61 AS 1428.1—2009
13.3.3 Sliding doors
13.3.3.1 General
The clear circulation space at doorways with sliding doors is based on the clear
opening width of the doorway (D). The clear circulation space shall be not less than
the dimensions specified in the tables in Figure 32 for the appropriate clear opening
width.
13.3.3.2 Cavity sliding doors
Where a sliding door is within the wall cavity, the circulation space at the doorway
shall be not less than that given in the tables of Figure 32 for the appropriate clear
opening width (D).
13.3.3.3 Surface-mounted doors
Where a sliding door is surface-mounted, the circulation space at the doorway shall
be as follows:
(a) The circulation space at the door face shall be not less than that given in the
tables of Figure 32.
(b) The circulation space opposite the door face shall be increased from that
given in the tables of Figure 32, by the values given in the Table of Figure 33.
When a surface-mounted sliding door is automatic, these increases do not
apply.
DIMENSIONS IN MILLIMETRES
NOTE: See Clause 13.2 for clear openings of doorways.
FIGURE 33 CALCULATING DIMENSIONS OF THE CIRCULATION SPACE
OPPOSITE THE DOOR FACE WHERE A SLIDING DOOR IS SURFACE-MOUNTED