20210216 RECOR Further Advice Response

of 3

Page text shows just the words. Original shows the document exactly as it was published.

            30 November 2022

            Ref: MCU22/0084

            Ms J Lyons
            PO Box 141
            Tewantin, QLD 4565


            Attention:      Jayda Lyons

            Dear Ms Schramm,

                    Re:     Further Advice
                    At:     62 Gateway Drive Noosaville Qld 4566

            With reference to the abovementioned development application and the subsequent
            further advice from Council, we have prepared a response to the engineering matters
            raised as follows:

            Location of Driveway Taper to Lintel
               1. Provide additional detail demonstrating that the proposed driveway
                   crossover is located generally in accordance with Noosa Council’s
                   Standard Drawing RS-049. The additional detail must be prepared by a
                   suitably qualified person (RPEQ – Registered Professional Engineer of
                   Queensland).

            The proposed location of the heavy-duty crossover generally complies with Standard
            Drawings RS-051 and 63, except for the Type A wing width of 1m instead of 1.5m.
            Standard Drawing RS-049 details an exclusion zone of 1m from the lintel to the
            driveway’s wing.




            Figure 1 Extract from Standard Drawing DS-063




P +61 7 5211 1003         A 75 Noosa Dr, Noosa Heads Qld 4567   E [email protected]   recorconsulting.com
Log in to download the original file

20210216 RECOR Further Advice Response.pdf · 139 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 2 pages

Page 2

            Figure 2 Extract from RS-049


            This is generally in accordance with the relevant Standard Drawings. We recommend
            that this be conditioned in the Operational Works permit to detail the modified Type
            A wing for the heavy-duty crossover.


            Existing Stormwater Chamber
               2. Provide additional detail demonstrating how the proposed development
                   will ensure the existing stormwater chamber will not be traversed, unless
                   reconstructed with a Class D manhole lid. The detail must be prepared by a
                   suitably qualified person (RPEQ – Registered Professional Engineer of
                   Queensland) and include, but not be limited to:


                      a. If proceeding with the reconstruction of the chamber:
                              i. reconstruct the existing gully chamber as a manhole with a
                                 Class D lid;
                             ii. construct a branch line connection to the newly constructed
                                 gully pit sufficiently clear from the driveway entrance; and




P +61 7 5211 1003       A 75 Noosa Dr, Noosa Heads Qld 4567   E [email protected]    recorconsulting.com

Page 3

                                 iii. demonstrate the existing branch connections across the
                                      existing stormwater line have sufficient depth to maintain
                                      existing freeboard in the system.

                          b. If forgoing the reconstruction of the chamber:
                                  i. Demonstrate a suitable driveway crossover location that
                                     complies with relevant standards and will not adversely
                                     affect Council’s existing stormwater infrastructure.

            We recommend that these be conditioned in the Operational Works permit to detail
            the reconstruction of the chamber using a Class D manhole.

            We believe that the above satisfactorily addresses the engineering matters raised
            however, should additional information be required, please contact our office directly.

            Yours faithfully,
            RECOR Pty Ltd

            Prepared by



            Jaro Bauleka
            Civil Engineer
            RPEQ: 20693




P +61 7 5211 1003          A 75 Noosa Dr, Noosa Heads Qld 4567   E [email protected]    recorconsulting.com