Attachment 4 - Response to Further Advice Rob Friend and Associates
[22]
Performance outcomes Acceptable outcomes Response
2. the long term physical integrity of
waterways, wetland and areas of native
vegetation.
Water Supply for Fire Fighting Purposes
PO3 AO3.1 R3.1
Development provides an adequate water Premises are connected to the reticulated
supply for fire fighting purpose which is water supply. The subject site has access to a reticulated
reliable, safely located and freely accessible. water supply/is in a water service area.
Editor's note—For reconfiguring a lot, water
supply needs to provide for a minimum flow and
pressure of 10 litres a second at 200kPa at all
times for fire fighting purposes.
OR
AO3.2
Where there is no available reticulated water
supply, the premises has:
1. an accessible dam, swimming pool or
water tank available for fire fighting
purposes with an onsite water volume of
not less than 5,000 litres; and
2. a water supply outlet pipe 50 millimetres in
diameter fitted with a standard fire brigade
fitting connected to the water supply (other
than where the water supply is in a
swimming pool or dam).
RFA17-040Bushfire Hazard Assessment & Mitigation Plan | 61 Noosa Springs Dr. Noosa Heads 30 April 2022