Attached to the e-mail Operational Works Application OPW22/0318 - DA Form 1 - Existing Easement - Existing Easement 2 - Civil Plans - Electrical Reticulation Plan - Owners Consent - 83 Bulter Street Tewantin (lot 1 on RP 864131).
LEGEND
GENERAL NOTES
EXISTING
OVERHEAD CABLE
1. NO OTHER SERVICES TO ENCROACH INTO THE STANDARD
UNDERGROUND ELECTRICITY CORRIDOR OF 0mm - 900mm FROM RPA.
PROPOSED 2. ALL CABLES TO BE INSTALLED IN CONDUIT WITHIN THE STANDARD
OVERHEAD CABLE ELECTRICITY ALIGNMENT ALLOCATED BY THE LOCAL COUNCIL. WHERE
CONDUITS VARY FROM THIS AND AT FOOTPATH CROSSING PROTECTIVE
U70491 STRIP IS TO BE INSTALLED. WHERE PRACTICAL ELECTRICITY CABLES
EXISTING SHALL NOT BE CLOSER THAN 250mm TO THE REAL PROPERTY
UNDERGROUND
CABLE BOUNDARY.
P209281
3. A, B OR C WHEN SHOWN BESIDE LV PILLARS DENOTES SERVICE
u 2C
PROPOSED
Lot 16
PHASING.
UNDERGROUND
4C
RP864131
CABLE
#13 4. THE CONTRACTOR SHALL MEASURE ACTUAL CABLE LENGTHS
E A REQUIRED ON SITE AFTER INSTALLATION OF CONDUITS THEN NOTIFY
PROPOSED ENERGEX/SUPPLIER WHEN CONFIRMING CABLE ORDER.
120 Al 4C P209273
(SP15358
1)
ELECTRICAL
-B/FS1)
/FS
SERVICE CONDUIT 5. ALL BENDS INSTALLED ON 80mm,100mm AND 125mm RETICULATION
-B
Lot 2
58
RP864131 CONDUITS MUST BE 1830mm RADIUS UNLESS OTHERWISE SPECIFIED.
53
ET
P1
1 #85
P302765
DANGER
(S
PROPOSED
6. CONTRACTOR TO SUPPLY ALL LABELS AND SITE ID NUMBERS TO
4C
ELECTRICAL &
U70490
Cu
ENERGEX SPECIFICATION.
COMMUNICATION
KA LIVE UG CABLE
16
SERVICE CONDUITS
T
X
@U70490
R
7. WHEN CROSS ROAD CONDUIT FINISHES OPPOSITE A TRUNCATION PEG,
UM COU
PROPERTY SIDE OF TRENCH TO BE 300mm ALIGNMENT FROM PEG.
POLE
TRANSFORMER 8. WHERE CROSS-ROAD ELECTRICITY CONDUITS RUN PARALLEL TO
OTHER SERVICES OR CONDUITS, A MINIMUM SEPARATION OF 1.0m MUST
GHOSTG
BE MAINTAINED.
PADMOUNT
TRANSFORMER 9. CIVIL CONTRACTOR TO INSTALL ALL CROSS ROAD CONDUITS.
-B/FS1)
16 Cu 4C
IN. 240LV (SP15358-B/FS1)
LOT 5 10. CO-ORDINATE CONDUIT INSTALLATION WITH COMMUNICATIONS
CARRIER CONTRACTORS.
(SP15358
HV POLE DETAIL 'A'
2 KA 11. ELECTRICITY PILLARS TO HAVE 600mm EXCLUSION ZONE. NO
Bϕ UG SUPPLY FROM STN 2 NON-ENERGEX ASSETS TO BE INSTALLED WITHIN THIS EXCLUSION
16 Cu 4C
ZONE.
3
1kV)
HV / LV POLE
(LV)
3-7/3.75 (1
12. ENERGEX REQUIRE 1.0m CLEARANCE BETWEEN SERVICE PILLARS AND
4-7/4.75
U70492
LOT 1
33
DRIVEWAYS. IF LESS THAN 1.0m SEPARATION THEN PROTECTIVE
LV POLE BOLLARDS MUST BE INSTALLED.
OVERHEAD SUPPLY
X
X
Aϕ CONSTRUCTION CONTRACTOR
HV UNDERGROUND AVAILABLE FROM P208295 THE CONTRACTOR SHALL BE RATED BY ENERGEX FOR THE FOLLOWING
POLE TERMINATION T
P PROCESS.
WCS 2 - UNDERGROUND CONSTRUCTION
WCS 31 - COMMISSIONING AND OPERATION OF THE NETWORK
LV UNDERGROUND
POLE TERMINATION
WCS 34 - EARTHING SYSTEMS
WCS 61 - UNDERGROUND CIVIL CONSTRUCTION
S
AERIAL STAY STANDARDS AND SPECIFICATIONS
cϕ THIS WORKS PLAN IS TO BE READ IN CONJUNCTION AND COMPLY WITH THE
FOLLOWING ENERGEX MANUALS AND SPECIFICATIONS
S
GROUND STAY
· OVERHEAD CONSTRUCTION MANUAL
· OVERHEAD DESIGN MANUAL
P208295
EARTH OVERHEAD SUPPLY 4 · UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL
· WCS 61.1 - UNDERGROUND TRENCHLESS TECHNOLOGY
S
Lot 17 AVAILABLE FROM P208295 · NETWORK LABELLING AND SIGNAGE MANUAL
X
RP864131 KA
#22
EXISTING PILLAR Bϕ CONSUMER'S INSTALLATION SHALL COMPLY WITH AS/NZS 3000:2018 - SAA
WIRING RULES.
LOT 2
S
PROPOSED PILLAR FOR DETAILS OF TRENCH CROSS-SECTIONS, REFER TO ENERGEX
UNDERGROUND DISTRIBUTION CONSTRUCTION MANUAL.
LINK PILLAR LOT 4 ON SITE SERVICES CHECKS
240LV
S
UNDERGROUND SERVICES SHOWN ON THIS WORKS PLAN IN THE VICINITY
D UG SUPPLY FROM STN 2 OF PROPOSED EXCAVATION WORKS HAVE BEEN TAKEN FROM ASSET
CONDUIT / CABLE OWNER'S PAPER RECORDS AND ARE INDICATIVE ONLY.
CROSS-SECTION
THE CONTRACTOR IS RESPONSIBLE FOR THE REPAIR OF DAMAGE TO ANY
X KA EXISTING UNDERGROUND ASSETS CAUSED BY HIS WORKS AND THE
S
WATER METER RE-ESTABLISHMENT OF ANY SURVEY MARKS DISLODGED.
Emt ARP864131 THE CONTRACTOR SHALL REQUEST ON-SITE IDENTIFICATION AND
(11kV)
PROPOSED LOCATION OF EXISTING BURIED SERVICES FROM THE QUEENSLAND DIAL
(LV)
DRIVEWAY ENTRY
OVERHEAD SUPPLY BEFORE YOU DIG SERVICE - PHONE: 1100 WEB: www.1100.com.au (A MINIMUM
4-7/4.75
3-7/3.75
37
OF TWO DAYS NOTICE IS REQUIRED)
S
Emt BRP864131
S
PROPOSED ZERO
S
S AVAILABLE FROM P69186 SEWERAGE, STORMWATER, GAS AND WATER PLANS FOR THE SITE MAY BE
LOT IDENTIFIER S
OBTAINED ON REQUEST FROM THE PROJECT SERVICE SUPERVISOR.
LIGHTING 16 Cu 4C S
LOT 3
LEGEND
NOTE: NOT ALL
IN. 240LV ( SP15358-B/ cϕ
REINSTATEMENT NOTES
· BACKFILL & REINSTATEMENT OF FOOTPATH AND ROADWAY TO
SYMBOLS MAY BE
USED
FS1) REDLAND CITY COUNCIL REQUIREMENTS. REFER STANDARD
DRAWINGS:
·· R-RSC-9, TYPICAL SERVICE CORRIDORS AND ALIGNMENTS
LED STREET
·· R-RSC-10, TYPICAL SERVICE CONDUIT SECTIONS
X
LIGHT
P307057
S100 HPS STREET 5
LIGHT SERVICE POLE TO REMAIN
RECOVER UNDERGROUND
Bϕ 4 0 4 8 12 16 20 METRES SERVICE FROM POLE
S150 HPS STREET
LIGHT Emt CSP115873
2 SCALE 1:200 (BEFORE REDUCTION) A
S250 HPS STREET P69186
FILE: \\ADDS\PROJECTS\221869\01 WORKING\A221869A_BOUND
DRIVEWAY
LIGHT CLEARANCE ZONE
EXISTING UNKNOWN
Lot 4 Cϕ
STREET LIGHT
PRELIMINARY ISSUE
(NOT FOR CONSTRUCTION)
DETAIL 'A'
NTS
13/12/2022 3:53 PM
CLIENT SITE CONTACT DETAILS ALIGNMENTS PROJECT
This document is CERTIFICATION:
the property of NAME ENERGEX OH 3.0RP
PROJECT /
SUB PROJECT NO. S2602337 APPROVED:
RPEQ No:
5 LOT RESIDENTIAL SUBDIVISION
Ampflo Pty Ltd SHARON FOLEY ENERGEX UG 0-0.90 PARENT PROJECT NO. - 83 BUTLER STREET, TWEANTIN
DATE:
and may only be COMPANY TELSTRA 2.1-3.0 WORK REQUEST NO. - ELECTRICAL RETICULATION, LEGEND, NOTES
PLOT: 13/12/2022 3:53:54 PM
used for the ABN 28 111 423 842
purpose for ANDY SALMONS TOWN PLANNING ALLIANCE GAS N/A PLANNER & PHONE SUBDIVISIONS
Electrical and Telecommunications
& DETAIL
which it was PHONE (07) 3361 9999 HP GAS N/A LOTS 1-5 Consultants CHECKED: U.STAROWICZ
commissioned. MOBILE - WATER 0.9-2.1 CANCELLING LOTS LOT 1 ON RP864131 ISO 9 0 0 1
Phone : (07) 3372 9280 ISSUE
CERTIFIED DESIGNER: B.BHUJEL DRAWING: A221869
Unauthorised A 13.12.2022 PRELIMINARY ISSUE BB US EMAIL - STORMWATER N/A LOCAL AUTHORITY NOOSA SHIRE COUNCIL Email : [email protected]
use is prohibited. REV DATE DETAILS DRAWN CHECKED APPRVD SEWERAGE 0.9-2.1 PEGGED? ON REQUEST
Q U A L I T Y
MANAGEMENT
Website : ampflo.com.au ISSUE DATE: DATE PROJECT: 221869 SHEET 1 OF 2 A
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 1 page
Page 2
URD CIVIL WORKS SCHEDULE - BY ELECTRICAL CONTRACTOR
CONDUIT LENGTH (m) X-SECTION (m)
STATIONS P100 DRAW
LOCATION 40 HD 100mm 125mm EXCAV TRENCH KERB MARK REMARKS
FROM - TO COMMS WIRE
/TAPE DETAIL
No. m No. m No. m m
GHOSTGUM COURT 1-2 USE EXISITING 80mm CONDUIT
TOTAL
SWITCHING & COMMISSIONING PLAN - LV
(subject to site conditions, amendments by switching co-ordinator
and approval by LV outage co-ordinator)
SWITCHING
1. INSTALL NEW LV UG NETWORK AS PER PLAN
2. BREAK BRIDGES AT U70488 - GHOSTGUM COURT
3. MAKE NEW CONNECTIONS AT U70490(STN 1) -
GHOSTGUM COURT
P307178
4. REMAKE BRIDGES AT U70488- GHOSTGUM COURT
UNDERGROUND CABLE SCHEDULE 5. TEST AND COMMISSION
STATIONS 11kV CABLE 415 VOLT 415 VOLT 240 VOLT 240 VOLT 6. PERFORM POST COMMISSIONING CHECKS
LOCATION FROM - TO EX REC IN 240mm AL TRIPLEX 240mm AL XLPE 16mm 4C 16mm 2C 4mm 2C REMARKS
11AT240XSH LVA4240XPV LVC416XPV LVC216PVPV LVC24PVPV
GHOSTGUM COURT 1-3 * CUT & TERMINATE CABLE AT STN 2
1-2 * * RECOVER EXISTING 16LV CABLE
1-2 * 16
TOTAL 16m P1403561 U1403562
U70483
U70477
U70481 GYMPIE
STREET
U70480
EQUIPMENT SCHEDULE U70478 SP15358
LOCATION STN NO SITE ID EXIST REC INSTALL SIZE AND DESCRIPTION IIN COMP ID PLANT No. MODEL ID QTY LCC REMARKS -B/FS1
GHOSTGUM COURT 1 U70490 * SERVICE PILLAR 1-WAY PI1 1x240LV 1x16LV U70476
* PILLAR MEN EARTHING
* 240mm2 LUG SET LVSPL240 1
2 U12534917 * SERVICE PILLAR 1 -WAY LVSP2-6 1 1x240LV 1x16LV
U1284658 SP1614391/DL
* PILLAR MEN EARTHING PI1 LV4CMEN 1 L1
(OPEN)
URT
BANK CO
-B/FS1
SP15358 U1284657
STRINGY
SP15358
CONSUMER CONDUIT SCHEDULE - BY CIVIL CONTRACTOR GROUND LEVEL
T
M COUR
FROM TO ELECTRICAL (m) COMMS (m)
-B/FS1
LOCATION REMARKS
STN LOT 40HD 50HD 63HD 80HD 20MD 50MD
U
450mm
GHOSTG
18
SP15358
GHOSTGUM STREET 2 4
TOTAL 18m TAPE
600mm
STREET
-B/FS1
COM U1284659
BUTTLER
SP15358
COMMS
AS REQUIRED
E E
U70498
U70488
SUMMARY SHEET - S2602337
ELECTRICAL CONDUITS
UNDERGROUND MATERIALS 1
(Supplied by the URD Contractor) (Supplied by the URD Contractor)
AS REQUIRED U70490
P302765
(OPEN)
/FS1
MODEL No. No. OFF MODEL No. No. OFF
SECTION VIEW
SP3382-A
2
LVSP2-6 1 LV4CMEN 2
LVSPL240 1 LVC4240XPV 16
SHARED TRENCH ELECTRICAL / COMMS / WATER
TOTAL 0
TRENCH LENGTH
ELECTRICAL & COMMUNICATIONS SERVICE
URD CONTRACTOR SHALL NOTE THAT THIS SUMMARY SHEET MUST NOT BE USED FOR TENDER PURPOSES.
CONDUITS (by Civil contractor )
THE CONTRACTOR SHALL CHECK QUANTITIES AGAINST ACTUAL SCHEDULES ON THESE DRAWINGS. EXISTING & PROPOSED LV SCHEMATIC DIAGRAM
SCALE NTS
Electrical and communication conduits to be installed in compliance with AS/NZ
3000 (SAA Wiring Rules). ALL NEW LV CABLES TO BE 240mm 4c Al XLPE UNO
· Electrical main conduit to be minimum as required orange heavy duty PVC
· Electrical service conduit to be minimum as required orange heavy duty PVC
· Communications conduit refer pit and pipe design
FILE: \\ADDS\PROJECTS\221869\01 WORKING\A221869A_BOUND
· Protective cover strip to be laid above all service conduits.
· All conduits to be installed with draw wire.
PRELIMINARY ISSUE
(NOT FOR CONSTRUCTION)
13/12/2022 3:53 PM
CLIENT SITE CONTACT DETAILS ALIGNMENTS PROJECT
This document is CERTIFICATION:
the property of NAME ENERGEX OH 3.0RP
PROJECT /
SUB PROJECT NO. S2602337 APPROVED:
RPEQ No:
5 LOT RESIDENTIAL SUBDIVISION
Ampflo Pty Ltd SHARON FOLEY ENERGEX UG 0-0.90 PARENT PROJECT NO. - 83 BUTLER STREET, TWEANTIN
DATE:
and may only be COMPANY TELSTRA 2.1-3.0 WORK REQUEST NO. - SCHEDULES, SCHEMATICS &
PLOT: 13/12/2022 3:53:56 PM
used for the ABN 28 111 423 842
purpose for ANDY SALMONS TOWN PLANNING ALLIANCE GAS N/A PLANNER & PHONE SUBDIVISIONS
Electrical and Telecommunications
COMMISSIONING PLAN
which it was PHONE (07) 3361 9999 HP GAS N/A LOTS 1-5 Consultants CHECKED: U.STAROWICZ
commissioned. MOBILE - WATER 0.9-2.1 CANCELLING LOTS LOT 1 ON RP864131 ISO 9 0 0 1
Phone : (07) 3372 9280 ISSUE
CERTIFIED DESIGNER: B.BHUJEL DRAWING: A221869
Unauthorised A 13.12.2022 PRELIMINARY ISSUE BB US EMAIL - STORMWATER N/A LOCAL AUTHORITY NOOSA SHIRE COUNCIL Email : [email protected]
use is prohibited. REV DATE DETAILS DRAWN CHECKED APPRVD SEWERAGE 0.9-2.1 PEGGED? ON REQUEST
Q U A L I T Y
MANAGEMENT
Website : ampflo.com.au ISSUE DATE: DATE PROJECT: 221869 SHEET 2 OF 2 A