47. As the site is proposed to be filled, appropriate stormwater drainage pipes shall be installed or
overland flowpaths created within the site to collect and discharge stormwater runoff from all
adjoining properties to prevent additional ponding/flooding on these properties.
48. All site stormwater drainage shall be by means of a gravity system.
49. All stormwater drainage lines including inter-allotment drainage shall be inspected by closed
circuit television (CCTV) prior to commencement of the approved Use.
CCTV inspection will be carried out by Council's CCTV contractor and arranged by Council
following satisfactory completion of construction works. The developer will be responsible for
the full cost of CCTV inspection, including any additional inspection necessary following defect
identification and rectification. This charge is payable prior to the issue of Operational Works
approval and will be determined on the unit rate basis current at the time of approval.
Surface Water Management
50. To ensure that polluted run-off does not enter Council’s stormwater drainage system or the
downstream ecosystem, stormwater run-off from the carparking areas and the driveways shall
be treated in accordance with an approved Surface Water Management Plan. The Cardno
Surface Water Management Plan dated 8 February 2008 shall be amended to reflect the
conditions of this approval and the modified layout approved herein. It shall also ensure that
there is a requirement for monitoring to be undertaken for a period of three years after the
commencement of the use and the results submitted for Council for their records in digital
form. The amended plan shall also include a method to effectively remove trash from the
stormwater system. Rectification measures for non-compliance with water quality objectives
shall be included in the Environmental Management Plan.
51. The amended Surface Water Management Plan shall demonstrate that the ecosystem located
downstream will not be adversely affected by water harvesting and detention proposed.
Sewer Mains
52. The site shall be connected to Council’s existing sewerage reticulation systems and be
constructed in accordance with Council’s standards and requirements at no cost to Council.
This may require the construction of sewer mains external to the site to connect to an
approved connection point.
53. Any existing sewer mains that traverse the site and are no longer required shall be removed
and capped in accordance with Council’s requirements.
Town Water Supply
54. The site shall be connected to Council’s existing town water supply and be constructed in
accordance with Council’s standards and requirements at no cost to Council.
55. The water connection to the water reticulation system shall extend to the property boundary
and be metered. All fees for the supply of water meters shall be paid to the Council.
56. The water meter must be located outside the property boundary and in an easily assessable
location to facilitate unhindered reading by Council and/or Council’s contracted water meter
readers, and not behind fences or locked gates. In this regard approval of the water meter
configuration and location must be obtained from Council’s Water & Sewerage Capital Works
Manager prior to lodgement and approval of hydraulic drawings.
Earthworks
57. Filling works required on site shall be carried out in accordance with Section 3.8 of Council’s
Engineering Design Standards Manual and so as not to cause the additional ponding of water
on any adjoining lands or the blockage of, or interference with, any natural watercourses.
Detailed site surveys indicating natural surface levels and contours of the adjoining properties
must be provided with the application for a Development Permit for Operational Works for
Filling and Drainage.
Page 7 of 19
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Decision Notice - 010.2007.00000256.001 [As Published]Related documentApplication case desk ↗
About this file
- File size
- 98 KB (small file)
- File type
No other editions are linked here.