Attachment 1 - Amended advice form Rob Friend and Associates

Attached to the e-mail Applicant Response to SARA Advice Notice - 132005.638.04.

of 20

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

                                                 5


              Inputs                                           Outputs
Flame width            100 m      Minimum distance to < 40      9.1 m
                                  kW/m²
Windspeed              n/a        Minimum distance to < 29                       12.4 m
                                  kW/m²
Heat of combustion     18,600     Minimum distance to < 19                       18.2 m
                       kJ/kg      kW/m²
Flame temperature      1,090 K    Minimum distance to < 12.5                     26.3 m
                                  kW/m²
                                  Minimum distance to < 10                       31.5 m
                                  kW/m²
Rate of Spread - Mcarthur, 1973 & Noble et al., 1980
Flame length - NSW Rural Fire Service, 2001 & Noble et al., 1980
Elevation of receiver - Douglas & Tan, 2005
Flame angle - Douglas & Tan, 2005
Radiant heat flux - Drysdale, 1999, Sullivan et al., 2003, Douglas & Tan, 2005


   14. Therefore, the minimal distance that achieves a Radiant heat flux of 29kW/m2 is 12.4
       metres and this spatially located on Figure 1 and the light blue line.
Conclusion
Based on the above analysis we can conclude that;
   1. The clearing of Category X regulated vegetation that is not mapped under any other level
      of vegetation or habitat protection by the State i.e. Koala Habitat Area, or protected
      vegetation in a Planning instrument, does not require any approvals from the State or a
      Local Government for its removal.
   2. The exempted clearing distance for the existing development and the proposed
      development is a clearing with of 24.0 metres.
   3. However, the only clearing that is necessary is that which achieves a radiant heat flux of
      29kW/m2 is 12.4 metres, the only clearing that is necessary of any area of category B
      regulated vegetation is that which is within 12.4 metres of the closest edge of the existing
      and proposed infrastructure.
   4. As the 12.4 metres necessary clearing distance for a necessary firebreak is less than the
      1.5 time the height of the tallest adjacent trees, this clearing is considered to be exempted
      clearing.
Log in to download the original file

Attachment 1 - Amended advice form Rob Friend and Associates.pdf · 3.7 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.