MCU21.0193-Att 1 Acoustic Report
4. BCC Cinema Noosa Test Results
The results of the measurements from BCC Cinema Noosa are presented in the table below:
Table 3: Results of Free Weights (BCC Cinema Noosa)
Receiver Background Floor Test Lmax Vibration
Drop Area Audibility
Room L90 (dBA) Sample Scenario (dBA) Impact
SMAI
Rubber Clearly
57 Moderate
Gym Audible
Flooring
Free Weights
Single Layer 25kg
Area Foyer Clearly
45 Regupol Dumbbell 55 Moderate
(Location 1) Audible
4080
Double
Layer
54 Minor Audible
Regupol
4080
SMAI
Rubber Clearly
46 Moderate
Gym Audible
Flooring
Free Weights
Single Layer 25kg
Area Cinema 1
34 Regupol Dumbbell 37 Minor Audible
(Location 1) (Level 1)
4080
Double
Layer Just
35 Minor
Regupol Audible
4080
Weight drops from the 25kg Dumbbell conducted on the proposed floor SMAI Rubber
Flooring again produced significant noise and vibration impacts to the adjacent foyer and the
cinema above. The double layer of Regupol 4080 was able to significantly reduce the
vibration impact and audibility of weight drops in the foyer and cinema.
4.1 Wall (Airborne Noise) Test Results
An airborne noise transmission test was conducted through the intertenancy wall. The results
of the wall testing are presented in Table 2 as follows;
Table 4: Wall Transmission Loss Test Results
Source Receiver DnT,w Ctr DnT,w + Ctr
Lift Strength and BCC Cinema Noosa
24 -1 23
Conditioning Noosa - Foyer
The result is based on the overall composite sound transmission loss of the wall partition. As
the wall tested is a temporary tenancy wall, recommendations will be made to reduce the
noise in the neighbouring tenancy. See Section 5.2 for recommendations.