ORDINARY MEETING AGENDA                                                    19 JANUARY 2017


              Compliance Certification Required for UPSS
        86.   Notwithstanding any other condition of this Decision Notice, a Certificate of
              Compliance issued by a suitably qualified person* must be provided to Council
              prior to commissioning the operation of the UPSS, that certifies the design,
              installation, construction and operation of the underground petroleum storage
              system (Service Station) complies in all respects with the conditions of this
              Decision Notice and any relevant Australian Standards, Standard Test
              Procedures and Codes referred to herein.
                    * A suitably qualified person is a Registered Professional Engineer of
                    Queensland with experience and knowledge in the design and operation of
                    the storage and dispensing of petroleum products and underground
                    petroleum storage systems.
              Air
        87.   Offensive odours, dust, smoke, fumes, particulates, or other contaminants likely
              to cause a nuisance must not be emitted beyond the boundaries of the premises.
        88.   Incineration or open burning is not permitted on the premises.
        89.   Offensive odours, dust, smoke, fumes, particulates, or other contaminants likely
              to cause a nuisance must not be emitted beyond the boundaries of the premises.
        90.   When requested by Council, an Air Quality Assessment Report (AQAR)
              characterising, monitoring and recording of nuisance emissions must be
              undertaken to investigate any complaint (other than a frivolous or vexatious
              complaint) caused by odours, dust, smoke, fumes, particulates or other
              contaminants from operations at the premises.
        91.   Such monitoring must be undertaken within a reasonable and practicable
              timeframe nominated by Council and be performed by a suitably qualified person
              in accordance with relevant guidelines and Standards. The report must be
              submitted to Council detailing the results of such monitoring and
              recommendations for control measures to eliminate nuisance air emissions from
              the operation of the premises.
              Outdoor Lighting
        92.   Lighting associated with the use must be designed, sited, installed and tested to
              comply with the Rubidium Light Cooroy Highway Service Station Lighting Plan
              Environmental Mitigation report of 13 October 2016 and conditions of this
              Decision Notice.
        93.   Certification must be submitted to Council from a qualified person which certifies
              that all outdoor lighting devices comply with the report at the time of
              commissioning.
        WASTE
              Waste Disposal
        94.   The developer must provide waste storage and disposal facilities in accordance
              with Planning Scheme Policy No. 9 “Waste Management Multi-Dwellings and
              Commercial and Industrial Premises”. The facilities must include an external
              impervious area correctly sized for all refuse and recycling containers and
              suitably screened from public places and neighbouring properties. A bin wash
              area is required with a cold-water tap, hose and drain outlet connected to sewer,
              via a bucket trap. The drain outlet must be designed to prevent storm water entry
              to the sewerage system. This can be achieved with a nib wall 50mm high and up
              to 700mm x 700mm wide (max 0.5m²), or alternatively the waste area can be
              roofed, or any other design approved by Council.

                                                                                 Page 18 of 25
Log in to download the original file

2017-01-19 Ordinary Meeting Agenda(PDF, 593KB).pdf · 607 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.