Part 6 of 37 Appendix 3 - Geotechnical Assessment MCU12/0208

of 95

Text shows just the words. Original shows the document exactly as it was published.

Check the original when the exact wording matters.

Very large file (49.3 MB): the whole original can take several minutes to open, especially on a phone. Text is quick to read.

                                                                                                     Noosa on Weyba




                    S                      Land where acid sulphate soils occur within 5m of the surface

                   NS1                  Land <5m AHD with low probability of ASS occurrence, limited field
                                                         assessment has been carried out

                   NS2                   Land >5m AHD with low or negligible probability of ASS, treatment

                                                      mayor may not have been carried out

It is generally considered that ASS could potentially occur in areas lying below 5m AHD.


6.1      pH Tests
A total of 64 samples were recovered with a pHF and pHlox test carried out on each sample. The field tests

provided an indication as to the likelihood of the tested soils being actual or potential ASS. The results of the
reactions are detailed on the field pH reports attached in Annex A.


pHF Indicator

Premise: If the field pH is below pH4, the material is likely to contain Actual ASS (AASS).


Result: The field pH readings for all samples were above the threshold of pH 4. This indicated that actual
ASS were unlikely to be present at the tested locations.


pHFOX Indicators

Premise: If the pHFOX result is lower than 3 (the extremely acid range), this is a strong indication of Potential
Acid Sulfate Soils (PASS).


Results: The pHFOX results for all samples were above the threshold of 3 which indicates PASS were not

likely to be present.

Premise: The stronger the reaction with peroxide in the pHFOX test (in terms of gentle fizzing versus violent

effervescing) the more likely the material contains PASS.

Results: A visual assessment on the severity of the reaction that occurred immediately after adding hydrogen

peroxide to the insitu material was recorded. This result was recorded as being mild in 19% of the samples
and no reaction was recorded in the remaining 81 %. This indicated that PASS were not likely to be present.


Premise: If the pHFOX differs by more than 1 pH unit below the pHF, the material is likely to be PASS, with the

greater the difference the stronger the indication.

Results: 28 of the pHFOX readings (44% of samples taken) were greater than 1 pH unit from the field             pH
reading, indicating PASS material may not be present. The difference was close to 1 pH in most samples with
only a handful of samples with a difference of >1.5pH.

Overall, the pHFOX results and the other indicators showed a low likelihood of PASS at the tested locations.

These indicator test results were used to select samples for more definitive laboratory testing.




Prepared for Cardno (Old)                                                                                    Page 19

Used in these records

About this file

File size
49.3 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Part 6 of 37 Appendix 3 - Geotechnical Assessment MCU12_0208.pdf · 49.3 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.