AS 1428.1-2009 PWD Code
67 AS 1428.1—2009
14 SWITCHES AND GENERAL PURPOSE OUTLETS (POWER POINTS)
14.1 General
All switches and controls on an accessible path of travel, other than general
purpose outlets, shall be located not less than 900 mm nor more than 1100 mm
above the plane of the finished floor and not less than 500 mm from internal corners
except where on the architrave on the latch side as shown in Figure 37.
14.2 Accessible sole-occupancy units and accessible sanitary facilities
Rocker action and toggle switches shall be provided and have a minimum
dimension of 30 mm × 30 mm. Push-pad switches shall have a minimum dimension
of 25 mm in diameter.
General purpose outlets shall be located not less than 600 mm nor more than
1100 mm above the plane of the finished floor and not less than 500 mm from
internal corners.
DIMENSIONS IN MILLIMETRES
FIGURE 37 HEIGHTS FOR SWITCHES AND DOOR HANDLES
15 SANITARY FACILITIES
15.1 General
The facilities described in this Clause may be used as individual modules, in mirror
image configurations or in a combined form, as specified in Clause 15.6.
15.2 Accessible unisex sanitary facilities
15.2.1 Water taps
Water taps shall comply with the following:
(a) Taps shall have lever handles, sensor plates, or other similar controls.