Town Water Supply
64. The site shall be connected to Council’s existing town water supply and be constructed
in accordance with Council’s standards and requirements at no cost to Council. The
service shall be configured as a fire service (hydrants and sprinklers) and a single
domestic service (which includes the Fire Hose Reels).
65. Each individual water connection to the water reticulation system shall extend to the
property boundary and be metered. All fees for the supply of water meters shall be paid
to the Council.
66. All water meters must be located outside the property boundary and in an easily
assessable location to facilitate unhindered reading by Council and/or Council’s
contracted water meter readers, and not behind fences or locked gates. In this regard
approval of the water meter configuration and location must be obtained from Council’s
Water & Sewerage Capital Works Manager prior to lodgement and approval of hydraulic
drawings.
67. For Multiple Uses (including Building Format Plans, Group Title Plans, etc) the
development shall be served by:
67.1. A single Body Corporate water meter to measure the total water consumption
(including fire hose reels, but excluding fire hydrants and fire sprinkler systems),
and
67.2. Individual water meters to each tenement capable of being separately rated, and
67.3. A fire service (fully testable single detector check with metered bypass), where
applicable, for flows to fire hydrants and fire sprinkler systems (excluding fire
hose reels).
68. Fire hydrants are to be provided throughout the development in accordance with
Council Engineering Design Standards and in accordance with Queensland Fire Service
Standards.
Service Easements (Sewer / Stormwater)
69. A registered easement shall be created over the zone of influence of all sewers within
the subject site and over those parts of the subject site that are impacted upon by
sewers on any adjoining sites. The easements shall generally be parallel to and
centred over the sewer main and be equivalent in width to twice the depth to invert level
of the sewer at the deepest point within the allotment (measured from the finished
surface) and be no less than 3.0m wide overall. In this regard a licensed surveyor shall
accurately locate all sewer mains and determine the necessary width of the easement,
which shall be shown on any plans submitted for Operational Works / Building Works
approval. To this extent the surveyor shall certify that the sewer and the zone of
influence is wholly contained within the easement to be created.
In addition to this the Applicant’s Solicitor shall give Council’s Solicitor an appropriate
undertaking in writing that the Title Deed and the easement documents will be lodged at
the Land Titles Office and any additional Titles Office forms or requisitions requiring the
consent of Council will be attended to promptly.
A duly executed copy of the easement shall be submitted to Council for perusal prior to
the use commencing.
Any changes required by Council’s Solicitor must be corrected immediately.
Page 10 of 20
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
SUPERSEDED Decision Notice - 010.2007.00001841.001 [As Published]Related documentApplication case desk ↗
About this file
- File size
- 94 KB (small file)
- File type
No other editions are linked here.