STORMWATER MANAGEMENT PLAN 5 4.2.2 Manning’s ‘n’ Values for the dimensionless Manning’s ‘n’ coefficient for open channel and piped flows were ig pip assigned according to Table 4.1 in accordance with QUDM. Table 4.1: Study Manning’s ‘n’ Conduit condition Manning’s ‘n’ Grassed, Landscaped Swales 0.045 Reinforced Concrete 0.014 4.2.3 Energy Loss Coefficients Entrance and exit loss coefficients were utilised according to Table 4.2 in general accordance with QUDM. Table 4.2: Pipe Energy Loss Coefficients Energy Loss Loss Coefficient Entry Loss 0.5 Exit Loss 0.2 4.2.4 Infiltration Characteristics The Horton infiltration method was adopted for the drainage study. The values used for maximum infiltration rate, minimum infiltration rate and decay rate of infiltration were 10mm/hr, Imm/hr, and 0.0001/sec respectively for pervious areas and 1mm/hr, 1mm/hr, and 0.000 l/sec respectively for impervious areas BARLOW GREGG VOM M3048 DECEMBER 2007