Attachment 7. HTC Report flow and pressure test · OPW22/0319
w HTCGroup.com.au
e [email protected]
m 0423 383 329
abn 96 610 617 055
Test 1: H1 Performance and Street Supply Test
Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H1. The pressure
was recorded at the outlet of H1 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H2.
H1 Flow H1 Hydrant Pressure H2 Water Main
(L/s) (kPa) Residual Pressure
(kPa)
0 351 397
5 330 394
10 273 382
15 221 373
20 112 354
23.1 0 322
Test 2: H2 Performance and Street Supply Test
Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H2. The pressure
was recorded at the outlet of H2 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H1.
H2 Flow H2 Hydrant Pressure H1 Water Main
(L/s) (kPa) Residual Pressure
(kPa)
0 419 390
5 372 374
10 343 360
15 277 346
20 202 327
25 108 310
27.6 0 290
Water Mains Flow and Pressure Testing | Hydrant Commissioning | Fire System Maintenance
Page 2 of 5
[OCR of page images]
HTCGroup.com.au
w
[email protected]
0423 383 329
[ | | © croup "
abn 96610617 055
o
Test 1: H1 Performance and Street Supply Test
Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H1. The pressure
was recorded at the outlet of H1 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H2.
H1 Flow H1 Hydrant Pressure H2 Water Main
(L/s) (kPa) Residual Pressure
(kPa)
351 397
5 330 394
10 273 382
15 221 373
20 112 354
23.1 0 322
Test 2: H2 Performance and Street Supply Test
Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H2. The pressure
was recorded at the outlet of H2 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H1.
H2 Flow H2 Hydrant Pressure H1 Water Main
(L/s) (kPa) Residual Pressure
(kPa)
419 390
5 372 374
10 343 360
15 277 346
20 202 327
25 108 310
27.6 0 290
Water Mains Flow and Pressure Testing | Hydrant Commissioning | Fire System Maintenance
Page 2 of 5
See the original