Original source · versioned page text
Documentation Requirements for change of level applications
Attached to the e-mail MCU16/0081 - Energex request to applicant for further information.
Phone: (07) 3664 4065
Power Systems Engineering Fax: (07) 3664 9816
Memorandum
To Kirsten Sellers, Steve Soo
From James Canning - Principal Transmission Design Engineer
Date 21 March 2016 Reference
Subject Application for Change of Level on an Easement
PURPOSE
This memo sets out the minimum requirements for documentation which shall be submitted to
Energex Transmission Design to provide assessment of applications to change surface levels
or to erect structures on easements containing Energex Overhead Transmission assets.
BACKGROUND
It is incumbent upon the applicant to demonstrate to and satisfy Energex that their
development will not have adverse effects on Energex interests or health and safety to the
public or Energex staff.
Design group provides the following advice regarding such applications:
If the proposed development will restrict access to Energex assets (existing or future)
If the proposed development will restrict the future use of the easement by Energex
If the proposed development will compromise the integrity of Energex assets
If the proposed development will compromise electrical clearances required under the
electrical safety regulations.
Other electrical safety issues
Other issues which may become evident in the course of assessment.
Final approval or otherwise of the development remains the responsibility of Asset
Management.
To date the requirement for documentation from applicants has provided ad-hoc. In many
cases the documentation provided is substandard and significant effort is expended by
Energex in determining the suitability of a proposed development. These guidelines will aid the
provision of accurate information to Energex to assess future developments.
REQUIRED DOCUMENTAION
Where an applicant wishes to change surface levels on an easement containing Energex
Overhead Transmission assets they shall provide drawings showing a plan and profile view of the
development in relation to the Energex asset.
These drawings shall be produced specifically for this process and shall show:
The easement boundary and title
The location of Energex structures, poles, towers and the like within the easement
The location of the proposed structures
The proposed finished surface levels
The clearance from proposed ground level or structure (existing and proposed) to the
lowest conductors when operating at their maximum operating temperature (in profile)
The clearance from proposed objects to conductors when in the blowout condition (in
Plan
A ground profile under the conductors
Y:\Transmission\Users\James Canning\Easements\Documentation Requirements.docx/22-Mar-16
See the original