08/0197 - MCU - Detached House DJ Leach Pty Ltd [As Published] · 132008.197
DRAWING INDEX
PROPOSED RESIDENCE
LOT 40 ASPERA PLACE, NOOSA RETREAT
NERAL
Gi. READ THESE DRAWINGS IN CONJUNCTION WITH
ARCHITECTURAL AND OTHER ENGINEERING
LIVE LOADS:
e BALCONIES: 2.0kPa
SITE DRAINAGE
SD1FINISHED SLAB LEVELS TO BE 250mm (MIN.) ABOVE
GROUND, GR AS REQUIRED BY THE LOCAL
OOTING & FOUNDATION PREPARATION
Fi. PREPARE EXISTING FOUNDATION BELOW THE
BUILDING BY REMOVAL OF ANY TOPSOIL
Fad. ALL TREES, PROPOSED OR EXISTING, SHALL NOT
BE CLOSER TO THE FOOTING THAN 0.8 TIMES THEIR
C1.
RETE
ALL CONCRETE WORK AND REINFORCEMENT TO BE
EXECUTED IN ACCORDANCE WITH THE RELEVANT
SATISFACTION OF THE ENGINEER.
STRUCTURAL
Si, ALL WORKMANSHIP & MATERIALS SHALL BE IN
ACCORDANCE WITH AS 4100 & AS 1554 EXCEPT
$12.DAMAGED PAINT WORK & ALL NUTS, BOLTS AND
CONCRETE K_MASONRY
M1, ALL CONCRETE BLOCK MASONRY WORK IS TO BE
EXECUTED IN ACCORDANCE WITH THE CURRENT
STRUCTURAL TIMBER
Ti. ALL TIMBER-FRAMED CONSTRUCTION IS TO BE
CONSTRUCTED, SIZED & FIXED IN ACCORDANCE WITH
DRAWINGS AND SPECIFICATIONS AND WITH SUCH AUTHORITY. CONTAINING ORGANIC AND/OR INORGANIC MATTER S.A.A CODES AND SPECIFICATIONS: IN PARTICULAR WHERE VARIED BY THE SPECIFICATION. EDITION OF:- THE CURRENT BUILDING CODE OF AUSTRALIA & AS
OTHER WRITTEN INSTRUCTIONS AS MAY BE ISSUED. WHICH MAY INHIBIT COMPACTION. THE CURRENT EDITION OF AS 3600. 1684.2.
$D2. PONDING OF WATER ADJACENT TO FOOTINGS TO S2. ALL STEEL SHALL BE IN ACCORDANCE WITH AS AS 3700 - —S.A.A MASONRY CODE
1. DRAWING INDEX & STANDARD NOTES G2. VERIFY SET OUT DIMENSIONS SHOWN ON THE BE PREVENTED AT ALL TIMES. F2. DEEPEN FOOTINGS AND SLAB STIFFENING BEAMS (2. CONCRETE COMPONENTS AND QUALITY TO BE N25 3679 GRADE 250 OR 300 U.N.O. (AS 1163 GRADE AS 4455 - CONCRETE MASONRY UNITS T2. ALTERNATIVE MEMBER SIZES & STRESS GRADES MAY
DRAWINGS BEFORE SITE WORKS, CONSTRUCTION TO BEAR ON FOUNDATION MATERIAL WITH MINIMUM (EXPOSURE CLASSIFICATION At) U.N.O. MAXIMUM (350 FOR RECTANGULAR & SQUARE HOLLOW AS 3600 - —S.A.A CONCRETE STRUCTURES CODE BE USED IN ACCORDANCE WITH AS 1684.2 - MEMBER
AND FABRICATION COMMENCES. REFER ANY SD3. ALL SURFACE RUN-OFF TO BE DIRECTED AWAY SAFE BEARING PRESSURE AS NOTED IN THE TABLE AGGREGATE SIZE TO BE 20mm U.N.O. SECTIONS OR GRADE 200 FOR CIRCULAR HOLLOW AS 2699 - MASONRY WALL TIES SPAN TABLES.
DISCREPANCY, TO THE ENGINEER BEFORE FROM THE FOUNDATION BY A MINIMUM GROUND BELOW LEFT. SECTIONS TO 165.tmm 0.0. & GRADE C350 ABOVE AS 2699.2- MASONRY CONSTRUCTION,
2. FOOTING & SLAB ON GROUND LAYOUT & PROCEEDING WITH THE WORK. SLOPE OF 1 IN 30. G. CONCRETE TESTING TO CONFORM WITH THE 165.1mm 0.0} ACCESSORIES T3. MEMBER SIZES ARE MINIMUM ONLY & MAY BE
F3. COMPACT FOUNDATION BELOW THE CONCRETE ACCEPTABILITY REQUIREMENTS OF THE CURRENT INCREASED FOR AESTHETIC REASONS OR EASE OF
DETAILS G3. DO NOT OBTAIN DIMENSIONS BY SCALING FROM SD4. ALL ROOF DRAINAGE TO BE PIPED AND SLABS TO THE STANDARD OF COMPACTION FOR EDITION GF AS 3600. $3. WELDS SHALL BE TO THE REQUIREMENTS OF AS M2. ‘CLEAN OUT’ BLOCKS TO BE USED AT FIRST COURSE CONTRUCTION.
THE DRAWINGS. DISCHARGED AT LEAST 6.0m AWAY FROM THE FILL UNDER SLABS OR FOOTINGS HEREUNDER 1554 & SHALL BE 6mm CONTINUOUS FILLET WELDS ABOVE EACH FLOOR AND ALL MORTAR TO BE
FOUNDATIONS. UNLESS NOTED OTHERWISE. (4. THE CONCRETE SLUMP SHALL NOT BE LESS THAN UNLESS SHOWN OTHERWISE. REMOVED FROM CORES PRIOR TO CONCRETE FILLING. T&. THE ROOF/TRUSS LAYOUT DETAILS/DESIGNED BY
G&. ALL WORKMANSHIP ANO MATERIALS SHALL BE IN 75mm AND NOT MORE THAN 100mm. THE TRUSS MANUFACTURER SHOULD BE REFERRED TO
3. BRACING & ROOF FRAMING LAYOUT ACCORDANCE WITH THE CURRENT $.A.A CODES SDS. SITE DRAINAGE TO BE MAINTAINED AT ALL F4. SAND FILLING UNDER SLABS OR FOOTINGS SHALL Sk. BUTT WELDS SHALL BE PRE-QUALIFIED COMPLETE M3. CONCRETE MIX USED TO FILL CAVITY TO HAVE THE ENGINEER PRIOR TO FABRICATION/ERECTION FOR
AND THE BY-LAWS AND ORDINANCES OF THE TIMES BOTH DURING AND AFTER CONSTRUCTION. BE PLACED iN MAX. 200mm LAYERS, G. ALL CONCRETE SHALL BE ADEQUATELY VIBRATED PENETRATION BUTT WELDS. ALL WELDS SHALL BE CHARACTERISTIC COMPRESSIVE STRENGTH OF Z0MPa CONFIRMATION OF BEAM/LINTEL SIZES & TIEDOWN
RELEVANT BUILOING AUTHORITY. (UNCOMPACTED DEPTH) COMPACTED: IN . INTO PLACE, NO WATER TO BE ADDED ON SITE., CATEGORY SP IN ACCORDANCE WITH AS 1554 {F'c), MAXIMUM SLUMP 230mm, MAXIMUM AGGREGATE REQUIREMENTS.
ACCORDACNCE WITH AS 1289 (DENSITY INDEX TO CURE CONTINUOUSLY FOR NOT LESS THAN SEVEN UNLESS NOTED OTHERWISE. SIZE 6mm (MAXIMUM 6 COURSE HEIGHT PLACED AT
4. POOL LAYOUT, DETAILS & NOTES G5. THE STRUCTURAL WORK SHOWN ON THE BE GREATER THAN 70% IN ACCORDANCE WITH AS (7) DAYS IN AN APPROVED MANNER. ONE TIME}. TS, ALL BRACING WALLS ARE TO BE CONSTRUCTED IN
DRAWINGS HAS BEEN DESIGNED FOR THE LOADS 1289). . SS. ALL GUSSET AND CONNECTION PLATES SHALL BE ACCORDANCE WITH AS 1684.2 OR THE RELEVANT
SET OUT iN THE TABLE BELOW IN ACCORDANCE : (6. NO HOLES, CHASES OR VOIDS, OTHER THAN THOSE mm UNLESS SHOWN OTHERWISE. M4. MORTAR TO BE MIXED IN PROPORTION OF 1.0:1.0:6.0 MANUFACTURERS SPECIFICATIONS. ALL INTERNAL
WITH AS 1170 PARTS 1% 2. F5. FILL MATERIAL OTHER THAN SAND fie. GRAVEL, SHOWN ON THE STRUCTURAL DRAWINGS ARE TO CEMENT:HYDRATED LIME:SAND (OR EQUIVALENT WALLS ARE TO BE ADEQUATELY FIXED TO THE
DECOMPOSED ROCK OR BROKEN ROCK, FREE FROM BE MADE WITHOUT PRIOR APPROVAL OF THE - $6. BASE PLATES SHALL BE témm UNLESS SHOWN CEMENT - SAND MORTAR WITH PLASTICISER) AND CEILING/ROOF FRAME AS PER AS 1684.2.
G6. ALL STRUCTURAL WORK MUST BE INSPECTED AND ORGANIC MATERIAL AND LUMPS OF CLAY) UNDER ENGINEER. OTHERWISE. MORTAR COMPRESSIVE STRENGTH AT 28 DAYS TO BE
APPROVED BY THE ENGINEER. SLABS OR FOOTINGS TO BE COMPACTED TO 20MPa MINIMUM. Té. IN ALL BOLTED TIMBER STRUCTURAL JOINTS, ALL
ACHIEVE A DENSITY RATIO [CALCULATED BY AS G. SYMBOLS ON DRAWINGS FOR GRADE & TYPE OF $7. MINIMUM 5mm RADIUS CUT SHALL BE MADE TO ALL STEEL BOLTS AS SPECIFIED IN AS 1111 SHALL BE
G7. FORTY-EIGHT {48} HOURS NOTICE MUST BE GIVEN 1289) OF NOT LESS THAN 98% AT MAXIMUM DRY REINFORCEMENT ARE AS FOLLOWS:- RE-ENTRANT CORNERS. MS. CHARACTERISTIC COMPRESSIVE STRENGTH OF BLOCK FITTED INTO PREBORED TIMBER WITH BOLT HOLE
TO THE ENGINEER PRIOR TO ANY CONCRETE DRAINAGE LAYOUT FOR CUT & FILL SITES DENSITY AS DETERMINED BY AS 1289. R DENOTES STRUCTURAL GRADE 230 PLAIN fluc = 15 MPa U.N.O. DIAMETERS 10% GREATER THAN BOLT DIAMETERS
POURS OR OTHER SIMILARLY CRUCIAL PHASES OF ROUND BAR TO AS 4671. $8. ALL INTERNAL STEELWORK IS TO BE AND FITTED WITH WASHERS AS GIVEN BELOW.
/ CONSTRUCTION. F6. PROOF ROLL THE FOUNDATION AND REMOVE AND N DENOTES HOT ROLLED GRADE 500 DEFORMED MECHANICALLY WIRE BRUSHED TO REQUIREMENTS
i RECONSTRUCT AREAS THAT BREAK UP OR SHOW BAR TO AS 4671. OF AS 1627.2 AND HAVE 2 COATS OF A ZINC RICH SPA TICULATION JOWTS FOR T7. IN ALL BOLTED TIMBER STRUCTURAL JOINTS WHERE
. EVIDENCE OF MOVEMENT UNDER THE PROOF SL DENOTES HARD DRAWN WIRE REINFORCEING PRIMER PAINT COMPLYING WITH AS 3750. UNREIMFORCED MASONRY WALLS STEEL PLATE DOES NOT PROTECT TIMBER, WASHERS
LOADING. FABRIC TO AS 1304. (TTC acoby wal] AS SPECIFIED BELOW SHALL BE PRoVINFD
GROUND RUECTUR GRABE-BEFORMEB-BAR Qh A RNA WOR 0 BE AUT DIPPED CONSTRUCTION AND JOINT
F7, CONSTRUCT FOOTINGS UNDER ALL:LOAD BEARING 1302. GALVANISED, STEELWORK TO BE GALVANISED CLASS SPACING (m)
Y NY WALLS (TYPICAL). SHALL BE CLEANED TO REQUIREMENTS OF AS 4680 MINIMUM REQUIRED SIZE OF WASHERS FOR
: <| C& MINIMUM LAPS OF REINFORCEMENT (U.N.O}: CLASS 2 1/2 OR BETTER & HOT DIP GALVANISED fags | ARTICULATION NOT | - | STRUCTURE BOLTED JOINTS (mm)
WIND LOADS. AS FB. LAP AND CORNER BARS EQUIVALENT TO THE MESH 250mm TG REQUIREMENTS OF AS 4680 REQUIRED ROUND SQUARE
‘e REGION: B REINFORCEMENT IN THE FOOTING TO BE PROVIDED i 12mm @ BAR 300mm EXTERNAL MASONRY BOLT | THICKNESS | WASHER MIN.| WASHER MIN.
: AT CHANGES IN DIRECTION AND JUNCTION OF : 16mm @ BAR 400mm 59. BOLTS TO BE HIGH STRENGTH, SNUG TIGHT TO AS FACE FINISH, RENDERED 70 g SIDE LENGTH
@ TERRAIN CATEGORY: 2.5 TO OUTFALL FOOTINGS. 4100, (LE. 8.8/5) ULN.O. MEH OR PAINTED
e@ DESIGN GUST WIND SPEED: DRAINAGE LAYOUT FOR WET SITES C9, ALL REINFORCEMENT SHALL BE CONTINUOUS WITH INCLUDING [uf ot [| a |
(Vz-P); &4m/ F9. LARGE TREES ADJACENT TO THE BUILDING ARE TO «THE FOLLOING LAPS AT SPLICE: S10.ALL NUTS, BOLTS & WASHERS TO BE HD & INTERNAL MASONRY [Me foo20 { 3% | 32 |
Tk Sous BE REMOVED. THE VOIDS SHALL BE EXCAVATED, TRENCH MESH 300mm GALVANISED. - HD SHEETED OR FACE co
{Vz-U); 50m/s BACKFILLED & COMPACTED WITH SUITABLE FABRIC 250mm . FINISHED
ee ANF REQUIRED MATERIAL SIMILAR TO THE EXCAVATED MATERIAL. S11. HOLDING DOWN BOLTS TO BE SUPPLIED COMPLETE INTERNAL MASONRY | so | [ w12 | | ss |
. C10, ALL REINFORCEMENT SHALL BE CHAIRED TO THE WITH LEVELLING NUTS, NUTS AND WASHERS. RENDERED OR PAINTED Pe
| 5
@ STAIRS:
@ FLOORS:
2.0kPa
1.5kPa
MINIMUM SAFE BEARING PRESSURE:
@ PRESSURE: 100kPa
1. This is the property of the engineer, and may not be used, copied,
“~~ SPOON DRAIN
SLAB CAST ABOVE GROUND
LEVEL TO SOIL DRAINAGE CONDITIONS.
SURFACE DRAINS ALONG LINE OF SLOPES
GROUND
“ / D>]
TO OUTFALL
cS
TO OUTFALL TO OUTFALL
GROUND
FALL /
TYPICAL DRAINAGE LAYOUT
PROPOSED
RESIDENCE
RETAINING WALL FOR
NEIGHBOURS BLOCK.
CONCRETE PATHWAY REQUIRED
FOR FREE DRAINAGE.
DRAINAGE LAYOUT FOR ADJACENT RETAINING WALLS
MATURE HEIGHT. WHERE THIS CAN NOT BE
ACHIEVED, BUILDER IS TO SEEK ADVICE FROM
ENGINEER.
FAL.TRENCHES FOR SERVICES SHALL BE LOCATED AT A
MINIMUM OF 1.0m CLEAR OF FOOTINGS.
FI2.PROPER SITE DRAINAGE & FOUNDATION
MAINTENANCE MUST BE STRICTLY OBSERVED TO
MINIMISE MOISTURE VARIATIONS IN REACTIVE CLAY
SOILS. IT IS THE HOUSE OWNERS RESPONSIBILITY
TO BE FAMILIAR WITH & COMPLY WITH THE
REQUIREMENTS OF "GUIDE TO HOME OWNERS ON
FOUNDATION MAINTENANCE & FOOTING
PERFORMANCE.” PUBLISHED BY CSIRO.
F13.REFER TO THE GEOTECHINICAL REPORT AS NOTED
CONSULTING ENGINEERS
IN THE TABLE TO LEFT.
C®. WHERE BRITTLE FLOOR COVERINGS ARE USED
Client: LEACH DEVELOPMENT GROUP
OVER AN AREA GREATER THAN t6m?, EXTRA
MEASURES SHALL BE TAKEN TO CONTROL THE
EFFECT OF SHRINKAGE CRACKING. SUCH MEASURES
SHALL INCLUDE ONE OF THE FOLLOWING:
A THE AMOUNT OF SHIRNKAGE REINFORCEMENT
SHALL BE INCREASED TO SL92 OR EQUIVALENT
THROUGHOUT THE AFFECTED SLAB PANELS.
ALTERNATIVELY, AN ADDITIONAL SHEET OF
SLAB MESH SHALL BE PLACED OVER AFFECTED
AREAS.
B THE BEDDING SYSTEM FOR BRITTLE COVERINGS
SHALL BE SELECTED ON THE BASIS OF THE
EXPECTED SLAB MOVEMENT AND THE
CHARACTERISTICS OF THE FLOOR COVERINGS.
C THE PLACEMENT OF FLOOR COVERINGS SHALL
BE DELAYED {THREE MONTHS).
WASHERS SHALL BE CLEANED AND RETOUCHED
AFTER ERECTION.
S13.CONCRETE ENCASED STEELWORK TO BE LEFT
UNPAINTED AND BE WRAPPED iN FGW 41 FABRIC
UNLESS OTHERWISE SHOWN.
S14.TWO (21 COPIES OF ALL WORKSHOP DRAWINGS TO
BE SUBMITTED TO THE ENGINEER AND APPROVAL
OBTAINED IN WRITING BEFORE FABRICATION 1S
COMMENCED. APPROVAL DOES NOT INCLUDE
CHECKING DIMENSIONS.
PLUMBING
PL1.ALLOTMENTS CONTAINING REACTIVE SITES
CLASSIFIED AS H OR E SHALL BE PROVIDED WITH
AN ADEQUATE SYSTEM OF PLUMBING DETAILED iN
ACCORDANCE WITH THE FOLLOWING.
(NOTE- METHODS USED SHOULD COMPLY WITH
LOCAL PLUMBING AND ORAINAGE REGULATIONS).
APENETRATIONS OF THE EDGE BEAMS OF A RAFT
AND PERIMETER STRIP FOOTINGS SHALL BE
AVOIDED, BUT WHERE NECESSARY SHALL BE
SLEEVED TO ALLOW FOR MOVEMENT.
CLOSED-CELL POLYETHYLENE LAGGING SHALL BE
USED AROUND ALL STORMWATER AND SEWER
PIPE PENETRATIONS THROUGH EXTERNAL
FOOTINGS. THE LAGGING SHALL BE A MINIMUM OF
20mm THICK ON CLASS H SITES AND 40mm THICK
ON CLASS E SITES. SLEEVES ALLOWING
EQUIVALENT MOVEMENTS MAY BE USED AS AN
ALTERNATIVE. LAGGING IS NOT REQUIRED
AROUND VERTICAL PENETRATIONS THROUGH
SLAB PANELS.
B CONNECTION OF STORMWATER DRAINS AND
WASTE DRAINS SHALL INCLUDE FLEXIBLE
CONNECTIONS.
C SEPTIC TANKS AND ASSOCIATED SOAKAGE
AREAS SHALL BE LOCATED TO MINIMIZE SOIL
MOISTURE INCREASE WITHIN THE FOUNDATION.
O PLUMBING AND DRAINAGE UNDER A SLAB SHALL
BE AVOIDED WHERE PRACTICABLE. PIPES MAY BE
ENCASED IN CONCRETE OR IN RECESSES IN THE
SLAB WHEN PROVIDED WITH FLEXIBLE JOINTS AT
THE EXTERIOR OF THE SLAB.
Tite DRAWING INDEX & STANDARD NOTES
| 25 |
po
4.0
| sa |
| 6.0 |
T8. ALL WASHERS TO BE GALVANISED U.N.O
MAINTENANCE
MA. THE OWNERS ATTENTION IS DRAWN TO
APPENDIX A OF AS 2870 ‘PERFORMANCE
REQUIREMENTS AND FOUNDATION MAINTENANCE.’
MA2. LARGE, MOISTURE-ABSORBING TREES ARE NOT
TO BE PLANTED IN CLOSE PROXIMITY TO THE
FOOTINGS.
MA3. NATURAL WATER RUN-OFF IS TO BE DIRECTED
AWAY FROM SLAB AND PLATFORM GENERALLY.
MA4. EXCESSIVE WATERING OF GARDENS ADJACENT
TO THE HOUSE SLAB iS TO BE AVOIDED, TO
MINIMISE ANY GROUND HEAVING.
Date: JANUARY 2008} Scate:
AS SHOWN
Job Ref No:
[sense [ot
or reproduced wholly, or in part without the express permission of Project: PROPOSED RESIDENCE
LOT 40 ASPERA PLACE,
NOOSA RETREAT
Approved: aw)
TROY PAULSEN / RPEQ: 6990
the engineer. Infringement in any way may result in legat action.
2. Figured dimensions take precedence over scaled.
3. Verify alt dimensions on site.
CORAL
FOBOX 685 FOBOX 2052
‘MARDOCHYDORE QLD 455 BUNDAGARG GUD 4670
i G7 S477 6437 PH 07 41547451
FAX: 07 5444 Q16 FAX. 07 4129 260g
‘TROY 0413 106 149 ROSS MOBILE: 0817 025 652
ENGINEERING Py.ua ABN 721112761510 ACN 112761510
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
08/0197 - MCU - Detached House DJ Leach Pty Ltd [As Published]Related documentApplication case desk ↗
About this file
- File size
- 5.7 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.