9307-OPW RFI 1 Civil Plans

of 22

Page text read automatically using OCR, there may be inaccuracies

Original PDF page 3, section 1. The text section number identifies this passage in the reader.

HOLD POINTS & INSPECTIONS:                             CONCRETE NOTES                                        REINFORCEMENT COVER
                                                                                                                                                                   GENERAL NOTES
THE FOLLOWING ITEMS DO NOT SUPERSEDE OR LIMIT THE                                                             THE CLEAR CONCRETE COVER TO REINFORCEMENT
REQUIREMENTS OF THE LOCAL AND STATE AUTHORITIES        GENERAL                                                SHALL BE AS FOLLOWS:-                                1. GENERAL
HOLD POINTS OR INSPECTIONS AS NOMINATED IN THE          ALL WORKMANSHIP AND MATERIALS SHALL BE IN                                                                   THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL
APPLICABLE      PLANNING     SCHEME     POLICIES,       ACCORDANCE WITH CURRENT EDITIONS OF AS 3600                    COMPONENT               COVER (mm) U.N.O.    OTHER WORKING DRAWINGS AND SPECIFICATIONS AND
CONSTRUCTION SPECIFICATIONS, APPROVAL CONDITIONS        "CONCRETE STRUCTURES" EXCEPT AS VARIED BY                                                                   WITH SUCH OTHER WRITTEN INSTRUCTIONS AS MAY BE
                                                        CONTRACT DOCUMENTS.                                    SLABS                         50mm U.N.O.            ISSUED DURING THE COURSE OF CONSTRUCTION. ALL
E.T.C OR DRAWINGS AND OR SPECIFICATION PROVIDED
                                                                                                                                                                    DISCREPANCIES AND VARIATIONS SHALL BE REFERRED TO
BY THE DESIGN ENGINEER(S).                                                                                     KERB                          N/A
                                                        CONCRETE STRENGTH GRADE FOR PARTICULAR                                                                      THE ENGINEER BEFORE PROCEEDING WITH THE WORK.
THE FOLLOWING HOLD POINTS AND INSPECTIONS ARE TO        ELEMENTS SHALL BE AS NOTED ON THE DRAWINGS.            FOOTPATH                      REFER RS-065           IF IN DOUBT, ASK!
BE CONFIRMED AT THE PRE-START MEETING AND DO NOT                                                               FIELD INLETS                  REFER DS-050           ALL DIMENSIONS RELEVANT TO SETTING OUT AND OFF-SITE
RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITY TO       SIZES OF CONCRETE ELEMENTS DO NOT INCLUDE                                                                   WORK SHALL BE VERIFIED BEFORE CONSTRUCTION AND
SATISFY THE CERTIFYING ENGINEER OF THE WORKS            THICKNESS OF APPLIED FINISHES.                         ACCESS CHAMBERS               REFER DS-010           FABRICATION IS COMMENCED. DIMENSIONS SHALL NOT BE
CONSTRUCTED.                                                                                                                                                        OBTAINED BY SCALING STRUCTURAL DRAWINGS.
                                                                                                               ACCESS CHAMBER ROOFS          REFER RS-065           DURING CONSTRUCTION THE STRUCTURE SHALL BE
                                                        THE FACE OF ALL CONCRETE AGAINST WHICH NEW
                                                        CONCRETE IS TO BE CAST IS TO BE THOROUGHLY             CUSTOM SWD STRUCTURES 50mm U.N.O.                    MAINTAINED IN A STABLE CONDITION AND NO PART TO BE
FAILURE TO FACILITATE THE ATTENDANCE OF THE                                                                                                                         OVERSTRESSED
AUTHORITY AND/OR CERTIFYING ENGINEER AT A               MECHANICALLY SCABBLED. FULLY EXPOSING THE                                                                    U.N.O. STANDS FOR 'UNLESS NOTED OTHERWISE'
REQUIRED HOLD POINT MAY RESULT IN THE RELEVANT          AGGREGATE MATRIX, UNLESS OTHERWISE NOTED.
WORKS BEING EXCLUDED FROM CERTIFICATION AT                                                                   REINFORCEMENT BAR LAPS                                 N.S.O.P. STANDS FOR 'NOT SHOWN ON PLAN'
COMPLETION.                                             PROVIDE 2N16 TRIMMER BARS TOP AND BOTTOM TO
1. PAVEMENTS:                                           ALL SLAB PENETRATIONS UNLESS NOTED OTHERWISE          U.N.O.    BAR LAPS (mm) SHALL BE AS FOLLOWS:-        2. EXPOSURE CLASSIFICATION
   1.1. SUBGRADE INSPECTION / PROOF ROLL                ON REINFORCEMENT PLANS. BARS TO EXTEND 1000mm                                                               CONCRETE ELEMENTS HAVE BEEN DESIGNED FOR THE
                                                        MINIMUM PAST EDGE OF PENETRATION.                                     BAR LAPS FOR SLABS                    FOLLOWING DURABILITY EXPOSURE CLASSIFICATIONS IN
        PRIOR TO PLACEMENT OF ANY PAVEMENT
                                                                                                                  BAR SIZE          TOP BAR          BOTTOM BAR     ACCORDANCE WITH AS 3600:-
        GRAVELS, VISUAL INSPECTION OF SURFACE FOR
                                                       CONCRETE                                                                                                     EXTERNAL:                  B1
        CONFORMANCE TO FINISHED SURFACE PROFILE         ALL CONCRETE SHALL COMPLY WITH PERFORMANCE                     N12            600                  500
        AND PROOF ROLL REQUIRED.                        REQUIREMENTS AS NOTED ON THE DRAWINGS. A COPY                  N16            900                  700
        IN-SITU CBR AND SUBGRADE COMPACTION             OF ALL DELIVERY DOCUMENTS DETAILING QUANTITIES
                                                                                                                       N20            1200                 950
        TESTING RESULTS REQUIRED AT TIME OF             AND SPECIFICATIONS OF CONCRETE USED ON SITE
        INSPECTION.                                     SHALL BE PROVIDED.                                             N24            1550                 1200
   1.2. PRE-SEAL                                                                                                       N28            1950                 1500
        PRIOR TO PRIME/SEAL APPLICATION, VISUAL
                                                            28 DAY COMPRESSIVE STRENGTH:
                                                                                                                       N32            2300                 1800
        INSPECTION OF SURFACE FOR CONFORMANCE                    COMPONENT                 STRENGTH (f'c)
                                                                                                                       N36            2700                 2100
        TO FINISHED SURFACE PROFILE, PROOF ROLL          SLABS                      32MPa U.N.O.
        REQUIRED.                                        KERB                       25MPa
        COMPACTION TESTING RESULTS, CONFORMANCE                                                               NOTE:
                                                         FOOTPATH                   REFER RS-065              MINIMUM LAP FOR ALL FABRIC SHALL BE ONE MESH
        SURVEY AND ASPHALT/SEAL DESIGN APPROVAL                                                               PLUS 30mm.
        REQUIRED AT TIME OF INSPECTION.                  FIELD INLETS               REFER DS-050
   1.3. CONCRETE REINFORCING INSPECTION                  ACCESS CHAMBERS            REFER DS-010             PLACING
        CBR SUB-BASE MATERIAL IN PLACE WITH              ACCESS CHAMBER ROOFS       REFER RS-065              ALL CONCRETE IS TO BE MECHANICALLY VIBRATED
        FORMWORK, ALL REINFORCING ON CHAIRS AND                                                               DURING PLACING.
                                                         CUSTOM SWD STRUCTURES 32MPa U.N.O.                   CONSTRUCTION JOINTS SHALL BE FORMED AND USED
        TIES IN PLACE
                                                                   CONCRETE ATTRIBUTES                        ONLY WHERE SHOWN ON THE DRAWINGS OR
2. DRAINAGE:                                                                                                  SPECIFICALLY APPROVED BY THE ENGINEER.
   2.1. 1ST PIPE TRENCH AND BEDDING INSPECTION             PARAMETER           'N' CLASS         'S' CLASS
   2.2. 1ST PIPE INSTALLED/JOINTED PRIOR TO BACKFILL                                                         SURFACE FINISH
                                                          56 DAY DRYING
   2.3. MANHOLE BASE SLAB REINFORCING                                        REFER AS1379      650µ MEDIAN
                                                            SHRINKAGE                                         FORMWORK IS TO BE IN ACCORDANCE WITH AS 3610
        PRIOR TO CONCRETE POUR                                                                                "FORMWORK FOR CONCRETE" UNLESS SPECIFIED
                                                             MAXIMUM
   2.4. MANHOLE (CAST IN-SITU) WALL PRE-POUR                                    20mm               20mm       OTHERWISE, CONCRETE IS TO BE A CLASS 3 FINISH
                                                         AGGREGATE SIZE
        BASE SLAB INSTALLED WITH                                                                              WHERE EXPOSED TO VIEW IN THE FINAL PROJECT AND
                                                                SLUMP         80 ± 15mm          80 ± 15mm    CLASS 4 ELSEWHERE.
        INCOMING/OUTGOING PIPES AND SUBSOIL LINES
        IN PLACE. FORMWORK AND REINFORCING                 CEMENT TYPE       REFER AS1379           GP
                                                                                                             CURING
        INSTALLED.                                                           PROJECT TO        PROJECT TO
                                                             CONTROL                                          ADEQUATE MEASURES SHALL BE TAKEN TO CONTROL
   2.5. MANHOLE (CAST IN-SITU) ROOF PRE-POUR                                    AS1379            AS1379      DRYING  SHRINKAGE    OF    CONCRETE  DURING
                                                           TESTING TYPE
                                                                              CLAUSE 6.5        CLAUSE 6.5    PLACEMENT, COMPACTION AND FINISHING.
        BASE SLAB INSTALLED WITH
        INCOMING/OUTGOING PIPES AND SUBSOIL LINES
                                                        TYPICAL DETAIL REFERENCED ABOVE ARE FROM THE          ACCEPTABLE CURING METHODS ARE PONDING,
        IN PLACE. FORMWORK AND REINFORCING                                                                    ABSORPTIVE COVER, LOW PRESSURE STEAM,
                                                        NOOSA SHIRE COUNCIL OR IPWEA STANDARD
        INSTALLED.                                      DRAWINGS AVAILABLE ON COUNCIL'S WEBSITE.              IMPERMEABLE SHEET MEMBRANE AND CURING
3. WATER AUTHORITY (UNITYWATER) INSPECTIONS:                                                                  COMPOUNDS AS PER AS3799 (PVA COMPOUNDS ARE
   INSPECTIONS ARE TO BE CONFIRMED WITH                                                                       NOT PERMITTED).                                                                                                                            CONSULTANT: MPN CONSULTING PTY LTD
   UNITYWATER AND CONSTRUCTION CERTIFIER AT
                                                       REINFORCEMENT                                                                                                                                                                                     CONTACT: TOBY TAWDE MUSPRATT
   PRE-START MEETING.                                   ALL REINFORCEMENT SHALL BE TO CURRENT EDITIONS        CONCRETE PLACEMENT AND COMPACTION IS TO BE                                                                                                 (RPEQ 24982)
                                                        OF AS 4671 U.N.O.                                     COMPLETED WITHIN AN APPROPRIATE TIME.                                                                                                      TELEPHONE: (07) 3335 4595

                                                        SYMBOLS:-                                             NO WATER IS TO BE ADDED TO CONCRETE MIX ON SITE                                                                                                                            DATE 30/01/2026
                                                        E = DEFORMED RIBBED 500MPa EARTHQUAKE                 UNLESS APPROVED AND SPECIFIED BY ENGINEER.
                                                        DUCTILITY BAR (D500E);
                                                        L = DEFORMED RIBBED 500MPa LOW DUCTILITY BAR          USE ALIPHATIC ALCOHOL AS SOON AS SCREEDING IS
                                                        (D500L);                                              FINISHED AS NECESSARY.
                                                        N = DEFORMED RIBBED 500MPa NORMAL DUCTILITY BAR
                                                        (D500N);                                              CURING SHALL COMMENCE ONTO SLABS IMMEDIATELY
                                                        R = ROUND 250MPa NORMAL DUCTILITY BAR (R250N);        AFTER INITIAL SET OF THE CONCRETE OR IMMEDIATELY
                                                        THE NUMBER FOLLOWING THE BAR IS THE NOMINAL           AFTER REMOVAL OF FORMWORK.
                                                        BAR DIAMETER IN MILLIMETRES.
                                                                                                              IN WINDY CONDITIONS, WIND BREAKS SHALL BE                                                                                          C       30.01.26 FOR APPROVAL                                            TTM     LS
                                                        ALL WELDED MESH REINFORCEMENT SHALL BE                ERECTED TO SHIELD THE CONCRETE SURFACES                                                                                            B       28.11.25 OPERATIONAL WORKS                                       TTM     LS
                                                        FABRICATED FROM DEFORMED RIBBED 500MPa BAR            DURING AND AFTER PLACEMENT.
                                                        (D500) U.N.O.                                                                                                                                                                            A       14.11.25 FOR COORDINATION                                        TTM     SR
                                                                                                              CONCRETE PLACEMENT AND CURING PROCEDURES                                                                                           ISSUE DATE                      AMENDMENT                                BY     APP
                                                        REINFORCEMENT SHALL BE BENT COLD IN                   ARE TO BE SUBMITTED TO THE ENGINEER FOR                                                                                            COPYRIGHT: THIS DESIGN AND PLANS ARE NOT TO BE USED OR REPRODUCED WHOLLY OR IN
                                                        ACCORDANCE WITH AS 3600 EXCEPT WHERE                  APPROVAL PRIOR TO CONSTRUCTION.                                                                                                               PART WITHOUT WRITTEN PERMISSION OF MPN CONSULTING PTY LIMITED 2023 ©
                                                        APPROVED BY THE STRUCTURAL ENGINEER.
                                                                                                                                                                                                                                                                                                                ABN: 39 062 191 799
                                                                                                             STRIPPING
                                                        PENETRATION LOCATIONS AND POSITIONS ARE TO BE                                                                                                                                                                                                              P: 61 7 3335 4555
                                                        SUBMITTED TO THE ENGINEER FOR APPROVAL ON             STRIPPING OF FORMS AND REMOVAL OF FORMWORK                                                                                                                                                       E: [email protected]

                                                        EXISTING STRUCTURAL DRAWINGS. DO NOT CUT              SHALL BE IN ACCORDANCE WITH AS 3600 "CONCRETE                                                                                                                                                       Level 4, Building 3,
                                                        REINFORCEMENT ON SITE TO CLEAR PENETRATIONS.          STRUCTURES" CLAUSE 17.6 UNLESS SPECIFICALLY                                                                                                                                                    Kings Row Office Park,
                                                                                                              APPROVED BY THE ENGINEER.                                                                                                                                                       42 McDougall Street, Milton, QLD, 4064
                                                        DISPLACE REINFORCEMENT SLIGHTLY AS NECESSARY
                                                        TO CLEAR BLOCK OUTS.                                                                                                                                                                      CLIENT:




                                                                                                                                                                                                                          NOT FOR CONSTRUCTION
                                                        REINFORCEMENT IS SHOWN DIAGRAMMATIC; IT IS NOT                                                                                                                                            STOCKWELL DEVELOPMENT GROUP PTY LTD
                                                        NECESSARILY SHOWN IN TRUE PROJECTION.                                                                                                                                                     NOOSA EARLY LEARNING CENTRE
                                                        FOR LAPS AND COVERS REFER SCHEDULES ON                                                                                                                                                    LOT 4 NOOSA
                                                        REINFORCEMENT DRAWINGS.                                                                                                                                                                   63-65 HOFMANN DRIVE
                                                                                                                                                                                                                                                  NOOSAVILLE, QLD 4566

                                                                                                                                                                                                                                                                 CONSTRUCTION NOTES
                                                                                                                                                                                                                                                                      SHEET 2
                                                                                                                                                                                                                                                 DESIGN: TTM           DRAWN:     TTM             SCALES:       AS SHOWN
                                                                                                                                                                                                                                                 CHKD:      LS         APPRD:     TTM             DATE:         30.01.2026

                                                                                                                                                                                                                                                      mpn JOB            DRAWING No.                                            REV


                                                                                                                                                                                                                                                    9307 CN.0.03   C

                                                                                                                                                                                                                                                      FOR APPROVAL

Log in to download the original (9307-OPW RFI 1 Civil Plans.pdf)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.