BT Tee 18556 64 Gateway Drive, Stage 1
CONSTRUCTION INPUT / INSPECTION RECORD

   
  

   
   

 

    

 

Date: Inspector: Inspected Item Re-inspected
(initials) and approved:

13/11/2020 HG . Prepour inspection of RW1 and RW2 footings: Ok to pour

* Any rubble and debris to be pulled out before pour

* Starter bars to be installed for the basin blockwork walls

= Screwpile certification to be provided

2. RW3 footing not complete during inspection — photos provided of RW3 before pour

17/11/2020 HG 8. Prepour inspection of GB1 and GB2 footings (unit 38-42): Ok to pour

= Bottom cover not adequate in some spots — cages were re-chaired during inspection,
= Western GB1 footing cage had no side cover — cage was moved over during inspection to achieve
adequate side cover.
= Any rubble and debris to be pulled out before pour.
* Where stop pour— after concrete cured, break out loose concrete overpour ready for next pour.
Vibrate all concrete, maintain cover during pour.
18/11/2020 HG 4. Prepour inspection of GB1 and GB2 footings (unit 32-38): Photos to be sent
= Bottom cover not adequate in some spots ~ cages were re-chaired during inspection.
= Some side cover issues to GB2s as they were dropping cages in - cage to be moved over to achieve
adequate side cover and photos sent.
= Cages to unit 32/33 yet to be placed — photos to be sent
» Any rubble and debris to be pulled out before pour.
= Where stop pour- after concrete cured, break out loose concrete overpour ready for next pour.
Vibrate all concrete, maintain cover during pour.
20/11/2020 HG 5. Prepour inspection of GB1 and GB2 footings (unit 30-31): ok
« Any rubble and debris to be putled out before pour.
* Where stop pour- after concrete cured, break out loose concrete overpour ready for next pour.
Vibrate all concrete, maintain cover during pour.
20/11/2020 HG 6. Prepour inspection of RW1-RW2 Blockwork walls ok
* Horizontal bars missing -- these were being drilled and feed through end of blockwork during and
after inspection
= Vertical bars to be held and adjusted to maintain position and cover — ensure inner tie bars to slab
positioned to avoid precast wall panels

 

 

 

 

 

 

 

 

Noosa: 07 5449 9600 inspection Record Page 1 of 3

Ted Job Number: 18556
hl Hs 9 31: i i
ieee outstanding results personal service

PO Box 61, Noosavilte, QLD 4566, Australia infrastructure buildings subdivisions placemaking
www.todconsuiting.com
Log in to download the original file

QB1910553 - STG 1 19 Ind Units - Lot 13 (#64) - QB1910553 - MISC - Form 11 Final & Supporting Certificates - 26.11.2021 KW.pdf · 10.4 MB (very large file)

Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.