4.0 HYDRAULIC FLOWS AND RECOMMENDED DISPOSAL SYSTEMS:
Calculations in accordance with Appendix 4.2D of A.S.1547:2012, using the
proposed 4-bedroom residence, supplied by on site storage tank water supply as
having 6 equivalent person occupancy rating. A typical wastewater flow design
allowance from Table H1 of AS1547 of 120 litres/person per day was used to
calculate a daily effluent sullage flow figure of 720 litres per day or 5,040 litres per
week using standard water fixtures.
We recommend the use of Standard Water Reduction Fixtures. These fixtures should
include: - a) Dual Flush 11 litre/5.5 litre WC's.
b) Shower Flow Restrictors.
c) Aerator Faucets.
d) Water Conserving Washing Machines.
Due to the poorly-draining Category 5 silty soils and the presence of a shallow
weathered siltstone, the steep slope and the close proximity of nearby gully
(watercourse),, we recommend all domestic effluent be treated to a minimum
Secondary Quality as described in Clause 11.8.4 of the “On-Site Sewerage Code”
and discharged into a shallow sub-surface irrigation area, utilizing the
evapotranspiration effects of the surface soils, plants, the sun and wind. Treatment
shall be by On-Site Treatment Plant with model or type specification approval,
installed, operated and maintained in accordance with the conditions of model or type
specification approval. Many approved Secondary treatment wastewater systems are
available these days and their particular irrigation methods may vary slightly.
We recommend a suitable wastewater land application area could be a Shallow Sub-
Surface Irrigation area consisting of rows of shallow buried geofabric wrapped
seepage pipes along the contour surrounded by 10-15mm gravel connected by
manifold and turf valves from the treatment tank. Each shallow pipe should have its
own isolation valve and cleanout end capping.
8894-193 SANKEYS RD-FEDERAL Page 3 of 13 24/07/2023
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Appendix D - On-site domestic wastewater evaluation report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 4.1 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.