Appendix D Acoustic Report - 14-16 Mary Street, Noosaville - Bounce Hostels 15.6.2018

Attached to the e-mail Visitor Accommodation Type 4 Conventional - 122 beds (Engineering Report, Economic Study, Geotechnical Investigation, Flood Certificate, Accoustic Report, Management Plan) MCU18/0102.msg.

of 31

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

Visitor Accommodation, Noosaville                                                                               1142R1-R0




                     Figure 5:      Nearest potentially affected receivers to the Site

                     Noise levels were calculated using the inverse square law for geometric spreading,
                     and Maekawa’s equations for barrier insertion loss.
                     Most of the surrounding properties are 2-storey residential buildings.

        Air Conditioners
                     The general criteria in Section 3.2 and the measured ambient noise levels in
                     Section 4 provide site-specific criteria for noise from air conditioners as shown in
                     Table 5.
                     Table 5:       Site-Specific Criteria for Air Conditioning Plant

                      Period                      General Criterion                LA90    Site-Specific
                                                                                           Criterion
                      Day (7 am-6 pm)             ≤ background LA90 + 5dB(A)       30 dB   41 + 5 = 46 dB(A)
                      Evening (6 pm-10 pm)        ≤ background LA90 + 5dB(A)       28 dB   35 + 5 = 40 dB(A)
                      Night (10 pm-6 am)          ≤ background LA90 + 3dB(A)       27 dB   30 + 3 = 33 dB(A)

                     Air conditioning plant hasn’t been specified for the Site at this stage. However,
                     given the short distances to the Site boundaries from the Accommodation
                     Pavilions, it is recommended that external condenser units are located within the
                     undercover carpark.

        Refrigeration Plant
                     The general criteria in Section 3.2 and the measured ambient noise levels in
                     Section 4 provide site-specific criteria for noise from refrigeration plant as shown
                     in Table 6.




www.roadpro.net.au                                           21 March 2018                                     Page 8 of 11
Log in to download the original file

Appendix D Acoustic Report - 14-16 Mary Street, Noosaville - Bounce Hostels 15.6.2018.pdf · 5.4 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.