Noise Report
• Worst-case noise criteria at receiver: acoustic quality objectives - day & evening indoor 35dB(A) (outdoor
42dBA), night indoor 30dB(A) (outdoor 37dBA).
• Room façade height: 4m
• Façade open configuration: opening of max 50% of façade (operable windows / doors)
Based on the above assumptions, Table 9 presents the predicted maximum allowable internal patron and/or
amplified sound/music levels. Calculations are included in Appendix C.
Table 9: Indicative Maximum Allowable Internal Sound Level Predictions
Indicative Maximum Allowable Internal
Façade Reverberant Sound Level L eq dB(A)*
Façade
Room Min. Sound Day Evening Night
Configuration
Rating Rw
7am – 6pm 6pm – 10pm 10pm – 12am
Façade closed 107 107 102
Function rooms
Min. Rw32
(central)
Façade open 80 80 75
Façade closed 103 103 98
Function space
Min. Rw38
(southwest)
Façade open 70 70 65
*Measured at centre of room equidistant from any speakers
The predicted maximum allowable internal sound levels for patron and/or amplified sound/music are
expected to be adequate for operation of the function room during all time periods with the façade closed.
Function room façades may be open during the day/evening period (7am – 10pm) for:
• Patron noise and background amplified sound/music only
• Function space (southwest) to have southwest façade closed for any use
Function room façades to be closed for:
• Use of amplified sound/music during any time period (louder than background music)
• Any use during the night period (10pm – 12am)
Refer to Section 7 for recommended noise mitigation measures.
Site: 3 - 7 Serenity Place, Noosa 18
Reference: 22BRA0079 R01_1