240608Opw-b
DESIGN NOTES:
BACKFILL AND DRAINAGE
1. RETAINING WALL FOUNDATIONS DESIGNED IN ACCORDANCE WITH 1. Backfill should not be placed behind the wall until at least
LINDSAY CONSULTING P/L SITE CLASSIFICATION REPORT 240608. seven days after grouting.
2. RETAINING WALL IS NOT DESIGNED TO SUPPORT LOAD FROM ANY 2. Backfill should be placed and compacted to 95% standard compaction
FUTURE FENCES. FENCE FOUNDATIONS TO BE CONSTRUCTED NOT in layers not more than 200mm deep. The degree and method of
IMPACT RETAINING WALL. OWNER TO CONFIRM WITH ENGINEER IF LINDSAY CONSULTING PTY
LINDSAY CONSULTING PTY LTD
REQUIRED.
compaction depends on the proposed use of the backfill area. LTD
3. BUILDER TO ENSURE THAT THE WALL WILL NOT BE SUBJECTED TO 3. The drainage system should be installed progressively as the
ADDITIONAL LOADS OUTSIDE OF THE WALL DESIGN PROVIDED. backfill rises. RPEQ 4928
4. ANY NEW FOUNDATIONS FOR ADJACENT STRUCTURES SHALL BE 4. The drainage system behind the wall should be connected to the
OFF. 2C/82 PARKER STREET, MAROOCHYDORE PH 54 792 118
300mm MIN BELOW THE BASE OF THE RETAINING WALL. THIS DRAWING REMAINS THE PROPERTY OF
5. PIERS MAY REQUIRE THE BUILDER TO ADOPT SUITABLE MEASURES
main drainage system.
LINDSAY CONSULTING PTY LTD AND IS FOR
AGAINST ANY POTENTIAL WATER SEEPAGE IN HOLES. THE SOLE USE OF THE CLIENT. NO PART
6. Fc = 25MPa MIN STRENGTH. Fsy = 500MPa. GROUT FILL = 20MPa MIN. MAY BE USED IN PART OR WHOLE WITHOUT
7. N12 TENSILE LAP LENGTH 600mm MIN. N16 TENSILE LAP LENGTH PRIOR EXPRESS WRITTEN CONSENT OF
800mm MIN. LINDSAY CONSULTING PTY LTD
8. LINDSAY CONSULTING WAS NOT ENGAGED TO PERFORM FLOOD
CHECKS OR PROVIDE A GEOTECHNICAL STABILITY REPORT FOR THE CLIENT AND PROJECT DESCRIPTION
SUBJECT SITE.
GJ GARDNER NOOSA
PROPOSED RESIDENTIAL
DEVELOPMENT
4-6 HAY STREET,
TEWANTIN
Spoon drain or similar to free draining
outlet by builder
DRAWING TITLE
Flat - 2.5kPa Live Surcharge RETAINING WALL
DETAILS
Line
190 Series Blockwork
H - 1400mm Max Retaining Height
N12 Vertical bars @ 400 crs
tion
Well Compacted
600mm
N12 Horizontal bars @ 400 crs
ava
Site Clay
SCALES
Exc
y
orar
p
N12 Starters / Footing Bars @
Tem
400 crs. 60mm min rear cover. Approved waterproofing
600mm min lap membrane
Cleanout block
200 Free draining granular backfill
PROVIDE WEEPHOLES
WHERE REQUIRED
SURVEY DATUM
110
.
240
200
Dia 100 Agg drain to free
N16 Key/Toe bars @ 400 crs draining outlet.
ASSOCIATED CONSULTANTS
H B Filter cloth to agg drain and
200
granular backfill
800 800 REPRODUCED AND
1000 800 UPDATED FROM
300
1200 1000 N12 Longitudinal bars
CONTOUR CONSULTING
1400 1200 B - 1200mm Max @ 300 crs
ENGINEERS APPROVED
N12 Key Longitudinal bars OPW DRAWINGS FOR
@ 300 crs
N12 bar through
top of screw pile
PROJECT 3045 FOR OPW
(600 mm long) 22/0218 APPROVED 31
Screw piles 100 kN SWL OCT 2022
at 2.0m MAX spacings
REVISION LIST
A ORIGINAL ISSUE 15/10/24
B OVERLAND FLOW PATHS ADDED 18/12/24
RETAINING WALL DETAIL - Up to 1.4m High
NOT TO SCALE
Computer File
240608OW.DWG
DRAWING NUMBER SHEET REV.
24-0608-C12 12 B
See the original