Method Blank (MB) and Laboratory Control Sample (LCS) Report
The quality control term Method / Laboratory Blank refers to an analyte free matrix to which all reagents are added in the same volumes or proportions as used in standard sample preparation. The purpose of this QC
parameter is to monitor potential laboratory contamination. The quality control term Laboratory Control Sample (LCS) refers to a certified reference material, or a known interference free matrix spiked with target
analytes. The purpose of this QC parameter is to monitor method precision and accuracy independent of sample matrix. Dynamic Recovery Limits are based on statistical evaluation of processed LCS.
Sub-Matrix: SOIL Method Blank (MB) Laboratory Control Spike (LCS) Report
Report Spike Spike Recovery (%) Acceptable Limits (%)
Method: Compound CAS Number LOR Unit Result Concentration LCS Low High
EG005(ED093)T: Total Metals by ICP-AES (QCLot: 4934343)
EG005T: Chromium 7440-47-3 2 mg/kg <2 15 mg/kg 107 83.0 125
EN33: TCLP Leach - Inorganics/Non-Volatile Organics (Glass Vessel) (QCLot: 4932852)
EN33a-G: Final pH ---- 0.1 pH Unit 5.0 ---- ---- ---- ----
EG048: Hexavalent Chromium (Alkaline Digest) (QCLot: 4934344)
EG048G: Hexavalent Chromium 18540-29-9 0.5 mg/kg <0.5 20 mg/kg 109 80.0 120
<0.5 13.93 mg/kg 123 70.0 130
Sub-Matrix: WATER Method Blank (MB) Laboratory Control Spike (LCS) Report
Report Spike Spike Recovery (%) Acceptable Limits (%)
Method: Compound CAS Number LOR Unit Result Concentration LCS Low High
EG005(ED093)C: Leachable Metals by ICPAES (QCLot: 4943154)
EG005C: Arsenic 7440-38-2 0.1 mg/L <0.1 0.1 mg/L 115 89.0 123
EG005C: Cadmium 7440-43-9 0.05 mg/L <0.05 0.1 mg/L 100.0 88.0 120
EG005C: Chromium 7440-47-3 0.1 mg/L <0.1 0.1 mg/L 102 86.0 115
EG005C: Copper 7440-50-8 0.1 mg/L <0.1 0.1 mg/L 102 87.0 117
EG005C: Lead 7439-92-1 0.1 mg/L <0.1 0.1 mg/L 85.7 85.0 117
EG005C: Nickel 7440-02-0 0.1 mg/L <0.1 0.1 mg/L 103 90.0 116
EG005C: Zinc 7440-66-6 0.1 mg/L <0.1 0.1 mg/L 98.6 87.0 122
EG035C: Leachable Mercury by FIMS (QCLot: 4941920)
EG035C: Mercury 7439-97-6 0.0001 mg/L <0.0001 0.01 mg/L 89.9 84.0 117
Matrix Spike (MS) Report
The quality control term Matrix Spike (MS) refers to an intralaboratory split sample spiked with a representative set of target analytes. The purpose of this QC parameter is to monitor potential matrix effects on
analyte recoveries. Static Recovery Limits as per laboratory Data Quality Objectives (DQOs). Ideal recovery ranges stated may be waived in the event of sample matrix interference.
Sub-Matrix: SOIL Matrix Spike (MS) Report
Spike SpikeRecovery(%) Acceptable Limits (%)
Laboratory sample ID Sample ID Method: Compound CAS Number Concentration MS Low High
EG005(ED093)T: Total Metals by ICP-AES (QCLot: 4934343)
EB2307649-002 Anonymous EG005T: Chromium 7440-47-3 100 mg/kg 89.9 70.0 130
EG048: Hexavalent Chromium (Alkaline Digest) (QCLot: 4934344)
EB2307718-001 Anonymous EG048G: Hexavalent Chromium 18540-29-9 200 mg/kg # 24.6 70.0 130
EB2307718-001 Anonymous EG048G: Hexavalent Chromium 18540-29-9 139.3 mg/kg # 2.9 70.0 130
Sub-Matrix: WATER Matrix Spike (MS) Report