Test 1: H1 Performance and Street Supply Test
Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H1. The pressure
was recorded at the outlet of H1 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H2.

              H1 Flow                  H1 Hydrant Pressure      H2 Water Main
              (L/s)                    (kPa)                    Residual Pressure
                                                                (kPa)
              0                        351                      397
              5                        330                      394
              10                       273                      382
              15                       221                      373
              20                       112                      354
              23.1                     0                        322

Test 2: H2 Performance and Street Supply Test
Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H2. The pressure
was recorded at the outlet of H2 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H1.

              H2 Flow                  H2 Hydrant Pressure      H1 Water Main
              (L/s)                    (kPa)                    Residual Pressure
                                                                (kPa)
              0                        419                      390
              5                        372                      374
              10                       343                      360
              15                       277                      346
              20                       202                      327
              25                       108                      310
              27.6                     0                        290




       Water Mains Flow and Pressure Testing | Hydrant Commissioning    | Fire System Maintenance

                                                                                            Page 2 of 5


[OCR of page images]
HTCGroup.com.au

w
[email protected]
0423 383 329
[ | | © croup "

abn 96610617 055

o

Test 1: H1 Performance and Street Supply Test

Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H1. The pressure
was recorded at the outlet of H1 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H2.

 

 

 

 

 

 

 

H1 Flow H1 Hydrant Pressure H2 Water Main
(L/s) (kPa) Residual Pressure
(kPa)
351 397
5 330 394
10 273 382
15 221 373
20 112 354
23.1 0 322

 

 

 

 

 

Test 2: H2 Performance and Street Supply Test

Water was drawn, at the flow rates below, from both outlets of street spring hydrant, H2. The pressure
was recorded at the outlet of H2 to determine the hydrant performance. This pressure used to
determine if the hydrant meets the pressure requirements of AS2419.1. The residual pressure was
recorded from the outlet of street spring hydrant H1.

 

 

 

 

 

 

 

 

 

 

 

 

 

H2 Flow H2 Hydrant Pressure H1 Water Main
(L/s) (kPa) Residual Pressure
(kPa)
419 390
5 372 374
10 343 360
15 277 346
20 202 327
25 108 310
27.6 0 290
Water Mains Flow and Pressure Testing | Hydrant Commissioning | Fire System Maintenance

Page 2 of 5

Used in these records

About this file

File size
386 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Attachment 7. HTC Report flow and pressure test.pdf · 386 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.