Attachment C - SCG Engineers Response
22 March 2021
SCG Ref: 31026(L1)
By email: nadinemartooconsulting.com
HRS Developments Pty Ltd
c/- Martoo Consulting Pty Ltd
Dear Sir/Madam
Re: MCU21/0027 & OPW21/0047 ~ Lot 4 RP72986, 30 & 32 James Street, Noosaville
We refer to Noosa Council’s Information Request dated 9 March 2021 and respond to the engineering matters as
follows:-
Issue 3-5 - Stormwater
SCG Consulting Engineers drawing No: 31026-C1.RevA ‘Stormwater Relocation Plan’, provides details of the
works for the proposed relocation of Council’s stormwater infrastructure. We have amended our plans to show a
pipe long-section and a new 4m wide easement (copy attached).
With the survey information provided by Max Watterson & Associates dated July 2016 we can confirm the
proposed stormwater management plan detailed in SCG Drawing No. 31026-SW1.RevA will not cause any
worsening of existing stormwater conditions to the neighbouring properties or increased runoff into the road
reserve.
SCG Consulting Engineers drawing No: 31026-SW1.1 ‘Stormwater Management Plan’ does not make reference
to PVC kerb adaptors. Galvanised (RHS) kerb adaptors have been proposed as per Council requirements.
Issue 6 - Earthworks
The proposed works include filling of the site to satisfy the minimum habitable floor level of RL 2.70 AHD. We
have provided a typical retaining wall/fence detail, please refer to architectural plans for proposed fencing and
heights.
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 1 page
Page 2
Issue 8 – Acid Sulphate Soils
As the Civil and Structural Engineers for the project we can confirm a Geotechnical Engineer has been engaged
to conduct acid sulphate soils (ASS) investigation and an ASS Management Plan in the case ASS are
encountered. The current turnaround timeframes are greater than 6 weeks. We kindly ask Noosa Council if this
can be conditioned prior to conducting a pre-start meeting.
Yours faithfully
Checked by
TOM HARRINGTON SEAN RICHARDSON– RPEQ 5835
For and on behalf of For and on behalf of
SCG CONSULTING ENGINEERS SCG CONSULTING ENGINEERS
Enc SCG Consulting Engineers Drawings – 31026-CS1.1, OW1.1 thru OW7.1, SW1.1 & C1.1A
SCG Consulting Engineers Page 2 of 2 SCG Ref: 31026(L1)