4707_FOSTER AND BLACK - Working Drawings ISSUE B · 51901.4863.08

of 22

Text shows just the words. Original shows the document exactly as it was published.

Very large file (15.6 MB): the original may take a few minutes to open or download. The page text below is quick to read.

                                                                                                                                                                            A                                                                                                                         B
FINAL DETAILS TO SHOPFITTER/CABINET MAKERS SPECIFICATIONS
ALL CABINETRY TO HAVE ADJUSTABLE SHELVING
                                                                                                                                                                                                                                                5,305
FINAL EQUIPEMENT SIZES (FRIDGES, BINS, DISHWASHERS,
CASHDRAWER, SINK, JUG RINERS ETC) TO BE CONFIRM BY CLIENTS
PRIOR TO CABINETRY CONSTRUCTION
ALLOW FOR SERVICES DUCT BEHIND/THROUGH CABINETRY FOR
PLUMBING AND POWER SERVICES                                                   STRICTLY NO VISIBLE METAL CAPPINGS / FLASHINGS TO TOP OR                                                                                                          NL-1
                                                                                 SIDES OF TILED ROOF (TYPICAL) - INSTALLATION TO COMPLY
                                                                                    WITH MANUFACTURES SPEC. - REFER SECTION & DETAILS
                                                                                                                                                                                                                                                                                                                                          APPROX. TOP OF EXISTING 3.400
                                                                                                                                                                                                                                                                     [email protected]° ROOF PITCH
                                                                                                                                                                                                                                                                                                                                  PROPOSED TOP OF ROOF R.L. 3.320 (NOM)
                                                                                                                                                                                                               H
                                                                                                                                                                                                        OF PITC                                                                                    SK1N
                                                                                          NO VISIBLE GUTTERING (AS PER EXISTING STRUTURE -                                                       5.5° RO                                                                                                                          EXISTING AC CONDENSOR UNIT RELOCATED -
                                                                                       INSTALLATION TO COMPLY WITH MANUFACTURES SPEC. -                                                    RF @ 1                                                                                        AC                                       NEW WALL BRACKETS (TO BE SLIM PROFILE)




                                                                                                                                                                                                                                                                                                                                                                                970
                                                                                            REFER SECTION & DETAILS (SUBJECT TO APPROVAL)                                                                                                                    RL 2.602 (NOM)
                                                                                                                                                                                                                           PMF
                                                                                                       SLIM PROFILE ALUMINIUM POWDERCOATED
                                                                                                    PERIMETER FRAMING AROUND OPENINGS (PC-T                                                                                                                                                        SK1N
                                                                                                    COLOUR) TO CAP ENDS OF SK1N TILE CLADDING                                                                                                                                                                                                            CEILING HEIGHT 2.350


                                                                                                                                                                                                                                                                                                                                  PROPOSED FRAMING TO BOX OUT EXISTING
                                                                                                                                                                                                                                                                                                                                  STEPPED CORNER - SUBJECT TO APPROVAL




                                                                                                                                                                                                                                                                                                                                                                                        3,320
                                                                                                        WALL MOUNTED REVERSE OSMOSIS WATER




                                                                                                                                                            NL-2A
                                                                                                             FILTER SYSTEM - SUPPLIED BY OWNER
                                                                                                                     (WITHIN SERVICE CUPBOARD)                                                                                                     CL
                                                                                                  EXISTING SERVICE DOOR TO REMAIN - RE-PAINTED




                                                                                                                                                                                                              2,040 NOM




                                                                                                                                                                                                                                                                                                                                                                                2,350
                                                                                                                                                                                                              (EXISTING)
                                                                                                        TO DARK COLOUR (TBC BY CLIENT), REPLACE                                                                                                                             EDB
                                                                                                   HANDLE AND LOCK (BLACK SELECTION BY CLIENT

                                                                                    EXISTING MAIN DOOR TO REMAIN - RE-PAINTED - DARK                                                                                                                                                                         BEN
                                                                              COLOUR EXTERNALLY AND GREEN INTERNALLY (TBC BY CLIENT),
                                                                                  REPLACE HANDLE AND LOCK (BLACK SELECTION BY CLIENT
                                                                                                    ALUMINIUM PERIMETER KICK (PC-T FINISH) - TO                                                                                                             WATER
                                                                                                  ALLOW FOR CLADDING FINISH TO STOP ABOVE FGL




                                                                                                                                                                                                          (NOM)
                                                                                                                                                                                                                                                                                                                                            FLOOR LEVEL 0.000 (EXISTING)




                                                                                                                                                                                                            50
                                                                                                                                                                                                                                                                                                                        TDK




                                                                                                                                                                     01 Eleva on 01 (West)
                                                                                                                                                                                    1:50

                                                                                                                                                                            A                                                                                                                         B

                                                                                                                                                                                                                                 NL-1
                                                  STRICTLY NO VISIBLE METAL CAPPINGS / FLASHINGS TO TOP OR
                                                     SIDES OF TILED ROOF (TYPICAL) - INSTALLATION TO COMPLY
                                                        WITH MANUFACTURES SPEC. - REFER SECTION & DETAILS
                                                                                                                                                                                                                                                                                                             APPROX. TOP OF EXISTING 3.400
                                                                                                                                                                                            H
                                                                                                                                                                                        PITC SK1N                                                                 RF @                              PROPOSED TOP OF ROOF R.L. 3.320 (NOM)
                                                                                                                                                                                 ° ROOF                                                                                  15.5°
                                                                                                                                                                                                                                                                               ROOF
                                                                                                                                                                              5.5
                                                                                                                                                                       RF   @1                                                                                                      PITCH




                                                                                                                                                                                                                                                                                                                                                 970
                                                                                                                                                                                                                                                                                                RL 2.602 (NOM)
                                                          NO VISIBLE GUTTERING (AS PER EXISTING STRUTURE -
                                                       INSTALLATION TO COMPLY WITH MANUFACTURES SPEC. -
                                                            REFER SECTION & DETAILS (SUBJECT TO APPROVAL)                                                                                                                                                                                SK1N
                                                                                                                                                                                                                                                                                                                        CEILING HEIGHT 2.350


                                                                      SLIM PROFILE ALUMINIUM POWDERCOATED
                                                                   PERIMETER FRAMING AROUND OPENINGS (PC-T




                                                                                                                                                                                                                                                                                                                                                          3,320
                                                                                                                                                                                                                                        1,280




                                                                                                                                                                                                                                                                                                    1,400
                                                                                                                                                                                                                                                                                                    NL-2A
                                                                                                                                                           NL-2B




                                                                   COLOUR) TO CAP ENDS OF SK1N TILE CLADDING

                                                        AWNING WINDOW WITH TINTED+FLUTED GLASS - DUAL




                                                                                                                                                                                                                                                                                                                                                 2,350
                                                              COLOUR FRAMING - SILL FRAME TO BE CUSTOM                                                                                                                                                                            POS
                                                            TERRACOTTA COLOUR - WINDOW / GLASS FRAME                                                                    A                                                        A
                                                             SURROUND DARK COLOUR - DETAILS BY OTHERS
                                                                                                                                                                                                                                                                                  NL-3
                                                                        PROPOSED FRAMING TO BOX OUT EXISTING




                                                                                                                                                                                                                                                                                         300
                                                                         STEPPED CORNER - SUBJECT TO APPROVAL                                                                           CL                                                                   CL
                                                                                                                                                                                                                                        940




                                                                                                                                                                                                                                                                                                       880
                                                                 ALUMINIUM PERIMETER KICK (PC-T FINISH) - TO




                                                                                                                                                                                                                                                                                         500
                                                               ALLOW FOR CLADDING FINISH TO STOP ABOVE FGL
                                                                                                                                                                                                                                                                                                                 FLOOR LEVEL 0.000 (EXISTING)




                                                                                                                                                                    02 Eleva on 02 (North)
                                                                                                                                                                                1:50
                                                                                                                                                                                                                                                                                                                                             0            1        2                            5                              10
                                                       Revision                                                             Notes.                                                                                                                                                 Project                                    Client                                Drawing                         Date                   Author


                 reitsma
                                                       Issue B - 23.06.2025                                                 Figured dimensions only are to be taken from this drawing.            All works must comply with NCC, local authority and all
                                                       - Increase Awning Window heights                                     All dimensions, bearings, exis ng services, mandatory council         relevant geographical/wind category requirements. All                            FOSTER & BLACK - HASTINGS                  FOSTER & BLACK                        Eleva ons 1+2                   24/06/2025               JTL
                                                       - Change Awnings to Fluted Glass ( nted)
                                                       - reduce overhead shelves                                            restraints/requirements and proposed levels are to be checked and     cut and fill ba ers are indica ve only and must be                                                                                                                                                 Scale                 Revision
                                                                                                                            verified on site by builder/client prior to commencement of works.     established and verified by builder/client in rela on to
                                                                                                                            Any discrepancies must be communicated to the designer prior to       proposed slab and/or floor levels                                                 SHOP 8 (No. 18) HASTINGS ST. Builder                                                                               1:50                     B
                                                                                                                                                                                                                                                              N




      +61 493 062 182       13 Ridgewood Road.                                                                              commencement of works. Please note, builder specifica ons and          These drawings are to be read in conjunc on with other                                                        ADDITION PROJECTS                                   Stage
                                     Caloundra                                                                              signed contracts to take precedence over all Reitsma documenta on.    relevant consultants drawings and reports.                                       NOOSA HEADS                  P: 0481 000 118                                     CONSTRUCTION                    Project Number   Sheet Number
      [email protected]            QLD, 4551
      www.reitsma.com.au              Australia
                                                                                                                            © Reitsma+Associates Pty Ltd. A.T.F The Reitsma Family Trust ABN 62 631 178 013 - ACN 158 385 767
                                                                                                                            QBCC Lic. No. 1234490 BDAQ Member
                                                                                                                                                                                                                                                                                   QLD     4567                                                                     DOCUMENTATION                   4707                  7 /22

Used in these records

About this file

File size
15.6 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

4707_FOSTER AND BLACK - Working Drawings ISSUE B.pdf · 15.6 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.