Table Error! No text of specified style in document.-24 — For All Residential Uses
Including amendments to 3 July 2017
column 1 column 2
The Noosa Plan
Specific Outcomes Probable solutions (if code assessablecode
assessment)
14.46 Effects of use
Electricity supply infrastructure
O1 The development does not adversely S1.1 No solution provided
impact on existing or future electricity supply
infrastructure;
AND
O2 All uses and works maintain an adequate S2.1 Development for uses adjacent to or
safe distance from electrical infrastructure within 50m of an existing electricity substation
including substations, overhead powerlines, incorporates noise attenuation measures to
power poles and transformers. mitigate noise impacts;
AND
S2.2 Buildings and structures (including
swimming pools, sheds, tennis courts or
outbuildings) are not constructed under
overhead electricity transmission lines, or
within electricity easements;
AND
S2.3 A minimum separation distance is
maintained from the electricity transmission
line to the closest boundary of habitable
buildings and child activity areas, as follows—
a) 20m for transmission lines up to 132kV;
b) 30m for transmission lines between
133kV and 275kV; and
c) 40m for transmission lines greater than
275kV.
Water supply and conservation 18
S3.1 & S4.1 For a Class 1 building other than
O3 On-site water storage is designed and
a Detached house , outside a reticulated
operated to support the efficient use of water;
water service area, a rainwater tank is to be
installed with the following minimum storage
AND
capacities—
O4 On-site water storage is adequate for a) Where no more than 3 bedrooms –
occupants every day use and fire fighting 45,000 litres; or
purposes. b) Where more than 3 bedrooms –
60,000 litres;
AND
c) There is to be on the lot a dam,
swimming pool or water tank
accessible for use by the fire brigade
that contains at least 5,000 litres of
water.
Editor’s note:
The 5,000 litres required can be included
within the water required in S3.1 or S4.1
providing it is accessible for the purpose of fire
fighting at all times and not used for other
domestic purposes.
Advisory note
18
Class 1 Buildings are defined under the Building Code of Australia
47
Residential Uses Code
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
2017-06-06 - P&E Agenda Attachment 1 to Item 6 Draft Alignment Amendments Part 1 (Pages 1-907)(PDF, 18MB)Related documentPublic source context ↗Public source context ↗Public source context ↗
2017-06-06-p-e-agenda-attachment-1-to-item-6-draft-alignment-amendments-part-1-pages-1-907-pdfRelated documentPublic source context ↗
About this file
- File size
- 18.9 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.