Picture Point Sewer Options - Rev A
EXISTING CONSTRAINTS TO BE ADDRESSED
1. EXISTING SEWER MANHOLES LOCATED WITHIN BUILDING FOOTPRINT
2. EXISTING SEWER LINE IS HIGHER THAN PROPOSED BASEMENT RL
3. NEIGHBOURS PERMISSION MAY BE REQUIRED WITH CERTAIN OPTIONS
4. BASED ON AERIAL PHOTOGRAPHY, THE REAR OF THE PROPOSED DEVELOPMENT IS
HEAVILY VEGETATED.
5. POSSIBLE LIMITED WORKS ALLOWED WITH BIODIVERSITY OVERLAY ZONES.
SUBJECT TO NOOSA SHIRE COUNCIL APPROVAL.
PROPOSED SOLUTIONS TO ADDRESS SEWER CONSTRAINTS
1. SEWER MANHOLES TO BE RE-POSITIONED SO THAT THEY ARE LOCATED
43 A MINIMUM 1.2m OUTSIDE BUILDING FOOTPRINT.
2. EXISTING SEWER RETICULATION LINE TO BE RELOCATED OUTSIDE
BUILDING FOOTPRINT.
3. EXISTING SEWER TO BE RE-LAID IN SAME LOCATION, HOWEVER, BELOW
BASEMENT RL (SUBJECT TO UNITY WATER CONFIRMATION &
CONFIRMATION OF SEWER INVERT LEVELS).
THIS SEWER MANHOLE NEEDS TO LOCATED TO CONFIRM
.81 THE EXACT POSITION. (WHICH PROPERTY IS THIS IN?) 4. SEWER NEW PROPERTY CONNECTION REQUIRED TO BE INSTALLED TO
45
IL
US
SERVICE THE PROPOSED DEVELOPMENT.
39
5. VACUUM EXCAVATION MAYBE REQUIRED WHEN WORKING WITHIN
BIODIVERSITY ZONES.
6. SEWER WORKS MAY NEED TO UNDERTAKEN WHILST UNDER
USIL 43
.40 SUPERVISION OF QUALIFIED ARBORIST.
IL
40.0
4 DS
43.37
US IL
USIL
40.1
OW
4 40.24
DS IL
FL
OF
N
IO
CT
RE
THIS SEWER MANHOLE NEEDS TO LOCATED TO CONFIRM
DI
THE EXACT POSITION. (WHICH PROPERTY IS THIS IN?)
37
SEWERAGE RETICULATION LEGEND
EXISTING PROPOSED ITEM DESCRIPTION
GRAVITY MAIN
DISUSED / ABANDONED GRAVITY MAIN
PROPERTY CONNECTION
MANHOLE STRUCTURE (MH)
EXISTING SEWER LOCATION OVERLAID ONTO PROPOSED FOOTPRINT MAINTENANCE STRUCTURE (MS)
1:200 @ A1
TERMINAL ENTRY POINT (TEP)
x 0.000 x 0.000 LOT CONTROL LEVEL
STRUCTURE NAME
PRELIMINARY DRAWING NOTES:
NOT TO BE USED FOR CONSTRUCTION PURPOSES 1. THIS IS A GENERIC LEGEND. NOT ALL ITEMS WITHIN THIS LEGEND MAY BE
PRESENT ON THIS PLAN AND THE SCALE OF THE ITEMS MAY BE DIFFERENT
TO THE ITEMS PRESENTED ON THIS PLAN.
Associated Consultant: Surveyor: RP Description: North: Client: Scale:
AMENDMENTS
PRELIMINARY
No. DATE DESCRIPTION DRAWN No. DATE DESCRIPTION DRAWN
.
.
. GRAYA AS NOTED
.
A 08.05.2022 PRELIMINARY ISSUE GF Plan Ref.: . . Project: Job No.
Level Datum AHD PROPOSED SEWER RE-CONFIGURATION OPTIONS
.
Size of Land: Orig. Drg. Size
TBC
. A1
T 1300 598 544
FOR PROPOSED NEW RESIDENCES
Approved: Drawn: Design: Drawing No.
IMAGERY, CADASTRAL AND SURVEY DATA DISCLAIMER
E [email protected] AT 39 PICTURE POINT CRESCENT
GF GT
While every care is taken by NAXOS Engineers Pty Ltd to ensure the accuracy of the data
supplied by local authorities, dial before you dig (dbyd) records, as constructed information
Ground Floor, Suite 1 NOOSA HEADS C101
and detailed survey, we make no representations or warranties about its accuracy, reliability,
424 Upper Roma Street, Brisbane 4000
NAME Checked: Supervisor: completeness or suitability for any particular purpose and disclaim all responsibility and all Title: Revision:
liability (including without limitation, liability in negligence) for all expenses, losses, damages PO Box 224, Spring Hill QLD 4004
RPEQ. . Date: . GT GT (including indirect or consequential damage) and costs which may be incurred as a result of
data being inaccurate or incomplete in any way and for any reason.
NAXOSENGINEERS.COM.AU EXISTING SEWER ALIGNMENTS A
ON BEHALF OF NAXOS ENGINEERS
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
The download may take up to a minute.