Original source · versioned page text
Request for Amended Advice Agency Response_Energex_Council CDA_01-04-2020
Attached to the e-mail Request for Energex to provide an Amended Advice Agency Response - 152006.1999.4.
The original of this document is very large (12.4 MB). Opening the original or downloading it may take a few minutes. Please be patient and don't click again. The page text is quick to read. If you are on mobile data, it is best to wait until you are on Wi-Fi.
J&P Richardson Industries Pty Ltd -6-
3.0 BACKGROUND ON MAGNETIC FIELDS
3.1 ARPANSA and ENA
ARPANSA stands for the Australian Radiation Protection and Safety Agency. ARPANSA is
a federal body that monitors and identifies solar radiation and nuclear radiation risks across
a wide frequency spectrum to the population of Australia.
The Energy Networks Association (ENA) is the peak national body representing gas and
electricity distribution businesses throughout Australia. ENA has specific interest in electric
and magnetic fields at power frequency (50Hz).
In January, 2016 the ENA published the “EMF Management Handbook” which is
considered to be the most up to date reference on the topic for Australian power networks.
3.2 Australian Guidelines
The ENA handbook lists two sets of internationally recognised guidelines on EMF :
a) International Commission on non-ionising radiation protection ( ICNIRP )
“Guidelines for limiting exposure to time-varying electric and magnetic fields ( 1Hz-
100kHz )” : 2010.
b) IEEE International committee on Electromagnetic safety on non-ionising radiation
“IEEE standard for safety levels with respect to human exposure to electromagnetic
fields” :2002.
As ARPANSA directly references ICNIRP 2010 as a guideline for exposure, the ICNIRP
document will be used as the primary source for EMF levels in this report. It is noted that
the IEEE guidelines provide an alternate set of limits which could be applied to specialist
exposure environments.
The reference levels for EMF exposure as listed in the ICNIRP guidelines ( Table 5-2 and
Table 5-3 ENA Handbook ) are shown in Table 3 below.
Table 3 ICNIRP reference levels for 50Hz EMF exposure
ELECTRIC FIELD MAGNETIC FIELD
EXPOSURE TYPE STRENGTH STRENGTH
(V/m) ( mG )
Occupational ( General ) 10000 10000
Occupational ( head and torso) Not specified Not specified
Occupational ( arms and legs) Not specified Not specified
General public ( General ) 5000 2000
General public ( head and torso) Not specified Not specified
General public ( arms and legs) Not specified Not specified
Hollett Road EMF Study V1.0
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalVery large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.