Part 6 of 37 Appendix 3 - Geotechnical Assessment MCU12/0208

of 95

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

Very large file (49.3 MB): the whole original can take several minutes to open, especially on a phone. Text is quick to read.

                                                                                                    Noosa on Weyba



It is recommended that a concrete           path with impermeable membrane under, or buried membrane about
1.5m   -
           2m wide, completely surround each residential building to protect the foundation soils from seasonal
moisture variations.    Gardens and lawns (placed over buried membranes) adjacent the building should not
be over-watered. Moderate, frequent watering is the most suitable. Gardens should not be concentrated in
one area but should be      spread evenly around the building.

5.3        Effluent Disposal Characteristics

As part of the effluent disposal assessment to be carried out by others, it was requested that the following
tests be carried out to provide an indication of permeability characteristics;

                                .      Textural classifications

                                .      Emerson Class Tests

                                .      Insitu Permeability Tests

Textural Classifications

A total of 16 textural classifications were carried out at varying depths and borehole locations across the site.
These are summarised in Table 4.

The results indicated a variety of soil types across the site ranging from loamy sand to medium clays. Some
classification test results indicated some heavy clays may also exist across the site.

Emerson Class Tests

A total of 11 Emerson Class tests were carried out across the site. These are summarised in Table 3.

The results indicated some variability in dispersiveness across the site.

All 3 samples from the Northbrook title indicated partial or complete dispersion.      Only 1 sample from BH9 on
the Hofman title showed partial dispersion.

Insitu Permeability Tests

A total of 7 constant head permeability tests were carried out across the site. The results are summarised in
Table 7 below.

Table 7: Permeability Results




       BH No.                 Depth                 Saturated Hydraulic conductivity, KSAT

                               (m)                                 (m/day)

            1                0.0-1.0                                0.02

            9                0.0-1.0                                0.05

           12                0.0-1.0                                 1.32

           20                0.0-1.0                                2.20

           32                0.0-1.0                                0.02

           17                0.0-1.0                                0.01

           18                0.0-1.0                                0.01



The permeability test results show some variability between the sand and clay strata.




Prepared for Cardno (Old)                                                                                  Page 17

Used in these records

About this file

File size
49.3 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Part 6 of 37 Appendix 3 - Geotechnical Assessment MCU12_0208.pdf · 49.3 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.