Appendix J - Water Supply and Wastewater Servicing Report
Lutheran Services Page 15 of 15
PF80 - Cooroy Care Farm
24 May 2018 Ref. No. 2017.0616
5.5 Design Details
The following system configuration is proposed. The system arrangement and indicative location
for the private pumping station is indicated in Appendix B – Figure B3.
Table 12 Wastewater System Configuration – Direct Connection to Unitywater Rising Main
Component Details
Wastewater collection system As required to carry wastewater from each
building to the central pumping station
Emergency storage Approx 24 hours storage (50 – 100 kL) to store
wastewater in the event of a problem with the
rising main connection
Wastewater pumping station Duty / standby submersible macerator sewage
pumps each capable of 1.5 to 2 L/s pumping
against the rising main pressure
Wastewater rising main to Unitywater Approx 50 mm diameter as required
rising main
Connection to Unitywater rising main To Unitywater requirements