Tod Consulting Stormwater Plans v2 · 132003.221172.A
Attached to the e-mail Change to DA - 132003.221172.A.msg.
Plans and drawings: the text below has words only, no drawings.
It can be seen from Table 3 that the Design Storm Method results in marginally larger trench sizes and thus
these sizes are recommended for use on this site. The hydraulic services design has nominated two location for
the infiltration systems with one being located near the northern and southern boundaries at the rear of the
house. A flow split has also been nominated with 60% of the flow going to the northern system and 40% going
to the southern system. The following is infiltration system is recommended for the southern and norther
system:
• Southern System – 10 x Atlantis Flo-Tanks (double) (w) x 0.90m (d) x 3.4m (l)
• Northern System – 15 x Atlantis Flo-Tanks (double) (0.82m (w) x 0.90m (d) x 5.5m (l)
It is noted that there is a 3m Unity Water sewer easement in the property. It is understood that Unity water
may in some circumstances allow the infiltration trench within the easement however Unity Water would need
to be consulted.
CONCLUSION
Based on the methodology contained within the “The WSUD Technical Design Guidelines for South East
Queensland” and the geotechnical information available for the site it is recommended that a minimum
infiltration area and volume as provided in Tables 3 be installed within the development to prevent water
leaving the site. This volume and area could be accommodated by a total of 25 x Atlantis Flo-Tank (Double).
I trust this assessment of stormwater management requirements for your development meets your needs. Feel
free to contact me should you wish to discuss any of the content in this letter.
Yours faithfully,
Kelly McKendry
Water Resources Engineer / Director (RPEQ 09298)
AquaIntel Pty Ltd
Attachments
1. Hydrologic Calculations
2. Geotechnical Information
3. Trench sizing calculations
m: 0439 119 890 t: +7 5414 7185
e: [email protected]
w: www.aquaintel.com.au
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Tod Consulting Stormwater Plans v2.pdfRelated documentApplication case desk ↗
About this file
- File size
- 6.7 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.