Appendix D - On-site domestic wastewater evaluation report · MCU25/0022
PROJECT NO. 23/8894 24th JULY 2023
1.0 INTRODUCTION: The Site Inspection and Field Testing to determine soil types
and characteristics were carried out by Civil Quality Assurance Pty.Ltd.
This report refers to their findings and results to determine a suitable method and size
of domestic wastewater application area from a proposed 4-bedroom residential
dwelling.
2.0 SITE: The allotment is situated off the western side of Sankeys Road, FEDERAL.
It is a large heavily timbered allotment described as Lot.6 RP216727 with an area of
6.041 hectares. Refer locality on front cover of this report. A wastewater application
area was selected on the northern western side of the proposed building site.
The area’s natural land surface falls to the south west at about 18%. The area is
heavily treed bushland and well grassed.
Testing was carried out over the proposed wastewater disposal area to determine soil
types and characteristics of the existing soils for the purpose of on-site domestic
wastewater disposal. Soil Classifications and Descriptions were carried out in
accordance with A.S. 1547:2012 “On-Site Domestic Wastewater Management” and
the “On-Site Sewerage Code” published by The Department of Natural Resources.
Test Locations are shown on the attached Site Plan.
3.0 SUB-SURFACE INVESTIGATIONS: Boreholes carried out revealed silty clay
surface soils of medium to high plasticity overlaying shallow highly weathered
shaley siltstone. Soils classified in accordance with Table 5.1 of A.S. 1547:2012
were given a general Soil Category 5 (Massive Structure). Borelogs showing the soil
profile are attached.
Percolation Testing measures the soil’s water absorption capabilities. The testing
was carried out in accordance with A.S. 1547:2012, Appendix G, using 100mm
diameter test holes to a depth of 450mm. The tests were carried out in several
positions on the site and the results are shown on the attached Desktop Analysis.
8894-193 SANKEYS RD-FEDERAL Page 2 of 13 24/07/2023
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Appendix D - On-site domestic wastewater evaluation report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 4.1 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.