Attached to the e-mail Response to Information Request MCU16/0079 (email 2 of 3).
Code Location Tolerance Description
(Drawing)
A Between top section Equal distance between the The distance is to ensure that any object
and underside of unit and the underside of the entering the pit, through the kerb inlet, will
grate grate to that between the kerb not cause any blockages
lintel and the gutter invert.
B Between the cage A minimum of 70mm. A This distance is to ensure that unit will not
walls and the pit maximum of 300mm (without cause material to accumulate between the
unit modification) pit walls and the cage and that standard
plastic sizes can be used.
C Between the cage A minimum of 70mm. This distance is to ensure that unit will not
base and the pit cause material to accumulate between the
pit base and the cage.
D Into through flow Maximum of the top ¼ of the To ensure that the through pipe is not
pipe pipe can be obstructed by the obstructed.
cage.
Kerb Lintel
A
A
A
Or
Cage
Cage
B Min B Min B Min
B Min 70mm 70mm 70mm
70mm D - ¼ Diameter
C Min
70mm
Diameter
©2013 Stormwater360 | EnviroPod Installation Manual 3