQ 09298)
Aquaintel Pty Ltd

Attachments

1. Hydrologic Calculations
2. Geotechnical Information
3. Trench sizing calculations

m: 0439 119 890 t: +7 5414 7185

e: [email protected]
Ww: www.aquaintel.com.au

Used in these records

About this file

File size
8.8 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Att 3b - Stormwater.pdf · 8.8 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.