130814 Acoustic Report 230913 · MCU13/0171

of 36

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

Cooroy Property Trust Pty Ltd c/- Lavin Trading
Environmental Noise Level Study for Proposed Wimmers Soft Drink Manufacturing Facility,
271 Lake Macdonald Drive, Lake Macdonald                                                                    Page 11 of 32




                                      55 dB(A) LAmax,T @ 30 m – 18 (distance) – 3 (ground) = 34 dB(A);

•   forklift operating:               78 dB(A) LA10,adj,T @ 10 m – 28 (distance) – 5 (building) = 45 dB(A);

                                      80 dB(A) LAmax,T @ 10 m – 28 (distance) – 5 (building) = 47 dB(A);

•   waste collection vehicle:         73 dB(A) LA10,adj,T @ 10 m – 28 (distance) – 3 (ground) = 42 dB(A);

                                      73 dB(A) LAmax,T @ 10 m – 28 (distance) – 3 (ground) = 42 dB(A);

•   manufacturing:                    90 dB(A) LA10,adj,T @ 1 m – 5 (inside to outside factory via open doors) –
                                      42 (distance) – 4 (ground) = 39 dB(A);

                                      92 dB(A) LAmax,T @ 1 m – 5 (inside to outside factory via open doors) –
                                      42 (distance) – 4 (ground) = 41 dB(A).

Steady state noise

•   office airconditioning unit:                82 dB(A) SWL – 54 (distance) – 8 (building) = 20 dB(A);

•   cooling tower:                              80 dB(A) LA10,adj,T @ 1 m – 47 (distance) – 8 (building) = 25
                                                dB(A);

•   exhaust fans:                               65 dB(A) LA10,adj,T @ 1 m + 10 (ten to 12 fans operating) – 48
                                                (distance) – 5 (barrier, roof edge) = 22 dB(A);

•   pumps:                                      70 dB(A) LA10,adj,T @ 1 m + 10 (ten to twelve pumps operating)
                                                – 48 (distance) – 8 (building) = 24 dB(A);

•   combined noise:                             20 + 25 + 22 + 24 = 29 dB(A) LA10,adj,T.

All of the above noise sources comply with the time varying and steady state noise limits at the closest
residence to the east.


Closest Residence to South-East

At the closest residence to the south-east of the subject site, for the closest possible location of the
nominated noise source, source noise levels will be:

Time varying noise

•   semi driving on site:             70 dB(A) LA10,adj,T @ 8 m – 28 (distance) – 2 (ground) = 40 dB(A);

                                      72 dB(A) LAmax,T @ 8 m – 28 (distance) – 2 (ground) = 42 dB(A);

•   truck door closing:               58 dB(A) LA10,adj,T @ 30 m – 18 (distance) – 8 (building) = 32 dB(A);

                                      60 dB(A) LAmax,T @ 30 m – 18 (distance) – 8 (building) = 34 dB(A);

•   truck engine starting:            58 dB(A) LA10,adj,T @ 30 m – 18 (distance) – 8 (building) = 32 dB(A);

                                      60 dB(A) LAmax,T @ 30 m – 18 (distance) – 8 (building) = 34 dB(A);

•   truck air brakes:                 80 dB(A) LA10,adj,T @ 25 m – 20 (distance) – 8 (building) = 52 dB(A);

                                      80 dB(A) LAmax,T @ 25 m – 20 (distance) – 8 (building) = 52 dB(A);



David Moore & Associates Pty Ltd                                               Our reference: R13095/D2847/Rev.0/23.09.13

Used in these records

About this file

File size
2.4 MB (large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

130814 Acoustic Report 230913.pdf · 2.4 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.