Test 3: H1 and H2 Combined Performance and Street Supply Test
Water was simultaneously drawn, at the flow rates below, from a single outlet of street spring
hydrants H1 and H2. The pressure was recorded at the outlet of H1 and H2 to determine the hydrant
performance. These pressures are used to determine if the hydrant meets the pressure requirements
of AS2419.1. The residual pressure was recorded from the outlet of street spring hydrant H3.

H1 Flow             H1 Hydrant            H2 Flow              H2 Hydrant           Total Flow            H3 Water Main
(L/s)               Pressure              (L/s)                Pressure             (L/s)                 Residual Pressure
                    (kPa)                                      (kPa)                                      (kPa)
0                   395                   0                    420                  0                     410
5                   354                   5                    384                  10                    410
10                  241                   10                   283                  20                    355
15.4                18                    18.1                 0                    33.5                  300

Test 3 Comments: This test was conducted in 10L/s increments due to H2 being in a driveway.

Hydrant Condition: H1, H2 and H3 were in good condition with a powder coat exterior.

General Notes:
• The test results are correct at the time of the tests
• Flow meters and pressure gauges are calibrated annually
• It is the responsibility of the recipient to determine the effect of changes in domestic/industrial usage, modifications to the
  main, differences in RL and extra hydraulic losses between the hydrant and tie in locations
• Flows are accurate to ±0.2L/s. Pressures are accurate to ±10kPa


 Approvals:
   Test Authority
                                         HTC Group Australia                             655 Waterworks Road, Ashgrove
                                         RPEQ 16239                                      0423 383 329
                                         QBCC 15018810                                   [email protected]
                                         ABN 96 610 617 055                              www.HTCGroup.com.au

       Test Leading Hand                                             Report Approval
        David Hopgood                                                 Daniel Barwick
        13:22hrs, 23rd of August, 2022                                24th of August, 2022




          Water Mains Flow and Pressure Testing | Hydrant Commissioning                     | Fire System Maintenance

                                                                                                                     Page 3 of 5


[OCR of page images]
HTCGroup.com.au

w
[email protected]
0423 383 329
[ | | © croup "

abn 96610617 055

o

Test 3: H1 and H2 Combined Performance and Street Supply Test

Water was simultaneously drawn, at the flow rates below, from a single outlet of street spring
hydrants H1 and H2. The pressure was recorded at the outlet of H1 and H2 to determine the hydrant
performance. These pressures are used to determine if the hydrant meets the pressure requirements
of AS2419.1. The residual pressure was recorded from the outlet of street spring hydrant H3.

 

 

 

 

 

H1 Flow H1 Hydrant H2 Flow H2 Hydrant Total Flow H3 Water Main
(L/s) Pressure (L/s) Pressure (L/s) Residual Pressure
(kPa) (kPa) (kPa)
395 0 420 0 410
5 354 5 384 10 410
10 241 10 283 20 355
15.4 18 18.1 0 33.5 300

 

 

 

 

 

 

 

 

Test 3 Comments: This test was conducted in 10L/s increments due to H2 being in a driveway.

Hydrant Condition: H1, H2 and H3 were in good condition with a powder coat exterior.

General Notes:

* The test results are correct at the time of the tests

© Flow meters and pressure gauges are calibrated annually

* It is the responsibility of the recipient to determine the effect of changes in domestic/industrial usage, modifications to the
main, differences in RL and extra hydraulic losses between the hydrant and tie in locations

¢ Flows are accurate to +0.2L/s. Pressures are accurate to +10kPa

Approvals:
Test Authority
HTC Group Australia 655 Waterworks Road, Ashgrove
CC) HTC RPEQ 16239 0423 383 329
Group QBCC 15018810 [email protected]
ABN 96 610 617 055 www.HTCGroup.com.au
Test Leading Hand Report Approval
David Hopgood Daniel Barwick
13:22hrs, 23rd of August, 2022 24th of August, 2022

Dittnegood. DP

Water Mains Flow and Pressure Testing | Hydrant Commissioning | Fire System Maintenance

Page 3 of 5

Used in these records

About this file

File size
386 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Attachment 7. HTC Report flow and pressure test.pdf · 386 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.