Compared to Location 1, less fuel has reaccumulated since the same fire passed through the area, and the
majority of available fuel is on the ground, with fuel arrangement diminishing likely fire behaviour.



3.5      Fuel Accumulation Assessment                        -
                                                                 Location 3




Figure 7. Fuel Accumulation Assessment             -
                                                       Location 3.


A significant proportion of the fuel adjacent to the eastern boundary is open patches of grasses (Panicum

sp, Paspalum sp, Cynodon sp, Chloris sp, Rhyncheletrum sp with patches of Singapore Daisy).


The effect of these areas on overall fire behaviour would depend on grass height and degree of curing, but
with the partial wind sheltering effect of the 3        -
                                                           4m vegetation, they would generally be expected to

moderate fire intensity close to the interface with the proposed development.


The grassy area, together with the 2m embankment (dropping down 2m to the east) can be seen as

assisting the exposure of the interface with the proposed development. The addition of a non          -
                                                                                                        combustible
barrier at the interface would prevent the passage of a fire front, leaving only radiant heat and embers

passing above the radiant heat barrier.


Averaging the effect of fuel accumulation in Locations 1, 2 and 3, it is considered reasonable to use a value
of 20t/ha total fuel availability for intact fuel areas shown in Figure 4 (15t/ha of which is surface/near
surface fuel) for the purposes of fire modelling in Section 6 of this assessment.



Report compiled by Bushfire Risk Reducers for Fulton Trotter Architects, April 2013               Page 11

Used in these records

About this file

File size
76.1 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Development Application Part 2 of 2 - Application Plans, Bushfire Management Plan and Fire and Evac Plan - OPW13_0463.pdf · 76.1 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.