Part 6 of 37 Appendix 3 - Geotechnical Assessment MCU12/0208
Very large file (49.3 MB): the whole original can take several minutes to open, especially on a phone. Text is quick to read.
Noosa on Weyba
S Land where acid sulphate soils occur within 5m of the surface
NS1 Land <5m AHD with low probability of ASS occurrence, limited field
assessment has been carried out
NS2 Land >5m AHD with low or negligible probability of ASS, treatment
mayor may not have been carried out
It is generally considered that ASS could potentially occur in areas lying below 5m AHD.
6.1 pH Tests
A total of 64 samples were recovered with a pHF and pHlox test carried out on each sample. The field tests
provided an indication as to the likelihood of the tested soils being actual or potential ASS. The results of the
reactions are detailed on the field pH reports attached in Annex A.
pHF Indicator
Premise: If the field pH is below pH4, the material is likely to contain Actual ASS (AASS).
Result: The field pH readings for all samples were above the threshold of pH 4. This indicated that actual
ASS were unlikely to be present at the tested locations.
pHFOX Indicators
Premise: If the pHFOX result is lower than 3 (the extremely acid range), this is a strong indication of Potential
Acid Sulfate Soils (PASS).
Results: The pHFOX results for all samples were above the threshold of 3 which indicates PASS were not
likely to be present.
Premise: The stronger the reaction with peroxide in the pHFOX test (in terms of gentle fizzing versus violent
effervescing) the more likely the material contains PASS.
Results: A visual assessment on the severity of the reaction that occurred immediately after adding hydrogen
peroxide to the insitu material was recorded. This result was recorded as being mild in 19% of the samples
and no reaction was recorded in the remaining 81 %. This indicated that PASS were not likely to be present.
Premise: If the pHFOX differs by more than 1 pH unit below the pHF, the material is likely to be PASS, with the
greater the difference the stronger the indication.
Results: 28 of the pHFOX readings (44% of samples taken) were greater than 1 pH unit from the field pH
reading, indicating PASS material may not be present. The difference was close to 1 pH in most samples with
only a handful of samples with a difference of >1.5pH.
Overall, the pHFOX results and the other indicators showed a low likelihood of PASS at the tested locations.
These indicator test results were used to select samples for more definitive laboratory testing.
Prepared for Cardno (Old) Page 19
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Part 6 of 37 Appendix 3 - Geotechnical Assessment MCU12/0208Related documentApplication case desk ↗
About this file
- File size
- 49.3 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.