12. Code Assessment
Performance outcomes Acceptable outcomes Comment
waterways, wetland and
areas of native vegetation.
Water Supply for Fire Fighting Purposes
PO3 AO3.1 AO3.2 Complies
Development provides an adequate Premises are connected to the reticulated water supply.
water supply for fire fighting purpose The hospice is not connected to urban services but
which is reliable, safely located and Editor's note—For reconfiguring a lot, water supply needs does have an existing water supply of 50,000L and
freely accessible. to provide for a minimum flow and pressure of 10 litres a this is proposed to be doubled to 100,000l as part of
second at 200kPa at all times for fire fighting purposes. the proposed additions.
OR The premises also includes a swimming pool which
could be used for firefighting purposes.
AO3.2
A 50mm fire brigade fitting is available to access the
Where there is no available reticulated water supply, the
site’s bushfire water supply reserve.
premises has:
The bushfire water supply is in addition to the
development drinking water supply.
1. an accessible dam, swimming pool or water
tank available for fire fighting purposes with
an onsite water volume of not less than
5,000 litres; and
2. a water supply outlet pipe 50 millimetres in
diameter fitted with a standard fire brigade
fitting connected to the water supply (other
than where the water supply is in a
swimming pool or dam).
Editor’s Note—Water supply capacity for fire fighting