([D)MWH.                                              Noosa on Weyba Water Network Performance Assessment




   1              Introduction
   MWH have been engaged by Unitywater to undertake a water network performance assessment of the
   proposed Noosa on Weyba development. Three initial supply options have been developed and are
   included within the assessment brief prepared by Cardno (refer to Appendix A).

  The proposed development is located off Old Hollett Road  near Walter Hay Drive. It will be serviced

  from     within  existing Noosa Industrial DMA (NIDMA) with storage provided at the Tewantin
                     the
  Reservoirs. Option 1 is to connect a 300 mm diameter main into the existing 375 mm diameter trunk
  main along Eenie Creek Road and serve as the primary connection to the development site. Options two
  and three assessed the potential for a secondary 200 mm diameter connection from the existing
  150 mm diameter main in Lake Entrance Boulevard. Details of the network layout for the three supply
  options assessed can be found in the Cardno Report (Appendix A).

   1.1            Methodology
  The assessment has applied the following methodology:

             The assessment has been carried out using H20MAP Water.

             The demands (EPs)for the Noosa on Weyba development site were developed by Cardno and
             adopted for use in the ’Unitywater Planning Model           -
                                                                             Water’. Demand       was   distributed to
             junction/s at the boundary of the development.
             The water network within the NIDMA was reviewed against the latest pipe GIS layer and the
             model was updated to reflect the existing water network.

             Fire flow demands were added to junctions within NIDMA and a fire flow assessment was run to
             determine the critical fire flow junction.

             The model     was   used to   assess      supply network performance for the three supply
                                                    the water
             options. The network      was    assessed    with
                                                        and without the proposed development under
             maximum hour and fire flow demand conditions during the Ultimate planning horizon.


   1.2            Assumptions
  The performance assessment of the water supply network has been undertaken assuming the following:

             The development demands for assessment were            provided by Cardno along with calculations,
             and assumptions. MWH have confirmed that demand conversion factors used are inline with the
             Noosa Planning Scheme Policy and no revision is necessary.

             Along with the "no-development" scenario, the three options proposed within the assessment
             brief were the only options assessed.

             Only the full development solution        was   assessed.   No interim     development stages were
             investigated.
             The assessment has provided results to the boundary of the development only. No internal
             water supply network was investigated and internal water supply network head losses were not
             assessed.




  Status: Draft                                                                                                 22/06/2012
   Project number:                                         Page 1               Our ref: Noosa on Weyba WS Assessment.docx

Used in these records

About this file

File size
29.5 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Part 7 of 37 Appendix 5 - Water and Sewer Infrastructure Report MCU12_0208.pdf · 29.5 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.